NICE MC800 Technical Manual with MCA5 Board

Overview of all three manuals · MC824HR30 · MC800 / MCA5 · Road RD400

Practical guide to NICE MC800 with MCA5 board

This guide is intended for MC800 with NICE MCA5 board: the board has an output OGI and a Photo PRG. This is the generation for which NICE provides a manual covering the period up to 09/2025. The newer MC800R30 has a different OutSTB output and an energy-saving mode; its wiring diagram cannot automatically be used here.

The MC800 controls one or two compatible 230 V AC swing gate motors. For a single leaf, use M2. For two leaves, M2 opens first and M1 closes first. Mechanical stops, capacitors and any limit switches must be compatible with the specific operators.

Operators and accessories for MC800

The exact operator type and power supply determine compatibility. For example, the manufacturer recommends the MC800 for NICE HY7005; the similarly named HY7024 is a 24 V motor and uses a different control unit. When replacing the original control unit, connect the wires according to the terminal functions, not their original numbers.

Item Meaning / procedure
Relay photocells NICE EPM – TX/RX power supply and a separate C–NC safety contact. An example is shown in the diagram below.
BlueBUS photocells NICE EPMB – two-wire connection to terminals 6–7, with no polarity. EPM and EPMB wiring is different.
Warning light NICE ELAC – mains-voltage version with a built-in flasher. FLASH on a 230 V control unit is not a low-voltage output.
Key switch NICE EKS – voltage-free C–NO contact for SbS, OPEN or CLOSE.
Radio control NICE OXIBD for the SM connector and a compatible remote control, for example NICE ON3EBD. Pairing depends on the specific receiver.
Service settings NICE IBT4N + NICE OVIEW for access via BusT4.

Check the motor limits, duty cycle and capacitor in the manual for the selected operator. BlueBUS system capacity is calculated in load units; the control unit supports a maximum of 15 units, not necessarily 15 arbitrary devices.

Wiring and terminal functions

Circuit Cable specified by the manufacturer
Power supply 3 × 1.5 mm² up to 30 m; for longer runs, the manufacturer specifies 3 × 2.5 mm² and earthing at the automation unit. The protection and supply arrangement must be suitable for the installation.
Each motor 4 × 1.5 mm² up to 10 m, including the protective conductor. Capacitor as specified for the particular motor.
FLASH warning light 2 × 1.5 mm² up to 20 m, with mains-voltage-rated insulation.
BlueBUS 2 × 0.5 mm² up to 20 m; for 20–40 m, use 2 × 1 mm².
Antenna RG58 coaxial cable, max. 20 m; recommended length under 5 m.
Key switch 2 cables, each 2 × 0.5 mm², up to 50 m.
Electric lock 2 × 1 mm² up to 10 m.
Item Meaning / procedure
L / N / PE Power supply to the 230 V control unit and protective earthing. Also connect PE to the motors as specified in their manuals.
M1 / M2 Three motor terminals: OPEN – COMMON – CLOSE, as marked on the board; the protective conductor connects separately to PE. Connect a single motor to M2; leave M1 unused.
FLASH Switched mains voltage for a self-flashing warning light, max. 21 W. Suitable model: NICE ELAC; do not connect a 12/24 V warning light here.
1–2 / EL 12 V AC electric lock, max. 15 VA.
3 / 4 3 = 0 V; 4 = COMMON, +24 V DC. A total of up to 200 mA is available to power accessories between terminals 3–4.
5 / OGI Gate-open indicator, 24 V, max. 4 W. This marking is for the older MCA5 board.
6–7 / BlueBUS Two BlueBUS power and communication wires; connect in parallel, with no polarity.
8 / AuxIn1 M1 open limit switch or PHOTO when using relay photocells.
9 / AuxIn2 M2 open limit switch or PHOTO1 when using relay photocells.
10 / AuxIn3 M1 close limit switch or PHOTO2 when using relay photocells.
11 / AuxIn4 M2 close limit switch. When relay photocell mode is enabled, the AUX inputs are not used as limit switches.
12 / STOP Safety input for NO, NC or 8.2 kΩ. A change from the learned state triggers a stop followed by a brief reverse movement.
13 / SbS Step-by-step operation via a voltage-free NO contact between terminals 4 and 13.
14 / OPEN Open via an NO contact between terminals 4 and 14.
15 / CLOSE Close via an NO contact between terminals 4 and 15; the function can be changed to partial opening.

Do not apply an external voltage to the control inputs. With the NICE EKS the common C contact and the NO contact of the selected microswitch are used. Leave unused AUX inputs open as required by the selected mode; do not create universal jumpers across all safety inputs.

