NICE Moonclever MC824HR30 – new control unit for 24 V swing gate operators in the Toona range
| Product availability: | within 3 days | We usually dispatch goods within 3 days. |
|---|
within 3 days
€308.80 including VAT
| Weight |
|---|
| 4,10 kg |
Description of NICE Moonclever MC824HR30 – new control unit for 24 V swing gate operators in the Toona range
Wiring and setting up the NICE MC824HR30 control unit
NICE Moonclever MC824HR30 is the successor to the MC824HR10 for single- and double-leaf gates. The Moonclever box contains an MCA1R30 board (SPMCA1R30). The control unit is powered by 230 V AC and operates compatible 24 V DC drives with magnetic encoders.
MC824HR30 belongs to the MC824H type. The MC824L version uses different motors, so the drive selection and encoder wiring shown below apply to the HR30. On a double-leaf gate, M2 opens first and M1 closes first. For a single-leaf gate, connect the motor to M2.
Compatible drives and accessories
| What | Why | Type |
|---|---|---|
| Warning light | Flashes to warn that the gate is moving, especially at exits with limited visibility. |
|
| Photocells | Detect an obstruction in the gate area and trigger the appropriate safety response. |
|
| Remote control | Open and close the gate remotely. |
|
| Receiver | Receives commands from remote controls; one module is fitted in the SM connector. |
|
| Service programming | Advanced control unit settings and diagnostics. |
|
| programmer | Antenna |
|
| ; with OXIBD, connect the coaxial cable directly to the receiver. | Keypad |
|
| with a compatible FloR receiver. | Key switch |
|
| command input | Backup battery |
backup power connection The control unit is designed for 24 V drives with magnetic encoders.
| Select the specific motor from the table below and set its type using the switches before teaching the travel limits. | Group |
|---|---|
| Models listed by the manufacturer for MC824H | Nice Toona 4024 (TO4024), Nice Toona 5024 (TO5024), Nice Toona 5024I (TO5024I), Nice Toona 7024 (TO7024) |
| TO7024 | Nice Toona 5024HS (TO5024HS), Nice Toona 6024HS (TO6024HS) |
| TO6024HS | Nice Hyppo 7024 (HY7024), Nice Hyppo 7124 (HY7124) |
| HY7124 | Nice M-Fab 3024 (MFAB3024), Nice L-Fab 4024 (LFAB4024), Nice B-Fab 5024 (BFAB5024) |
| BFAB5024 | Nice M-Fab 3024HS (MFAB3024HS), Nice L-Fab 4024HS (LFAB4024HS), Nice Wingo 3524HS (WG3524HS), Nice Titan 3724HS (TTN3724HS), Nice Titan 6024HS (TTN6024HS) |
| TTN6024HS | Other compatible models |
MB4024, MB5024, XFAB2124, METROELITE, WINGOELITE You can find the switch settings in the.
Selecting the motor type
Secure the control unit to a solid vertical surface so that its bottom edge is at least 40 cm above the ground. Prevent water from entering through the cable routes. According to the manufacturer, the side cable entry is intended only for a protected indoor environment; outdoors, use the prepared bottom entries with suitable cable glands.
| Purpose | Cable and maximum length |
|---|---|
| Control unit power supply | 3 × 1.5 mm²; up to 30 m. For lengths over 30 m, the manufacturer specifies 3 × 2.5 mm² and grounding at the automation system. |
| Each motor | 3 × 1.5 mm²; up to 10 m. |
| Encoder for each motor | 2 × 1 mm²; up to 10 m. The motor and encoder cables can be replaced with a single 5 × 1.5 mm² cable, as specified in the manual. |
| BlueBUS | 2 × 0.5 mm²; up to 20 m. For 20–40 m, use 2 × 1 mm². |
| Flashing light | 2 × 0.5 mm²; up to 20 m. |
| Antenna | RG58 coaxial cable; up to 20 m, with a recommended length of less than 5 m. |
| Key switch | Two 2 × 0.5 mm² cables or one 4 × 0.5 mm² cable; up to 50 m. |
| Electric lock | 2 × 1 mm²; up to 10 m. |
The specified cross-sections apply to the lengths shown. For longer cable runs, choose a cable based on the actual length, installation method and power circuit.
MC824HR30 terminals and wiring diagram
When changing the wiring, switch off both the mains power and the backup battery. Follow the labels printed directly on the MC824HR30 board; terminal numbering from other control units does not apply here.
