NICE Hyppo 7100 HY7124 – operator for double-leaf folding gates
| Product availability: | for the question | The product may not be available, contact us for more information. |
|---|
for the question
€468.38 including VAT
| Weight |
|---|
| 13 kg |
Description of NICE Hyppo 7100 HY7124 – operator for double-leaf folding gates
For the swing gate operator NICE Hyppo HY7124 with control unit version R30 (MC842HR30) to connect a backup power supply PS124 or PS324 a cable reducer must be used CABLA11.
NICE HYPPO HY7124 – folding gate operator
NICE HYPPO HY7124 is a standalone electromechanical motor with a telescopic arm for a folding gate. The motor operates on 24 V DC and is non-reversible. It requires a separate control unit, power supply and safety devices. In the event of a power failure, it can be released using a key.
When to choose this operator
The HY7124 is designed for folding-gate constructions with a telescopic arm. Before choosing an operator, check the dimensions and weight of each section, the position of the vertical hinges, resistance to movement, folding clearance and how the motor will be mounted.
| Folding gate section length | Maximum 1,500 mm per section, according to the installation diagram. |
|---|---|
| Weight and length | The maximum weight is 200 kg, but the permitted weight decreases as the length increases. At a length of 1.5 m, the curve is below 150 kg. |
| Duty cycle | 80%; assess suitability for the intended operating frequency based on the complete system. |
1.5 m and 200 kg are not a permitted combination at the same time. In the graph, the horizontal axis shows the section length in metres and the vertical axis shows the weight in kilograms; the area above the curve marked “Ne” is not permitted. This value does not indicate the load capacity of the entire passage or the combined weight of all sections. With solid infill and wind exposure, assess the load on the entire gate. The duty-cycle percentage is not the number of opening cycles per hour.
How a folding gate works
In the configuration shown, one motor moves one pair of folding sections. The motor is mounted on the first section of the folding pair; the telescopic arm connects the mechanism to the second section. A gate with two folding halves requires two motors and a compatible shared control system. So do not confuse the number of sections with the number of motors.
In the diagram:
- 1 – photocell post
- 2 – photocell
- 3 – key switch or keypad
- 4 – control unit
- 5 – warning light
- 6 – antenna
- 7 – HYPPO motor
- 8 – power supply
- 9 – release.
The drawing shows the system layout in principle; select accessories according to the control unit installed.
Standalone motor and control unit
This product page is for a standalone HY7124 motor with a telescopic arm. The control unit is not built into the motor. Select the control unit, safety devices, receiver and controls to suit the specific system. Check availability and the supplied equipment before ordering.
| Model | Motor and sensing | Suitable current control unit |
|---|---|---|
| HYPPO HY7124 | 24 V DC; magnetic encoder. | MC824HR30 / MCA1R30 |
The following wiring and initial start-up instructions apply to the MC824HR30 / MCA1R30. For an existing automation system, always follow the manual for the control board actually installed. The motor voltage and the control unit’s mains supply are separate circuits.
For an older MC824H/MC824HR10, use its own manual. The current MC824HR30 has its own procedures and backup power requirements. The MC824L is not a replacement for the HY7124 motor with encoder.
Installing the telescopic operator
Before starting work, disconnect the mains and any backup power supply, and secure the gate sections to prevent unintended movement.
- Check the strength of both sections and the hinges. The complete folding pair must move smoothly by hand throughout its full travel, without sticking or excessive play.
- Install solid mechanical stops for the open and closed positions, suitable for the chosen construction and control-unit learning procedure.
- Assess potential crush points at the end and centre hinges, between the folding sections and around the telescopic arm. Position the safety devices based on the gate’s full range of movement.
- The motor, arm, cables and release mechanism must not hit the frame, wall or other section. Fasten them to a load-bearing part of the structure.
Folding-section dimensions and mounting points
| Both sections shown | Each no more than 1,500 mm; this is not the permitted length for a single, rigid gate leaf. |
|---|---|
| Dimension at the centre hinge on the motor side | Max. 200 mm, at the position shown in the diagram. |
| Dimension at the telescopic arm mounting point | Min. 150 mm, at the position shown in the diagram. |
The 200 and 150 mm values apply to specific points in the drawing. They are not the post cross-section or a universal distance from the motor to the edge. During installation, follow the geometry shown for the telescopic arm and folding sections.