Source: original NICE MC800 manual IDV0544A00EN, Tables 1–2 and Sections 4.2–4.3.

Photocell wiring diagrams

Choose the diagram based on the photocell technology and whether photocell testing is used. TX and RX stand for transmitter and receiver. The two TX/RX sets in the original diagrams show different technologies; you do not have to install both.

Relay photocells without photocell testing – original example

MC800 MCA5: relay photocells without photocell testing, original Figure 8

Original NICE, Figure 8. The gray TX/RX units are relay type; the white TX/RX units are BlueBUS. The receiver shown is an OXI; the OXIBD antenna connects directly to the OXIBD. Click to enlarge the image.

For one pair NICE EPM and the PHOTO function, the basic existing wiring remains unchanged:

Section EPM wiring at 24 V DC
TX power supply MC800 terminal 3 → TX terminal 2; MC800 terminal 4 → TX terminal 1.
RX power supply MC800 terminal 3 → RX terminal 2; MC800 terminal 4 → RX terminal 1.
PHOTO contact RX terminal 4 (C) → MC800 terminal 4; RX terminal 5 (NC) → MC800 terminal 8. Connecting RX 4 to RX 1 is equivalent in this wiring to connecting COMMON.
Settings Hold Photo PRG until LP lights up, then teach the devices. Leave AUX1–3 unused.

The TX/RX terminal numbers apply to the wiring shown and the specified EPM model. For a different model, use its power supply and C–NC terminal markings. Relay photocells require the correct supply voltage range; the 12 V modification does not apply here.

Relay photocells with photocell testing

MC800 MCA5: relay photocells with photocell testing, original Figure 9

Original NICE, Figure 9. The relay TX photocell test uses output 5, marked OGI. Terminals 6–7 in the diagram supply separate BlueBUS devices. Click to enlarge the image.

As shown in Figure 9, connect TX terminal 1 to MC800 terminal 4 and TX terminal 2 to MC800 terminal 5. RX remains powered from terminals 3–4, and its C–NC contact connects to the selected PHOTO input. In this wiring, output 5 is used for the photocell test and cannot also be used for a standard OGI indicator light. After changing the wiring, repeat the learning procedure and function test. Selecting Photo PRG does not, by itself, change the TX power supply wiring.

BlueBUS photocells and motor limit switches

MC800 MCA5: BlueBUS and separate limit switches, original Figure 7

Original NICE, Figure 7. Here, the AUX inputs are assigned to the limit switches; the relay photocell function is disabled. Click to enlarge the image.

NICE EPMB connect with two wires to terminals 6–7. The TX and RX jumpers for one pair must set the same address; the next pair must have a different address. FOTO/FOTO II protects closing, FOTO1/FOTO1 II protects both opening and closing, and FOTO2/FOTO2 II protects opening. Address FOTO3 is not permitted. Set the jumpers to the exact positions specified in Table 3 of the MC800 manual and the photocell instructions.

If you use AUX as limit switches, LP must be off. Do not use relay photocells on AUX and limit switches on the same inputs at the same time. Repeat the learning procedure each time you add or remove a device.

Source: original NICE MC800 manual IDV0544A00EN, Figures 7–9, Sections 4.4–4.6; EPM terminals per IS0261A00MM.

Simplified first-start procedure

1. Mechanics, wiring and initial power-up

Check the stops, ensure the gate leaves move freely by hand, and make sure the drives are properly engaged. Check M1/M2, PE, capacitors and safety inputs. Before teaching, check that the force setting is suitable for the specific motor: level II, parameter L6.

After power-up, BlueBUS should flash green about once per second, and FLASH should be off. If this is not the case, disconnect the power and check the wiring. A preventive reset is not required before every adjustment.

2. Select the photocell mode

For relay photocells on AUX1–3, press and hold Photo PRG, until LP lights up. When AUX is used for limit switches, LP must be off; turn it off by pressing and holding Photo PRG again. If using only BlueBUS photocells, do not enable relay mode.

3. Teach the connected devices

  1. Press and hold Open ▲ + Stop/Set.
  2. Release when L1 and L2 flash rapidly, after about 3 seconds.
  3. Wait for the procedure to finish. L1/L2 will go out and STOP should be lit. L3/L4 may then indicate that the travel path needs to be taught.

Perform this step even if no devices are connected. For relay photocells, relay mode must be enabled before teaching.

