NICE MC824HR30 Technical Manual
Overview of all three manuals · MC824HR30 · MC800 / MCA5 · Road RD400
Practical guide to the NICE MC824HR30 control unit
This guide is intended for MC824HR30, model MC824H, with an MCA1R30 board. It will help you choose accessories, connect the system, start it up for the first time, and troubleshoot a single- or double-leaf gate.
Before connecting, compare the label on the control unit with the manual. The NICE document covers both the MC824H and MC824L, but these units do not use the same motors. In the manufacturer's table, the MC824L is specified for the OLTRE1824, and its ENC inputs are not used. The following procedures and motor selections apply to the MC824H/MC824HR30.
- The supported operators are 24 V DC; the control unit is supplied with 230 V AC.
- In the diagram below, the photocells are connected using the BlueBUS system.
- M2 opens first; M1 closes first. M2 is used for a single-leaf gate.
- Select the motor type using the switches before running the travel learning procedure.
What do you need to sort out?
- Compatible operators and accessories
- Installation and wiring
- Terminals and wiring diagram
- BlueBUS photocells
- First startup and travel learning
- Manual adjustment of leaf positions
- Programming functions and parameters
- Receiver, antenna and remote controls
- Standby and backup battery
- Diagnostics and reset
- Final checks and maintenance
Compatible operators and accessories
Compatibility is not determined by the 24 V supply or the operator family name alone. The specific motor must be listed in the motor selection table and its switches must be set correctly.
| Group | Models listed by the manufacturer for the MC824H |
|---|---|
| Toona | TO4024, TO5024, TO5024I, TO7024 |
| Toona Hi-Speed | TO5024HS, TO6024HS |
| Hyppo | HY7024, HY7124 |
| Underground operators | MFAB3024, LFAB4024, BFAB5024 |
| Other high-speed operators | MFAB3024HS, LFAB4024HS, WG3524HS, TTN3724HS, TTN6024HS |
| Other models in the manual | MB4024, MB5024, XFAB2124, METROELITE, WINGOELITE |
The designations are taken from the manufacturer's Table 4. If the trade name differs or the motor is an older model, first verify its full type designation. For the specific switch settings, see Selecting the motor type.
Safety and signalling
- NICE EPMB – two-wire BlueBUS photocells. EPM or BF relay photocells are not connected according to this diagram.
- NICE ELDC – warning beacon listed in the MC824H technical specifications. The light supply and antenna connection are two separate circuits.
- Safety edges and STOP contacts – select NO, NC or 8.2 kΩ according to the wiring and the risks associated with the specific gate.
Control and backup
- NICE OXIBD – plug-in radio receiver for the SM connector. One example of a remote control for this receiver is NICE ON3EBD; choose the pairing method and communication mode according to the receiver manual.
- NICE EKS – key switch with momentary contacts. For SbS, OPEN or CLOSE, use a volt-free C–NO contact. A suitable button or control module relay can provide the same type of contact.
- NICE PSS324 – backup battery listed in the current manual. For the older NICE PS324 the specific conditions set out in the backup section.
- NICE IBT4N and NICE OVIEW – interface and programmer for accessing service settings via BusT4; connect and operate them according to their manuals.
Source: original NICE manual, Table 4; accessories in sections 4.2, 8 and 11.
Installing the control unit and wiring
Mount the box on a solid vertical surface so that its bottom edge is at least 40 cm above the ground. Prevent water from entering through the cable routes. According to the manufacturer, the side cable entry is intended only for a protected indoor environment; outdoors, use the prepared bottom entries with suitable cable glands.
| Purpose | Cable and maximum length |
|---|---|
| Control unit power supply | 3 × 1.5 mm²; up to 30 m. For lengths over 30 m, the manufacturer specifies 3 × 2.5 mm² and grounding at the automation system. |
| Each motor | 3 × 1.5 mm²; up to 10 m. |
| Encoder for each motor | 2 × 1 mm²; up to 10 m. According to the manual, the motor and encoder cables can be replaced with a single 5 × 1.5 mm² cable. |
| BlueBUS | 2 × 0.5 mm²; up to 20 m. For 20–40 m, use 2 × 1 mm². |
| Beacon | 2 × 0.5 mm²; up to 20 m. |
| Antenna | RG58 coaxial cable; up to 20 m, recommended length less than 5 m. |
| Key switch | 2 cables, 2 × 0.5 mm² or one 4 × 0.5 mm²; up to 50 m. |
| Electric lock | 2 × 1 mm²; up to 10 m. |
The specified cross-sections do not replace the design of the power supply circuit. The insulation type, cable routing, protective conductor and disconnecting device must be suitable for the environment and the specific installation.