TX and RX in the diagram are BlueBUS photocells. The antenna connection on the board applies to OXI; with OXIBD, the antenna connects directly to the receiver, as shown in the radio section. Click to enlarge the image.
| Terminal | Use |
|---|---|
| L / N / PE | 230 V AC mains power and protective earth, as marked in the power supply section. Do not connect to low-voltage inputs. |
| M1 + ENC1 | Motor for the gate leaf that moves first when closing, and its encoder. |
| M2 + ENC2 | Motor for the gate leaf that moves first when opening, and its encoder. For a single-leaf gate, connect the motor to M2; leave M1 unused. |
| FLASH | Flashing light output; 12 V DC in flashing-light mode, max. 21 W. The manufacturer specifies NICE ELDC. This is not a 230 V output. |
| ELS | Electric lock output, 12 V AC, max. 15 VA. Changing the function to lighting also changes the electrical output parameters. |
| OGI | Open gate indicator: 24 V, max. 4 W; voltage may vary by −30 to +50%. |
| BlueBUS | Two wires for both power and communication with compatible devices; connect in parallel, with no regard to polarity. |
| STOP | Safety input for NO, NC or 8.2 kΩ. During setup, the control unit memorises the connected state; a change triggers a stop and brief reverse movement. |
| SbS / OPEN / CLOSE | Control inputs for volt-free NO contacts: step-by-step, open and close. Do not apply an external voltage to these inputs. |
| 24 V DC for additional devices | The minus (−) is the right-hand terminal of the STOP pair, and the plus (+) is the left-hand terminal of the SbS pair when viewing the terminal blocks labelled STOP and SbS. Maximum total current draw: 200 mA. This power supply remains available in Standby; the BlueBUS terminals are separate and have no polarity. |
| SM / IBT4N | Plug-in receiver connector / service interface connector. Insert accessories with the power disconnected. |
Motors and encoders
Each encoder must be matched to the correct motor. Polarity does not matter at the two-wire ENC input. If the gate leaves are found to be in the wrong order during setup, swap their encoders as well as their motors. Do not confuse the protective earth wire with the motor wires.
Button and key switch
For standard control, connect an NO contact to the SbS terminal pair. For the NICE EKS switch, use the C and NO contacts of the selected microswitch. The command sequence is set by parameter L2 in the second level. Separate commands can be connected to OPEN and CLOSE. Function L7 in the first level can change the CLOSE input to partial opening.
STOP input
Connect multiple NO contacts in parallel and multiple NC contacts in series. Configurations with 8.2 kΩ safety edges have their own wiring, depending on the edge type. If STOP indicates a fault, check the contact and wiring instead of permanently bridging the input.
BlueBUS photocells
For a basic pair, use a compatible TX transmitter and RX receiver, for example NICE EPMB. Connect both in parallel to BlueBUS using two wires. These are not relay photocells with COM/NC contacts; wiring for EPM or BF from another control unit does not apply here.
- Position TX and RX opposite each other to protect the required area.
- Set the addressing jumpers according to the required function. TX and RX in one pair must have the same address; each additional pair must have a different address.
- Connect both BlueBUS wires; polarity does not matter.
- Run the connected-device learning procedure and test each pair while the gate is moving.
| Address | MC824H control unit response |
|---|---|
| FOTO / FOTO II | Protection during closing: stop and reverse movement. |
| FOTO 1 / FOTO 1 II | During closing, stops and reverses; during opening, stops and resumes once the beam is clear. |
| FOTO 2 / FOTO 2 II | Protection during opening: stop and reverse movement. |
| FOTO 3 | This configuration is not used with the MC824H. |
Determine the exact jumper positions from the markings on the specific photocells. Repeat the connected-device learning procedure whenever a device is added, removed or replaced.
Initial startup and gate travel learning
1. Select the motor type
With the power disconnected, set the selector according to the exact drive model. Complete the setup before learning the mechanical stops. Use only a combination specified by the manufacturer.
The image shows the motor settings for the MC824H. Set the switch position according to the ON marking in the image and on the control unit selector. Click to enlarge the image.
2. Check the mechanics and power up for the first time
Check the stops, free movement, and locking of the drives according to their manuals. After power-up, the BlueBUS LED should flash regularly about once per second, the photocell TX/RX LEDs should flash, and the warning light should be off. If anything differs, disconnect the power and check the wiring.
