NICE MOFB - Moon Photocells - photocells with BlueBUS wiring, (1 pair)
| Product availability: | Unavailable | We’ll be happy to help you choose a replacement. Feel free to contact us. |
|---|
Description of NICE MOFB - Moon Photocells - photocells with BlueBUS wiring, (1 pair)
NICE MOFB photocells are no longer manufactured. They have been replaced by their successor, NICE EPMB, which have the same internal electronics (you do not need to replace the entire photocells; simply transfer the electronics from the new photocells to the old ones).
Other photocells compatible with the NICE MOFB model are the design variants NICE EPSB and NICE EPLB.
Replacement covers for the photocells are available to buy: NICE-ND-PRB-MOFB
Outdoor safety photocells NICE MOFB (technical specifications) are installed opposite each other across the gate opening, or at any point where there is a risk of the gate hitting an obstacle. They create an infrared beam along the optical axis; when it is interrupted, they send a signal to stop the gate. They can only be used with devices that support NICE BlueBUS.
They consist of two synchronised components: a TX transmitter and an RX receiver.
Installing NICE MOFB photocells
1. Mount the photocells on a wall, masonry wall, post, or any suitable surface (surface mounting), at the same height and facing each other along the same axis. The mounting surface must be flat so the photocells can be easily aligned:
2. Then connect the photocells according to the wiring diagram supplied with your gate operator or control unit (see wiring diagram for NICE Robus 400, 600, 1000 - control unit RBA3).
3. Run the procedure for detecting connected devices (this procedure is supported by every gate operator or control unit with a BlueBUS).
4. To test that the wiring is correct, refer to the chapter Checking operation and troubleshooting, or continue below for information on connecting multiple pairs of photocells:
Connecting multiple pairs of photocells NICE MOFB to the NICE BlueBUS
Position the photocells around the gate or gates according to the example configurations for a complete installation and set the jumpers according to the jumper table for the NICE MOFB gate operator. To prevent interference between pairs positioned close to one another, make sure to follow these example configurations, and observe the orientation of the transmitters TX and receivers RX. Connect the photocells in parallel as shown in the diagram (polarity does not need to be observed):
If you need the photocells to operate as gate openers (see FA1 and FA2 in the example configurations), i.e. to open the gate when a vehicle passes between their optical axes, you must break connection A on both the TX transmitter and the RX, see diagram:
Example configurations for fully connecting multiple pairs of NICE MOFB photocells to a gate operator
1. Single-leaf sliding gate
2. Two synchronised sliding gates facing each other
3. Swing gate
4. Sectional garage door
5. Up-and-over garage door
Jumper table for NICE MOFB photocells on a gate operator
|
Connecting multiple pairs of photocells to the BlueBUS system is done by setting different jumper combinations, with each connected pair requiring a unique jumper combination. Make sure that no two pairs in the same BlueBUS data network use the same combination. For each pair of photocells, set the same jumper value on both the TX transmitter and the RX receiver. If the jumper setting uses only one jumper, always place the other one in the unused jumper compartment, as shown in the picture on the left. |
| Photocell pair designation | Jumper setting using a combination of jumpers |
|---|---|
| FOTO | ![]() |
| FOTO II | ![]() |
| FOTO 1 | ![]() |
| FOTO 1 II | ![]() |
| FOTO 2 | ![]() |
| FOTO 2 II | ![]() |
| FOTO 3 | ![]() |
|
FA1 |
![]() |
|
FA2 |
![]() |
If a photocell needs to be replaced for any reason, simply set it to the same jumper setting as the original one; there is no need to carry out the device recognition phase.
Checking operation and troubleshooting NICE MOFB photocell wiring
![]() |
After the operator's device recognition phase, check that the LED on both the TX transmitter and RX receiver is flashing. The LED may flash in the following ways: |
| LED “L” | Status | What to do |
|---|---|---|
| Off | The photocell is not receiving power or is faulty. | Check that the voltage at the photocell inputs is approximately 8–12 V. If the voltage is correct, the photocells are probably faulty. |
| 3 quick flashes followed by a one-second pause | The device has not been recognized by the operator's control unit. | Repeat the recognition phase on the control unit. Make sure each pair of photocells has a unique address assigned using jumpers . |
| Very slow flashing | The TX transmitter is transmitting regularly The RX receiver is receiving an excellent signal |
Normal operation |
| Slow flashing | The RX receiver is receiving a good signal | Normal operation |
| Fast flashing | The RX receiver is receiving a weak signal | Normal operation. However, it is best to check that the TX transmitter and RX receiver are aligned and that their covers are clean. |
| Very fast flashing | The RX receiver is receiving a very weak signal | Operation is still normal, but only just. It is best to check that the TX transmitter and RX receiver are aligned and that their covers are clean. |
| On | The RX receiver is not receiving any signal | Make sure the LED on the TX is flashing slowly. Check that there is no obstruction in the optical path between the TX transmitter and RX receiver. Check the alignment of the TX and RX. |
NICE MOFB photocell technical specifications
| Product type | Detector for automatic swing gates, sliding gates and garage doors, type D according to EN 12453, consisting of a transmitter TX and a receiver RX. |
|---|---|
| Technology | Direct TX–RX optical interpolation with a modulated infrared beam. |
| Power supply/output | The device can only be connected to a data network that supports the NICE BlueBUS, from which it receives electrical power and sends an output signal. |
| Current consumption | 1 BlueBUS unit |
| Detection capability | Opaque objects larger than 50 mm passing through the optical axis between the TX transmitter and RX receiver at a speed below 1.6 m/s. |
| TX transmitter beam angle | 20° +-25% |
| RX receiver angle | Approximately 20° |
| Standard range | 15 m with maximum TX transmitter and RX receiver axis deviation of +-5%, even in adverse weather conditions |
| Maximum range | 30 m with maximum TX transmitter and RX receiver axis deviation of +-5% in excellent weather conditions |
| Addressing | 7 pairs with a safety function and 2 pairs with an “Open” command function |
| Use in acidic or salty environments, or in environments with an increased risk of explosion | No |
| Installation | Vertical wall mounting |
| Protection rating | IP55 |
| Operating temperature | -20°C to 55°C |
| Dimensions | 69x78x25mm |
| Weight | 50g |
Photocell wiring NICE MOFB with the operator NICE Robus 400, 600, 1000
Photocell interior NICE MOFB for gate operators