4. Automatically teach the end positions

  1. Move the disengaged gate leaves to about halfway along their travel, then mechanically re-engage the drives as described in their instructions.
  2. Press and hold Stop/Set + Close ▼ and release when L3/L4 flash rapidly, after about 3 seconds.
  3. Check the sequence: M1 closing, M2 closing, M2 opening, M1 opening, M1 closing and M2 closing.
  4. When complete, L3/L4 will go out. Test the Open and Close commands separately and check the gate leaves' sequence and slowdown.

If a gate leaf opens instead of closing: interrupt the learning procedure by pressing Open or Close. Disconnect the power and verify that the circuit is de-energized. At the relevant motor, swap the two OPEN/CLOSE direction wires—the two outer motor wires shown in the diagram. Do not change the COMMON or PE wire. With 230 V AC, this is not a polarity reversal. Then repeat the learning procedure.

Activation of a photocell or STOP input interrupts the learning procedure and L1 starts flashing. Fix the cause and restart the learning procedure. If the automatic setup is not satisfactory, continue with manual setup.

Source: original NICE MC800 manual IDV0544A00EN, Sections 4.5–4.9.

Manual setting of the end positions

Manual setup has two stages: first, the closed and open end positions, then the slowdown points during closing. Set points A for L5/L6 only after the open position of the relevant motor has been taught.

LED during teaching Position being stored
L1 0 M1 – M1 fully closed.
L2 0 M2 – M2 fully closed.
L5 A M2 – start of M2 slowdown during closing.
L6 A M1 – start of M1 slowdown during closing.
L7 1 M2 – M2 fully open.
L8 1 M1 – fully open M1.

Phase 1: end positions

  1. Hold Stop/Set + Close and release when L3/L4 flash rapidly, after about 3 s. Immediately press Stop/Set briefly, which selects manual learning.
  2. At L1, hold Open or Close to move M1 to the closed position. Release the button to stop movement. Save by holding Stop/Set for at least 3 s, then release.
  3. At L2, save the closed position of M2 in the same way.
  4. L5 is now selected. Briefly press Open/Close to move past L5 and L6 to L7. Do not save these slowdown points yet.
  5. At L7, set and save the open position of M2; at L8, the open position of M1.
  6. Let the mode exit, then test a safe opening and closing cycle.

Phase 2: slowdown points

After learning the end positions, enter mixed setting mode: hold Stop/Set + Close and release when L1 flashes. Briefly press Open/Close to select L5. Move M2 to set the start of slowdown during closing, then save it by holding Stop/Set for at least 3 s. Set L6 for M1 in the same way. When starting from fully open, this is movement toward the closed position.

Do not wait more than 10 s between successive button presses. A brief press of Open/Close selects the LED; holding the button moves the motor. For a single motor, use only L2, L5 and L7; skip the other items.

After each adjustment, check the full travel, the timing between the leaves, and safety. Generally extending the motor run time against the stop is no substitute for correct setup or the instructions for the specific operator.

Source: original NICE MC800 manual IDV0544A00EN, Table 4 and Sections 4.8.2–4.8.3.

Programming functions and parameters

In Level I, the function is switched on or off. In Level II, its value is selected. Therefore, the same LED number does not refer to the same thing in both levels.

Level I – switching on and off

Hold Stop/Set until L1 flashes, then release. Use Open/Close to select the LED, then briefly press Stop/Set to change the state: short flash = OFF, long flash = ON. Programming ends after 10 s without a button press.

Item Meaning / procedure
L1 – automatic closing After opening, the pause time counts down and the gate closes.
L2 – closing after photocell activation When automatic closing is enabled, this reduces the pause after the photocells are triggered to 5 s. Even with L1 disabled, triggering a photocell may initiate automatic closing after the set pause.
L3 – always close After power is restored, an open gate may close by itself; warning flashing precedes movement.
L4 – brief closing push Before opening a closed gate, it briefly moves in the closing direction to help release the electric lock.
L5 – auxiliary lighting Changes the FLASH output from a warning light to lighting. The output's electrical ratings must match the connected load.
L6 – pre-flashing The warning light signals for 3 s before movement starts.
L7 – partial opening Changes the CLOSE input to Partial Open 1.
L8 – pressure maintenance For compatible hydraulic motors only: after 4 h in the closed position, it briefly restores pressure with a closing command.

Level II – setting the value

Hold Stop/Set until L1 flashes, then release. Use Open/Close to select a parameter, then hold Stop/Set again. Its value appears after about 3 s. Keep holding Stop/Set and use Open/Close to select a new value. Release Stop/Set and wait 10 s.