3. Learn the connected devices
Buttons and indicator lights used to detect BlueBUS and STOP devices. Click to enlarge the image.
- Press and hold Open ▲ + Stop/Set.
- When L1 and L2 start flashing rapidly, after about 3 seconds, release the buttons.
- Wait for the process to finish. The STOP LED should be lit; L1 and L2 should be off. L3 and L4 may indicate that the travel path still needs to be learned.
This step is required even if no devices are connected to BlueBUS or STOP.
4. Automatically learn the mechanical stops
- Press and hold Stop/Set + Close ▼.
- Release the buttons only when L3 and L4 flash rapidly, after about 5 seconds. Releasing earlier, when L1 flashes, starts manual learning.
- Check the movement sequence: M1 closes slowly, M2 closes slowly, M2 and M1 open slowly to the stops, and finally both leaves close quickly.
- When the process completes correctly, L3 and L4 go out. Test opening and closing each leaf separately using the buttons.
If the direction or sequence is incorrect: stop the learning process using the Open or Close button. Disconnect all power before correcting the wiring. If the leaves are swapped, correct both M1/M2 and the corresponding ENC connections; if the direction is reversed, correct only the motor wires according to the original wiring diagram. Then repeat the learning process. Activation of a photocell or STOP interrupts the learning process.
You do not need to erase the entire memory as a precaution before repeating the learning process.
Fine-tuning the leaf positions manually
If automatic learning does not suit the gate geometry, you can fine-tune the positions manually. Mixed mode builds on the previous automatic learning process and fine-tunes selected intermediate positions; the mechanical end positions 0 and 1 remain unchanged.
SA and SC determine the sequence of leaf movement; A is the required open position. Click to enlarge the image.
| LEDs during manual learning | Position |
|---|---|
| L1 | M1 closed mechanical stop (0). |
| L2 | M2 closed mechanical stop (0). |
| L3 | SA: M2 position at which M1 starts moving when opening. |
| L4 | Required open position A of M1. |
| L5 | Required open position A of M2. |
| L6 | SC: M1 position at which M2 starts closing. |
| L7 | M1 open mechanical stop (1). |
| L8 | M2 open mechanical stop (1). |
To enter manual learning: hold Stop/Set + Close and release when L1 flashes, after about 3 seconds. Briefly press Open/Close to select a position; press and hold to move the relevant motor. To save a position, press and hold Stop/Set for at least 3 seconds; then move to the next position. Allow no more than 10 seconds between steps.
For a single-leaf gate, skip unused positions. Follow the LED sequence in the table and save only the positions for the connected M2 motor.
Programming functions and parameters
Use the Open ▲ and Close ▼ buttons to select an item; Stop/Set confirms or changes the setting. Level I switches a function on or off; Level II sets its value. For example, L1 at Level I enables automatic closing, while L1 at Level II sets the pause duration.
Level I – switching on and off
- With the gate stationary, hold Stop/Set until L1 starts flashing, then release it.
- Use Open/Close to select the desired LED.
- Briefly press Stop/Set to change the status: a short flash = OFF; a long flash = ON.
- When finished, wait for programming to end.
| LED – function | ON status and effect |
|---|---|
| L1 – Automatic closing Closes after the set pause. | After opening, the pause countdown begins, then the gate closes. |
| L2 – Closing after photocell activation Shortens or starts the pause after the photocell is triggered. | When automatic closing is enabled, it shortens the pause to 5 s. When automatic closing is disabled, triggering the photocell can start closing after the set pause. |
| L3 – Always close Response when power returns. | If the gate is open, the control unit closes it with a pre-flash after power is restored. |
| L4 – Standby all Energy-saving mode; enabled by default on the MC824HR30. | After a period of inactivity, it switches off BlueBUS and most LEDs. Battery requirements are covered in the section Standby and backup. |
| L5 – Lock / lighting Changes the function of the ELS output. | ON: courtesy light. OFF: electric lock; check the connected load parameters if you change this setting. |
| L6 – Pre-flashing Warning before movement. | The warning light starts flashing 3 s before movement begins. |
| L7 – CLOSE / partial opening Changes the function of the CLOSE input. | The CLOSE input issues a Partial Open 1 command instead of a close command. |
| L8 – OGI / maintenance Changes the function of the OGI output. | The output signals that maintenance is required instead of indicating that the gate is open. |
Level II – setting the value
- Hold Stop/Set until L1 flashes, then release it. Use Open/Close to select a parameter.