Source: original NICE manual, Table 1 and Section 3.5.
MC824HR30 terminals and wiring diagram
Connect all conductors with both the mains and backup power supplies disconnected. The markings on the board are authoritative; terminal numbering from the MC424L, MC800 or RD400 does not apply here.
Original NICE diagram, Figure 8. TX and RX in this diagram are BlueBUS. The antenna connection to the board shown here applies to OXI; with OXIBD, the antenna connects directly to the receiver, as shown in the separate section on the radio. Click to enlarge the image.
| Terminal | Function |
|---|---|
| L / N / PE | 230 V AC mains supply and protective earthing as marked in the power supply section. Do not connect to low-voltage inputs. |
| M1 + ENC1 | Motor for the gate leaf that moves first when closing, and its encoder. |
| M2 + ENC2 | Motor for the gate leaf that moves first when opening, and its encoder. For a single-leaf gate, connect the motor to M2; leave M1 unused. |
| FLASH | Flashing light output; in flashing-light mode, 12 V DC, max. 21 W. The manufacturer specifies NICE ELDC. This is not a 230 V output. |
| ELS | Electric lock output, 12 V AC, max. 15 VA. Changing the function to lighting also changes the electrical output parameters. |
| OGI | Open gate indicator: 24 V, max. 4 W; voltage may vary by −30 to +50%. |
| BlueBUS | Two wires for both power and communication with compatible devices; connect in parallel, with no polarity requirement. |
| STOP | Safety input for NO, NC or 8.2 kΩ. The control unit stores the connected state during learning; any change triggers a stop and a brief reverse movement. |
| SbS / OPEN / CLOSE | Control inputs for voltage-free NO contacts: step-by-step, open and close. Do not apply an external voltage to them. |
| SM / IBT4N | Plug-in receiver connector / service interface connector. Connect accessories with the power supply disconnected. |
Motors and encoders
Each encoder must be matched to the correct motor. Polarity does not matter at the two-wire ENC input. If learning indicates that the leaves are in the wrong order, swap their encoders as well as the motors. The protective conductor must not be confused with the motor conductors.
Push button and key switch
For standard control, connect an NO contact to the pair of SbS terminals. For the NICE EKS switch, use the C and NO contacts of the selected microswitch. The command sequence is determined by parameter L2 in the second level. Separate commands can be connected to OPEN and CLOSE. Function L7 in the first level can change the CLOSE input to partial opening.
STOP safety input
Multiple NO contacts are wired in parallel, and multiple NC contacts in series. Combinations with 8.2 kΩ safety edges have specific requirements; wire them according to Section 4.2.2 and the edge manufacturer's instructions. Do not disable a safety device by bridging it as a way of resolving a fault.
Source: original NICE manual, Figure 8, Table 2 and Note 1 under Table 14.
BlueBUS photocells
For a basic pair, use a compatible TX transmitter and RX receiver, for example NICE EPMB. Connect both using two wires in parallel to BlueBUS. These are not relay-type photocells with COM/NC contacts; wiring for EPM or BF from another control unit does not apply here.
- Position TX and RX opposite each other to suit the protected area.
- Set the addressing jumpers according to the required function. TX and RX in one pair must have the same address; the next pair must have a different one.
- Connect both BlueBUS wires; polarity does not matter.
- Run the learning procedure for connected devices and test each pair while the gate is moving.
| Address | Response according to the MC824H manual |
|---|---|
| FOTO / FOTO II | Protection during closing: stop and reverse movement. |
| FOTO 1 / FOTO 1 II | During closing, stop and reverse; during opening, stop and resume once the beam is clear. |
| FOTO 2 / FOTO 2 II | Protection during opening: stop and reverse movement. |
| FOTO 3 | This configuration is not permitted for this control unit. |
Check the exact jumper positions in Table 3 of the MC824H manual and in the instructions for the specific photocells. Repeat the learning procedure whenever a device is added or removed. When replacing a device, also follow the instructions for that accessory.