Mounting plate and telescopic arm
- Determine whether to install on the left or right when viewed from the inside. Before fastening, assess the full movement of both sections.
- Motor mounting plate A and front bracket B position them as shown in the folding-gate drawing. A/B here identify the mounting parts, not the dimensions in the articulated-arm table.
- Bolt the motor to the mounting plate. To suit the installation side, the plate can be rotated 180° as shown in the installation diagram.
- Assemble the telescopic arm with washers and fasteners as shown in the drawing. Lubricate the screws before assembly as instructed.
- With the motor disengaged, manually test the full travel. Correct minor alignment deviations using the slotted holes, then fully tighten the fasteners.
Cover and cables
The cable run to the motor on the moving section must remain protected even when the gate is fully folded. Allow sufficient cable slack and strain relief; the cable must not catch on the hinge or arm. After completing the adjustments, secure the cover and handle and check the cable glands.
Manual release
- Stop the automation, disconnect the power supply, and secure the folding sections against unintended movement.
- Slide the lock cover upwards, insert the key, and turn it clockwise.
- Turn the handle as shown, then move the gate manually. Keep hands clear of the hinges and the gap between the folding sections.
- Before operating automatically, return the handle to the locked upright position, check that the drive is engaged, remove the key, and close the lock cover.
If there is no other access, arrange for release from the outside during installation. NICE KIO with KA1 cable choose according to the specific installation; test the entire assembly before handover.
Accessories for the selected control unit
The motor alone does not replace the control unit or safety devices. The positioning of photocells and safety edges must also take into account the folding sections and the space between them.
| Component | Selection | What to look out for |
|---|---|---|
| Control unit | MC824HR30 | Separate control for one or two motors; select according to voltage and position sensing. |
| Photocells | EPMB | BlueBUS is polarity-free; use relay-type EPM only with a control unit connection it supports. |
| Flashing light | ELDC | 12 V DC FLASH with MC824HR30. |
| Backup power | PSS324; CABLA11 | For MC824HR30, use the current PSS324; the older PS324 uses CABLA11 with Standby OFF. |
| Receiver and remote controls | OXIBD, MYGO4 | SM plug-in receiver; the remote control must use a coding system compatible with the receiver. |
| Key switch | EKS | Voltage-free C–NO contact to the command input; do not apply an external voltage. |
| Electric lock | PLA10, PLA11 | For a suitable locking arrangement; ELS output 12 V AC, max. 15 VA. |
| External release | KIO + KA1 | Access to manual release in the event of a power failure. |
Wiring and electrical connection
Route and protect mains wiring, motor cables, and low-voltage signal cables according to their voltage and environment. The supply to the control unit comprises L, N, and PE; protect it with suitable overcurrent protection and a device for complete disconnection. Secure the cables with cable glands and strain relief.
| Circuit | Cable | Application |
|---|---|---|
| Supply to control unit | 3 × 1.5 mm² | Up to 30 m; L, N, and PE. For longer supply runs, use 3 × 2.5 mm² and protective earthing at the automation system as instructed in the control unit manual. |
| Motor | 3 × 1.5 mm² | Up to 10 m; two motor power conductors and a PE protective conductor. |
| Encoder | 2 × 1 mm² | Up to 10 m, polarity-free; for the corresponding motor. |
| BlueBUS | 2 × 0.5 mm² | Up to 20 m; for runs over 20 m and up to 40 m, use 2 × 1 mm². |
| Flashing light | 2 × 0.5 mm² | Up to 20 m, low-voltage FLASH. |
| Electric lock | 2 × 1 mm² | Up to 10 m; output 12 V AC / max. 15 VA. |
| Key switch | 4 × 0.5 mm² | Up to 50 m; alternatively, two 2 × 0.5 mm² cables. |
| Antenna | RG58 | Up to 20 m; less than 5 m is recommended. |
Check the cross-section and routing against the cable lengths and the manual for the installed control unit.
Connecting the motor and control unit
HY7124 is for the 24 V DC motor output on the MC824H, not for 230 V mains. The procedure below is for the MC824HR30 with an MCA1R30 board. The middle terminal of the three-pole M1 or M2 output is protective earth (PE); the two outer terminals are for the motor. Do not confuse PE with a motor wire or the 24 V auxiliary negative. The two encoder wires are non-polarized; connect them to the corresponding ENC terminal. The MC824L uses different motors.
| One folding leaf | Motor to M2, encoder to ENC2; M1 and ENC1 remain unused. |
|---|---|
| Two folding leaves | M2 opens first; M1 closes first. The M1 encoder connects to ENC1, and the M2 encoder to ENC2. |
| Motor selector | Before learning the positions, set DIP 1 = ON; DIP 2–12 = OFF for HY7124. Do not use any other combination. |
Use the model-specific setting for HY7124; the programmer may display this group as MB4024. The correct switch positions for HY7124 are what matter.
