NICE EPMB - Era Photocell Medium - photocells with BlueBUS wiring (1 pair)
| Product availability: | In stock | We normally dispatch goods within 24 hours. |
|---|
in stock
€50.90 including VAT
| Weight |
|---|
| 0,20 kg |
Description of NICE EPMB - Era Photocell Medium - photocells with BlueBUS wiring (1 pair)
Fully compatible successor NICE MOFB photocells.
Outdoor safety photocells NICE EPMB (Technical specifications) are installed opposite each other across the gate opening, or at any point where there is a risk of the gate hitting an obstacle. They create an infrared beam along the optical axis; when it is interrupted, they send a signal to stop the gate. They can only be used with devices that support NICE BlueBUS.
Installing NICE EPMB photocells
| 1. Open the photocell | 1a. Remove the transparent cover |
|---|---|
![]() |
![]() |
| 2. Pull out the electronics as shown by the arrows | 3. Punch out the holes needed for installation |
![]() |
![]() |
| 4. Punch out the required cable entry | 5. Refer to the example layouts, to determine how to position the photocells at the installation site. |
![]() |
|
| 6. Based on the position of the photocells at the installation site, set the address jumpers according to the table. | 7. Position the photocells directly opposite each other |
![]() |
![]() |
| 8. Mount the photocell housings on a wall or post | 9. Connect the photocell wiring (make sure to disconnect the power supply first) |
![]() |
![]() |
| 10. Fit the connected photocell electronics into the housings and restore the power supply. Run the connected-device detection phase on the drive control unit. | 11. Test the photocells. If you encounter a problem, follow the troubleshooting guide |
![]() |
![]() |
| 12. Fit the cover onto the photocell and secure it with screws. Remember the insulating rubber gasket | 13. Fit the transparent cover. Remember the insulating rubber gasket. |
![]() |
![]() |
Connecting multiple pairs of photocells NICE EPMB to the data network NICE BlueBUS
Position the photocells around the gate or door according to the example layouts for the complete wiring setup and set the jumpers according to the jumper table for the NICE EPMB gate drive. To prevent interference between pairs installed close to one another, the orientation of the transmitters and receivers must follow these example layouts, as shown in these example layouts TX and receivers RX. Connect the photocells in parallel as shown (polarity does not need to be observed):
If you need the photocells to open the gate (see FA1 and FA2 in the example layouts), i.e. when a vehicle passes between their optical axes, triggering the gate to open, you need to interrupt connection A on both the transmitter TX and receiver RX, see illustration:
Examples of complete wiring configurations for multiple pairs of NICE photocells EPMB drive
1. Single-leaf sliding gate
2. Two synchronised sliding gates facing each other
3. Swing gate
4. Sectional garage door
5. Up-and-over garage door
NICE photocell jumper table EPMB gate drive
![]() |
Connecting multiple pairs of photocells to the system BlueBUS is done by setting different jumper combinations, with each connected pair requiring a unique jumper configuration. Make sure that no two pairs have the same configuration on a single BlueBUS data network. For each pair of photocells, set the jumper on both the transmitter (TX) and receiver (RX) to the same position. If the jumper configuration requires only one or no jumpers, keep any unused jumpers for future use. |
| Photocell pair designation | Jumper setting using a combination of jumpers |
|---|---|
| FOTO | ![]() |
| FOTO II | ![]() |
| FOTO 1 | ![]() |
| FOTO 1 II | ![]() |
| FOTO 2 | ![]() |
| FOTO 2 II | ![]() |
| FOTO 3 | ![]() |
|
FA1 |
![]() |
|
FA2 |
![]() |
If a photocell needs to be replaced for any reason, simply set the same jumper as on the original one; there is no need to run the device recognition procedure.
Checking operation and troubleshooting NICE EPMB photocell wiring EPMB
![]() |
After the drive has completed device recognition, check that the LED on both the TX transmitter and RX receiver is flashing. The LED may flash in the following ways: |
| LED "L" | Status | What to do |
|---|---|---|
| Off | The photocell is not receiving power or is faulty. | Check that the voltage at the photocell inputs is approximately 8–12V. If the voltage is correct, the photocells are probably faulty. |
| 3 quick flashes followed by a one-second pause | The device has not been recognised by the drive control unit. | Repeat the recognition procedure on the control unit. Make sure that each pair of photocells has a unique address assigned using jumpers . |
| Very slow flashing | The TX transmitter is transmitting regularly The RX receiver is receiving an excellent signal |
Normal operation |
| Slow flashing | The RX receiver is receiving a good signal | Normal operation |
| Fast flashing | The RX receiver is receiving a weak signal | Normal operation. However, it is best to check the alignment of the TX transmitter and RX receiver and make sure the covers are clean. |
| Very fast flashing | The RX receiver is receiving a very weak signal | Operation is still normal, but marginal. It is best to check the alignment of the TX transmitter and RX receiver and make sure the covers are clean. |
| On | The RX receiver is not receiving a signal | Make sure the LED on the TX is flashing slowly. Check that there is no obstruction in the optical path between the TX transmitter and RX receiver. Check the alignment of the TX and RX. |
NICE EPMB photocell technical specifications EPMB
| Product type | Detector for automatic swing gates, sliding gates and garage doors, Type D according to EN 12453, consisting of a transmitter TX and receiver RX. |
|---|---|
| Technology | Direct optical TX-RX modulation with a modulated infrared beam. |
| Power supply/Output | The device can only be connected to a data network that supports the NICE BlueBUS, from which it receives electrical power and sends an output signal. |
| Absorption | 1 BlueBUS unit |
| Detection capability | Opaque objects larger than 50 mm passing across the optical axis between the TX transmitter and RX receiver at speeds below 1.6 m/s. |
| TX transmitter angle | 20° +-25% |
| RX receiver angle | 8° +-25% |
| Normal range (usable) | 15 m (may be halved in adverse weather conditions, e.g. fog, rain, dust, etc.) |
| Maximum range | 30 m |
| Addressing | 7 pairs with a safety function and 2 pairs with an "Open" command function |
| Use in acidic or saline environments, or in environments with an increased risk of explosion | No |
| Installation | Vertical wall mounting; maximum cable length for one branch of the BlueBUS system is 50 m. |
| Protection rating | IP44 |
| Operating temperature | -20°C to 55°C |
| Dimensions (W×H×D) | 50x80x28.5mm (one photocell) |
| Weight | 143g (photocells combined) |
Photocell wiring NICE EPMB with operator NICE Robus 400, 600, 1000
Inside the photocells NICE EPMB for gate operators