Initial startup and learning the gate travel
1. Select the motor type
With the power disconnected, set the selector to match the exact drive model. Complete this setting before learning the mechanical stops. Use only the combination specified by the manufacturer.
Excerpt from Table 4 of the current Slovak manual: MC824H rows only. Determine the black and white switch positions according to the ON marking in the diagram and on the actual selector. Click to enlarge the image.
2. Check the mechanics and switch on for the first time
Check the stops, free movement and drive release according to the relevant instructions. After power-up, the BlueBUS LED should flash regularly about once per second, the photocell TX/RX LEDs should flash, and the flashing light should be off. If anything differs, disconnect the power and check the wiring.
3. Learn the connected devices
Figure 13: controls for recognizing BlueBUS and STOP. Click to enlarge the image.
- Press and hold Open ▲ + Stop/Set.
- When L1 and L2 start flashing rapidly, after about 3 seconds, release the buttons.
- Wait for the procedure to finish. The STOP LED should be on, and L1 and L2 should be off. L3 and L4 may indicate that the travel still needs to be learned.
This step is necessary even if no devices are connected to BlueBUS or STOP.
4. Automatically learn the mechanical stops
- Press and hold Stop/Set + Close ▼.
- Release the buttons only when L3 and L4 flash rapidly, after approximately 5 seconds. Releasing earlier, when L1 flashes, starts manual learning.
- Check the movement sequence: M1 closes slowly, then M2 closes slowly, then M2 and M1 open slowly to the stops, and finally both leaves close quickly.
- When learning is completed correctly, L3 and L4 go out. Test opening and closing separately using the buttons.
If the direction or sequence is incorrect: stop the learning process using the Open or Close button. Disconnect all power before correcting the wiring. If the leaves are swapped, correct both M1/M2 and the corresponding ENC connections; if the direction is reversed, correct only the motor wires according to the original wiring diagram. Then repeat the learning process. Activation of the photocell or STOP interrupts the learning process.
You do not need to erase the entire memory as a precaution before repeating the learning process.
Source: original NICE manual, chapters 4.5 to 4.8.1.
Manually fine-tuning leaf positions
If automatic learning is not suitable for the gate geometry, the positions can be learned manually. In mixed mode, automatic learning is performed first, followed by fine-tuning of selected intermediate positions. The mechanical end positions 0 and 1 are not changed in mixed mode.
Figure 15: SA and SC define the timing of the leaf movements; A is the required open position. Click the image to enlarge it.
| LEDs during manual learning | Position |
|---|---|
| L1 | M1 mechanical closing stop (0). |
| L2 | M2 mechanical closing stop (0). |
| L3 | SA: M2 position after which M1 starts moving during opening. |
| L4 | Required open position A for motor M1. |
| L5 | Required open position A for motor M2. |
| L6 | SC: M1 position after which M2 starts closing during the closing cycle. |
| L7 | M1 mechanical opening stop (1). |
| L8 | M2 mechanical opening stop (1). |
To enter manual learning, hold Stop/Set + Close and release when L1 flashes, after approximately 3 seconds. Briefly press Open/Close to select a position; press and hold to move the corresponding motor. Save the position by holding Stop/Set for at least 3 seconds; then move to the next one. Wait no longer than 10 seconds between steps.
Single-leaf gates have a special procedure for skipping unused positions. The detailed sequence for one- and two-motor setups is in chapters 4.8.2 and 4.8.3, pages 11–12. Do not confuse the positions and LEDs with the MC800 table.
Programming functions and parameters
The Open ▲ and Close ▼ buttons select an item; Stop/Set confirms or changes a setting. Level I switches a function on or off; Level II sets its value. For example, L1 at Level I enables automatic closing, while L1 at Level II sets the pause duration.
Level I – switching on and off
- With the gate stationary, hold Stop/Set until L1 starts flashing, then release it.
- Use Open/Close to select the required LED.
- Briefly press Stop/Set to toggle the state: short flash = OFF, long flash = ON.