Accessory terminals and polarity
| Auxiliary power supply | Left terminal of the SbS pair = +; right terminal of the STOP pair = −, as shown in the detail below. 24 V DC −30% / +50%, total max. 200 mA. Voltage remains present in Standby. These are the power supply terminals shown, not arbitrary signal contacts. |
|---|---|
| BlueBUS | Two parallel wires carry both power and data; no +/− polarity. |
| ENC1 / ENC2 | Encoders for the corresponding motors; non-polarized. |
| FLASH | 12 V DC warning light, max. 21 W; for example, ELDC. Before connecting, check the +/− markings on the specific output and warning light. |
| ELS | Electric lock 12 V AC, max. 15 VA; AC has no +/− polarity. |
| OGI | Open-gate indicator: 24 V DC (−30% / +50%), max. 4 W. The mode depends on the settings; follow the markings on the installed output. |
| SbS / Open / Close | Voltage-free NO contacts for the corresponding terminal pairs: step-by-step, open only, or close only. The contacts are non-polarized and must not be connected to an external voltage. |
| STOP | Learned safety input: NO, NC or 8.2 kΩ. Voltage-free contacts are non-polarized; wiring must match the safety devices. |
For a different board or terminal layout, follow the manual for the installed unit. Detailed MC824HR30 wiring.
Backup in the event of a mains failure
The MC824HR30 supports PSS324. Disconnect both mains power and the battery before connecting, and use the specified connector. If you are keeping the older PS324, you need CABLA11 cable and Standby must be OFF. The number of operations depends on the battery charge and gate load. Backup power does not replace proper manual release. Complete backup power connection procedure.
Photocells and safety inputs
Position the photocells according to the movement of the folding leaves and the gate’s hazards. Align TX/RX correctly. Protecting the passage does not replace protection at crush points around the hinge and arm.
The MC824H uses BlueBUS. EPMB, EPLB, EPSB, EPMORB and F210B connect them in parallel using two non-polarized wires. TX/RX units in one pair must have the same address, and each pair must have an address different from the others. After changing the devices, repeat the learning procedure.
PHOTO/PHOTO II protect during closing; PHOTO 1/PHOTO 1 II intervene during both opening and closing. PHOTO 2/PHOTO 2 II protect during opening. PHOTO 3 is not permitted. The exact jumpers and responses are shown in the addressing table.
Test each pair during both opening and closing, test STOP, and test any safety edge. Do not bypass a safety device to make the gate move.
First startup and learning
Perform these steps after the mechanical and electrical checks. Secure the motor in automatic mode; check the stops, clear travel path, and M1/M2 assignment. Be ready to stop the gate during its first movement.
On the MCA1R30, set DIP 1 ON and all others OFF for HY7124, and connect the encoder.
After switching on the power, BlueBUS must flash approximately once per second, the LEDs on connected BlueBUS photocell TX/RX units must flash, and the FLASH warning light must be off. If any check fails, disconnect the power supply and any backup battery, then check the wiring before continuing.
1. Device recognition
- Press and hold Open ▲ + Stop/Set.
- Release both buttons when L1/L2 start flashing rapidly, after approximately 3 seconds.
- Wait for the process to finish. Success: STOP is lit, L1/L2 go out. L3/L4 may flash to indicate that position learning is required.
Repeat after adding or removing a BlueBUS/STOP device. Perform the learning procedure even if no accessories are connected.
2. Automatic position learning
- Press and hold Stop/Set + Close ▼.
- Release the buttons when L3/L4 start flashing rapidly, after approximately 5 seconds.
- Watch for: M1 slowly closes to the stop, M2 slowly closes to the stop, both motors slowly open to the stops, then both motors close quickly. With one motor, only M2 moves.
- Successful completion is confirmed when L3/L4.