- Press and hold Stop/Set again. After about 3 seconds, the LED for the current value lights up.
- Keep holding Stop/Set and use Open/Close to select a value.
- Release Stop/Set and wait for the mode to end. Then test the function.
| Input LED – parameter | Setting LED – value |
|---|---|
| L1 – Pause time The time before automatic closing; applies only when Level I/L1 is enabled. | L1 – 5 s L2 – 15 s L3 – 30 s L4 – 45 s L5 – 60 s L6 – 80 s L7 – 120 s L8 – 180 s |
| L2 – Step-by-step Sequence of SbS, OPEN, CLOSE, and radio commands. For L4, L5, L7, and L8, the behavior of OPEN and CLOSE also changes. | L1 – open–stop–close–stop L2 – open–stop–close–open L3 – open–close–open–close L4 – condominium L5 – condominium 2; a command held for more than 2 s gives STOP L6 – step-by-step 2; a short command of up to 2 s partially opens L7 – movement only while the command is held L8 – semi-automatic opening, closing by holding the command |
| L3 – Motor speed Speed during normal movement. | L1 – very slow L2 – slow L3 – medium L4 – fast L5 – very fast L6 – extremely fast L7 – opens quickly, closes slowly L8 – opens extremely quickly, closes at medium speed |
| L4 – Relief after closing A short reverse movement of both motors reduces residual pressure. | L1 – no relief L2 – level 1, approximately 100 ms L3 – level 2 L4 – level 3 L5 – level 4 L6 – level 5 L7 – level 6 L8 – level 7, approximately 800 ms |
| L5 – Motor force Shared force setting for both motors; check the mechanics before increasing it. | L1 – level 1 – minimum L2 – level 2 L3 – level 3 L4 – level 4 L5 – level 5 L6 – level 6 L7 – level 7 L8 – level 8 – maximum |
| L6 – Partial opening Range of the Partial Open 1 command. For two leaves, the proportion is calculated from the smaller configured opening. | L1 – M2 to ¼ L2 – M2 to ½ L3 – M2 to ¾ L4 – M2 fully open L5 – both leaves to ¼ L6 – both leaves to ½ L7 – both leaves to ¾ L8 – both leaves to the smaller full opening |
| L7 – Maintenance interval Number of operations before the maintenance signal. | L1 – 500 L2 – 1,000 L3 – 1,500 L4 – 2,500 L5 – 5,000 L6 – 10,000 L7 – 15,000 L8 – 20,000 |
| L8 – Fault history Results of the last eight operations; L1 is the most recent. | L1 – 1st operation – most recent L2 – 2nd operation L3 – 3rd operation L4 – 4th operation L5 – 5th operation L6 – 6th operation L7 – 7th operation L8 – 8th operation |
In step-by-step modes L4 and L5, the SbS or OPEN command has no effect while opening, and CLOSE reverses the direction; while closing, SbS or OPEN reverses the direction, and CLOSE has no effect. In L5, holding the command for more than 2 s also stops movement. L7 requires the command to be held throughout the movement; L8 requires it only while closing.
Example – closing after 60 seconds: At level I, switch on L1. Then at level II, enter parameter L1 and select value L5. If the photocell closing function is also enabled, the pause may be shortened.
Do not leave a long pause between programming steps; afterwards, the control unit returns to normal mode.
Radio receiver, antenna and remote controls
Remote control operation depends on the receiver installed. For the plug-in NICE OXIBD use the SM connector. The button with the radio symbol on the MC824H panel is not used; pair the remote control with the relevant receiver.
For the OXIBD receiver, our range includes, for example, the NICE ON3EBD. When expanding an existing setup, also check the coding and receiver mode already in use; matching frequency alone is not enough.
With OXIBD, connect the external antenna with RG58 coaxial cable directly to receiver terminals 1 and 2, not to the control board’s antenna terminal. Click to enlarge the image.
Choose the procedure for saving the remote control according to the specific receiver in the NICE remote control pairing guide. Adding a remote control does not require erasing the control unit’s travel settings.