- When finished, do not press anything; wait for programming to end.
| LED / function | What it changes |
|---|---|
| L1 – automatic closing | After opening, the set pause countdown starts, followed by closing. |
| L2 – closing after photocell activation | Changes the closing behavior after the photocells are triggered. When automatic closing is enabled, it shortens the pause to 5 s; if L1 is not enabled, a photocell trigger may still start automatic closing after the set pause. Check the behavior against Table 6. |
| L3 – always close | After power is restored, an open gate may close automatically; warning lights flash before it starts moving. |
| L4 – Standby all | Energy-saving mode, enabled by default. Battery-related conditions are described below. |
| L5 – lock / lighting | Changes ELS from an electric lock output to an auxiliary lighting output. Before changing it, check that the connected load is suitable. |
| L6 – pre-flashing | The warning light starts flashing 3 s before movement. |
| L7 – CLOSE / partial opening | Changes the CLOSE input to a Partial Open 1 command. |
| L8 – OGI / maintenance | Changes the open-gate indicator output to a maintenance signal; see chapter 6.4.2 for the maintenance signal settings. |
Level II – setting a value
- Hold Stop/Set until L1 flashes, then release it. Use Open/Close to select a parameter.
- Press and hold Stop/Set again. After about 3 seconds, the LED for the current value lights up.
- Continue holding Stop/Set and use Open/Close to select a value.
- Release Stop/Set and wait for the mode to end. Then test the function.
| Input LED | Parameter and available values |
|---|---|
| L1 – pause duration | L1–L8: 5 / 15 / 30 / 45 / 60 / 80 / 120 / 180 s. Factory setting: 30 s. |
| L2 – step-by-step mode | L1: open–stop–close–stop; L2: open–stop–close–open; L3: open–close. Other modes include condominium and hold-to-run control; see Table 7. |
| L3 – speed | Six speed levels and two combinations with different opening and closing speeds. After changing the setting, check that operation remains safe. |
| L4 – release after closing | L1: no release; L2–L8: progressively greater brief reverse movement to release residual pressure. |
| L5 – motor force | L1: minimum; L8: maximum. Increasing force is not a substitute for correcting mechanical resistance; the result must be checked and measured by a technician. |
| L6 – partial opening | L1–L4: open M2 by ¼, ½, ¾ or fully. L5–L8: both motors open by ¼, ½, ¾ or fully, whichever is less of their configured opening distances. |
| L7 – maintenance interval | L1–L8: 500 / 1 000 / 1 500 / 2 500 / 5 000 / 10 000 / 15 000 / 20 000 cycles. |
| L8 – fault history | Record of the last eight cycles; L1 is the most recent. |
Example – closing after 60 seconds: enable L1 at Level I. Then, at Level II, enter parameter L1 and select value L5. If the photocell closing function is also enabled, the pause may be shortened.
Do not wait unnecessarily between programming steps. Chapter 6, Tables 6 and 7, gives the full definitions of the modes and explains how they interact.
Radio receiver, antenna and remote controls
Remote control operation depends on the receiver installed. For the plug-in NICE OXIBD use the SM connector. According to the current manual, the radio-symbol button on the MC824H control panel is not used; pair remotes using the appropriate receiver, following its instructions.
For the OXIBD receiver, our range includes, for example, the remote control NICE ON3EBD. When expanding an existing setup, also check the coding and receiver mode already in use; matching frequencies alone are not enough.
Figure 25 in the current manual. For the OXIBD, connect the external antenna with RG58 coaxial cable directly to receiver terminals 1 and 2, not to the control board’s antenna terminal. Click the image to enlarge it.
Choose the procedure for storing the remote control according to the specific receiver in the NICE remote control pairing guide. Adding a remote control does not require erasing the control unit’s travel settings.
Source: original NICE manual, section 8.1.
Standby and backup power
Function L4 in level I puts BlueBUS and most indicator LEDs to sleep about 5 minutes after a completed operation. BlueBUS flashes more slowly. Operation resumes with a short delay when a command is received. This state alone does not indicate a fault.
| Battery | Connection requirements |
|---|---|
| PSS324 | The current type specified by the manufacturer. Use the relevant manual and the cable supplied for this setup; NICE PSS324 details. |
| Older PS324 | Use NICE CABLA11 and disable Standby (L4 = OFF). The adapter alone is not enough. Expect higher power consumption. |
Connect the battery only when the mains power is disconnected. Charging takes priority over entering energy-saving mode. The radio receiver, service interface and continuously powered accessories can increase power consumption; the catalog figure without accessories cannot be applied to every setup.