If either motor opens instead of closing during the first closing movements, stop the learning procedure using the Open ▲ or Close ▼. Disconnect the power supply and any backup supply, then correct the direction of the relevant motor by swapping the two outer motor wires as shown in the MC824H wiring diagram; do not change the protective PE or encoder wires. With two motors, if the sequence is incorrect, correct the M1/M2 connections and their ENC1/ENC2 connections as well. Restart the learning procedure from the beginning. Activation of a photocell or STOP input interrupts the procedure and L1 flashes; remove the cause and repeat the learning procedure.
3. Testing and handover
Test full opening and closing cycles, stops, slowdowns, coordination of the folding leaves, and manual release. Check every safety device, including stopping and reversal when an obstacle is encountered. Measure the forces and assess the complete installation. Do not set a high force to compensate for a gate that is sticking. Provide the user with the instructions and ensure they know how to release the drive safely.
Manual and mixed learning: detailed control unit procedure. Automatic learning must be completed before mixed learning.
Settings and remote controls
Set automatic closing, pause time, step-by-step operation, slowdown, and force to suit the gate. Repeat the tests after changing the force or safety functions. The full ranges, LEDs, and factory settings are listed in the control unit programming tables.
Receiver, remote control, and antenna
The motor alone does not have a built-in radio receiver. An SM receiver is installed in the control unit. NICE OXIBD also supports bidirectional operation ON3EBD; OXILR use with ON3ELR. With the older OXI choose transmitters based on the stored coding. The same frequency alone does not guarantee compatibility.
Connect the coaxial cable according to the receiver: directly to the receiver with OXIBD, and as shown in the control unit wiring diagram with OXI. Pairing and deleting remote controls. Erasing the radio memory does not reset the control board or perform position learning.
Troubleshooting
| Symptom | What to check |
|---|---|
| Gate does not move | Power supply, release mechanism engagement, and STOP. Check the power supply and fuses with the power disconnected. |
| Motor runs, gate leaf does not move | Gear engagement and arm attachment; return the release mechanism to the locked position. |
| Gate stops or reverses | First check manual movement and the arm's clearance, then check the photocells, STOP, and stops. Do not increase the force without identifying the cause. |
| Learning procedure does not complete | Motor sequence and direction, stops, and safety devices. For HY7124, also check DIP 1 and the encoders. |
| Remote control does not work, but the button does | Battery, coding, transmitter storage in the receiver, and antenna. |
| Fault after changing the photocells | Check addresses and cables, then repeat device recognition. |
Flasher and LED blink counts: diagnostics and repairs. Record the settings before resetting. Resetting the control board, erasing the receiver, and performing new learning are separate operations; refer to the instructions for the installed control unit.
Inspection and maintenance
Have the entire automation system inspected at least every six months; inspect it more frequently in case of intensive use or harsh environmental conditions, according to the maintenance schedule. Check the outer and centre hinges, motor mounting, telescopic arm, stops, cable routing, release mechanism, and all safety devices. Record the results in the maintenance log.
While the gate is moving, do not enter between the folding sections or into the arm's path. Do not allow children to play near the gate, and keep remote controls out of their reach. Secure the gate against movement before manually releasing it or cleaning accessible surfaces. Repeat functional and safety tests after repairs, electrical work, or changes to safety settings. If the gate malfunctions, take it out of service and secure it.
NICE HYPPO HY7124 technical specifications
| Type | Non-reversible electromechanical motor with telescopic arm for a folding gate. |
|---|---|
| Motor voltage | 24 V DC |
| Current | 5 A |
| Power consumption | 120 W |
| Torque | 250 Nm |
| Rotational speed | 2 rpm |
| Opening time specified by the manufacturer | 10 s |
| Duty cycle | 80 % |
| Position sensing | Magnetic encoder |
| Capacitor | No starting capacitor for an AC motor. |
| Ingress protection rating | IP43 |
| Operating temperature | −20 to +70 °C |
| Motor weight | 13 kg |
| Dimensions | 350 × 165 × 242 mm; body with mounting plate as shown in the drawing. |
| Folding section limits | Maximum 1,500 mm; weight according to chart. The maximum length and weight limits do not apply simultaneously. |
The opening time is not guaranteed for every folding gate. It depends on the geometry, control settings, and load. For an older operator, refer to its rating plate and the corresponding manual.
How can I order this item?
Choose the option that suits you:
- order online: use the buy button to add the goods to your shopping cart (you will find the buy button here in the product variants table).
- order by email: place your order at [email protected]