Standby and backup power
The Standby all (L4 at level I) function is enabled by default on the MC824HR30. Approximately 5 minutes after a movement is completed correctly, it switches off the BlueBUS power supply and most indicator LEDs; the BlueBUS indicator then flashes more slowly. After receiving a command, the unit returns to normal operation with a short delay, so slower flashing after a period of inactivity does not indicate a fault. If a backup battery is connected, Standby is activated only after the battery has finished charging.
| Battery | Connection requirements |
|---|---|
| PSS324 | Current type specified by the manufacturer. Use the relevant manual and the cable supplied for this setup; NICE PSS324 details. |
| Older PS324 | Use NICE CABLA11 and disable Standby (L4 = OFF). The adapter alone is not sufficient. Allow for higher power consumption. |
Connect the battery with the mains power disconnected. The radio receiver, service interface and continuously powered accessories increase power consumption, so battery operating time varies depending on the specific setup.
Solemyo: solar power is connected via the battery connector. Standby all must be active; the mains power supply must not be connected at the same time as the solar setup. The requirements for the older PS324 do not apply to it.
Troubleshooting common problems
When troubleshooting, note the LED status and the number of short flashes from the warning light. The fault sequence repeats twice, with a pause of approximately one second. Leave resetting until the last step, as it erases saved settings.
| Short flashes | Meaning and initial check |
|---|---|
| 1 | BlueBUS device mismatch. Check connections and addresses; after changing the setup, run device recognition. |
| 2 | Photocell triggered. Check for obstructions, cleanliness, and correct alignment of TX/RX. |
| 3 | Obstruction detected based on force. First check for mechanical resistance and ensure free movement. |
| 4 | STOP active. Check the safety device and its wiring. |
| 5 / 7 | Internal parameter / electrical circuit fault. Wait at least 30 s; if the fault recurs, servicing is required. |
| 6 | The number of cycles per hour or continuously has been exceeded. Let the system rest for a few minutes. |
| 8 | A continuously active command is blocking further commands. Check the button, relay, or timer control. |
| 9 | The automation system is blocked by a command. The appropriate command is required to unblock it. |
| 10 | Obstruction or increased resistance detected by the MC824H encoder. Check the mechanics and ensure the correct encoder is connected to the motor. |
What the LEDs on the control board indicate
| Indicator | Meaning |
|---|---|
| BlueBUS flashes once per second | Normal operation. Slower flashing after inactivity may indicate Standby. |
| BlueBUS – two quick flashes | An input has changed or a command has been received; this is not a fault in itself. |
| STOP lit / unlit | Lit: the learned safety status is OK. Unlit: check STOP and the connected devices. |
| SbS / OPEN / CLOSE lit | The corresponding control input is active. Steady illumination without a command may explain why the controls are blocked. |
| L1 + L2 flash slowly | The connected devices need to be identified. |
| L3 + L4 flash slowly | The travel limits have not been learned, or the motor selector setting was changed after learning. Check the selector and repeat the relevant learning procedure. |
| Neither BlueBUS nor the LEDs are lit | Check the power supply and fuses. The MC824H has a 15 A motor fuse and an F 2 A service fuse; check the rating and type on the control board. Do not replace a fuse with one of a higher rating. |
The gate works with the buttons but not with the remote control
Check the power supply and installation of the radio receiver, remote control compatibility, its battery, and whether it has been stored in memory. If the range is poor, also check the antenna connection point. First distinguish a radio issue from a control unit issue.
History of the last eight cycles
In Level II, select L8 and hold Stop/Set. When L1 lights up, use Open/Close to select a record; L1 indicates the most recent one. Read the number of flashes using the diagnostic information above. For the detailed procedure, see section 7.3.
Clearing the control unit memory
This will erase the individual settings. Hold Open + Close simultaneously until L1 and L2 start flashing, then release the buttons. Then repeat device learning, travel learning, and custom programming. This procedure does not erase the memory of the plug-in radio receiver.
Post-setup checks and routine maintenance
- Test opening, closing, and stopping with every control device in use.
- Check the leaf sequence, stops, acceleration, and deceleration.
- Test each pair of photocells, the safety edge, and STOP separately while the gate is moving.
- After adjusting the force or speed, test the gate through its full travel.
- If a battery is connected, test operation during a mains power failure and when mains power is restored.
Inspect the gate and its accessories at least every 6 months, or sooner if the gate is used more frequently. In the event of a power failure, release the drives themselves as described in their instructions; the MC824HR30 control unit does not have its own mechanical release key.
Information for technical support
When reporting a problem, provide the model designation of the control unit and both motors, the types of photocells and receiver, the LED status, the number of flashes, and the step at which the problem occurs. A photo of the complete wiring and a close-up of the rating plate are helpful.