Solemyo: the manual specifies solar power via the battery connector. Standby All must be enabled, and connecting the mains supply at the same time is prohibited. Check the specific solar setup and its wiring separately; the requirements for the older PS324 do not automatically apply to it.
Source: original NICE manual, sections 8.3 and 8.4.
Diagnostics and troubleshooting common problems
First, note the LED status and the number of short flashes from the warning light. The fault sequence repeats twice, with a pause of about one second. Resetting as a first step may erase useful settings without resolving the cause of the fault.
| Short flashes | Meaning and initial check |
|---|---|
| 1 | BlueBUS device mismatch. Check the connections and addresses; after changing the setup, run device learning. |
| 2 | Photocell triggered. Check for obstructions, cleanliness and correct alignment of the TX/RX units. |
| 3 | Obstacle detected based on force. First check for mechanical resistance and ensure free movement. |
| 4 | STOP input active. Check the safety device and its wiring. |
| 5 / 7 | Internal parameter / electrical circuit fault. Wait at least 30 seconds; if the fault recurs, service is required. |
| 6 | The number of operations per hour or continuous operations has been exceeded. Let the system rest for a few minutes. |
| 8 | A continuously active command is blocking further commands. Check the button, relay or timer control. |
| 9 | The automation system is locked by a command. The appropriate command is required to unlock it. |
| 10 | Obstacle or increased resistance detected by the MC824H encoder. Check the mechanism and that the correct encoder is connected to the motor. |
What the LEDs on the board indicate
| Indicator | Meaning |
|---|---|
| BlueBUS once per second | Normal operation. Slower flashing after inactivity may indicate Standby. |
| BlueBUS – two quick flashes | An input change or command received; this is not a fault by itself. |
| STOP on / off | On: the learned safety status is OK. Off: check STOP and the connected devices. |
| SbS / OPEN / CLOSE on | The corresponding control input is active. Steady illumination without a command may explain why the controls are blocked. |
| L1 + L2 flashing slowly | The connected devices must be recognized. |
| L3 + L4 flashing slowly | The travel has not been learned, or the motor selector setting was changed after learning. Check the selector and repeat the relevant learning procedure. |
| Neither LED nor BlueBUS is lit | Check the power supply and fuses. The MC824H has a 15 A motor fuse and an F 2 A service fuse; check the rating and type on the board. Do not replace a fuse with one of a higher rating. |
The gate works with the buttons but not with the remote control
Check the power supply and installation of the radio receiver, remote-control compatibility, its battery and whether it has been stored in memory. If the range is poor, also check where the antenna is connected. First distinguish a radio problem from a control unit problem.
History of the last eight operations
At level II, select L8 and hold Stop/Set. Once L1 lights up, use Open/Close to select a record; L1 indicates the most recent one. Interpret the number of flashes using the diagnostics above. For the detailed procedure, see section 7.3.
Erasing the control unit’s memory
This erases the individual settings. Press and hold Open + Close together until L1 and L2 start flashing, then release the buttons. The setup and safety tests must then be carried out again. Do not confuse this procedure with erasing the memory of the plug-in radio receiver.
Source: original NICE manual, section 7; reset in section 6.5 and fuses on page 4.
Final checks and maintenance
- Test opening, closing and stopping with every control device used.
- Check the leaf sequence, stops, acceleration and deceleration. The leaves must not collide or bind mechanically.
- Test each pair of photocells, safety edge and STOP separately, including their response during movement.
- After adjusting force or speed, verify safety and carry out any required force measurements.
- If a battery is connected, check operation during a mains failure and that power is restored correctly.
- The owner must receive the operating instructions, the manual release procedure for the specific operators and a maintenance schedule.
Check the entire automation system at least every 6 months, or more often depending on usage. In the event of a power failure, release the operators themselves according to their instructions; the MC824HR30 control unit has no mechanical release key of its own.
Source: original NICE manual, section 5; routine maintenance in section 9.
Information for technical support
When troubleshooting, provide the model of the control unit and both motors, the type of photocells and receiver, the LED status, the number of flashes and the step at which the problem occurs. A photo of the complete wiring and a close-up of the label are also useful.
Overview of all three guides · MC824HR30 · MC800 / MCA5 · Road RD400
Source: NICE MC824H/MC824L, IS0606A01, revision 21. 4. 2026; this manual applies to MC824HR30.