Item Meaning / procedure
L1 – pause time L1–L8: 5 / 15 / 30 / 45 / 60 / 80 / 120 / 180 s. Factory setting: 30 s.
L2 – step-by-step mode L1: open–stop–close–stop. L2: open–stop–close–open. L3: open–close–open–close. L4/L5: condominium mode; L6: step-by-step with partial opening; L7: hold-to-run; L8: semi-automatic opening and closing by holding the button. The detailed OPEN/CLOSE responses vary in the extended modes; see Table 6.
L3 – opening delay L1–L8: 0 / 10 / 15 / 20 / 25 / 30 / 40 / 50% of the operating time.
L4 – closing delay The same steps: 0 / 10 / 15 / 20 / 25 / 30 / 40 / 50% of the operating time.
L5 – time balance L1–L8: 0 / 20 / 30 / 40 / 60 / 70 / 80 / 100%. A lower setting shortens and a higher setting lengthens the closing time; this is not a force setting.
L6 – motor force L1–L8: 25 / 35 / 45 / 55 / 65 / 75 / 85 / 100%. These values indicate electrical power regulation, not measured impact force.
L7 – start-up time L1–L8: 0 / 0.5 / 1 / 1.5 / 1.8 / 2 / 2.5 / 3 s.
L8 – partial opening L1–L4: M2 opens ¼, ½, ¾, or fully. L5–L8: both leaves open ¼, ½, ¾, or the lesser of the set opening distances for M1/M2.

Example – closing after 60 seconds: switch on L1 in Level I. In Level II, select parameter L1 and set its value to L5. If L2 is also active, triggering the photocells may shorten the pause.

Do not use force to compensate for a binding mechanism. After changing the force, start-up, or timing, verify the safety of the entire gate and carry out any required force measurements.

Source: original NICE MC800 manual IDV0544A00EN, Chapter 6, Tables 5–6.

Remote controls and service programmers

Install the plug-in receiver with the power disconnected. An existing SMXI or OXI can remain part of a suitable working setup; when adding remote controls, follow the exact receiver type and coding in use.

For a new compatible setup, NICE OXIBD and, for example, NICE ON3EBD. The OXIBD antenna connects directly to the receiver terminals. The original older diagrams with OXI do not show this connection method. The antenna coaxial cable and the warning light's mains supply are two separate circuits.

Example for an existing SMXI receiver

To store in Mode I, hold the receiver button for at least 3 s until its LED lights up, then release it. Within 10 s, hold the remote control button for at least 2 s. Three flashes from the receiver confirm storage. This mode stores the entire remote control; when only one specific command is required, use the relevant Mode II procedure.

For procedures for OXI, OXIBD, and other receivers, see our NICE remote control pairing guide. Do not automatically apply the SMXI procedure to another receiver. Adding a remote control does not require resetting the MC800 travel settings.

Programming via BusT4

The original manual describes NICE IBT4N and NICE OVIEW. These provide advanced settings and diagnostics, such as OGI service indication. The existing reference to NICE BIDIWIFI remains for selecting mobile programming; check the module manual for its connection, functions, and support for the specific revision.

Source: original NICE MC800 manual IDV0544A00EN, Sections 8.1–8.2; pairing and antenna instructions depend on the receiver installed.

Diagnostics, fuse, and reset

In the event of a fault, record the number of red BlueBUS LED flashes and any other illuminated or flashing LEDs. The red sequence repeats after a pause of about one second. Two quick green flashes when a command is issued indicate a normal input change.

BlueBUS LED Meaning and initial check
1 red flash BlueBUS devices do not match the learned configuration. Check the wiring and addresses; repeat the learning procedure after changing the configuration.
2 Photocell triggered. Check for obstructions, cleanliness and TX/RX alignment, the power supply, and the contact in relay wiring.
4 STOP triggered. Check the connected safety device and wiring.
5 Internal parameter error. Wait at least 30 s and try issuing a command. If the error recurs, servicing is required.
7 Electrical fault. Next, read L1–L4 using the table below.
8 A continuously active command blocks the others. Check the button, relay or timed control.
9 The automation was blocked by a command; use the appropriate command to unblock it.
Item Meaning / action
7 + L1 flashing Motor protection activated or motors disconnected.
7 + L2 flashing Anomaly in the learned limit switches.
7 + L3 flashing Limit switches are present but have not been learned.
7 + L4 flashing General anomaly; if it persists after checking, servicing is required.
L1 + L2 flashing slowly Device learning is incomplete.
L3 + L4 flashing slowly Mechanical limit positions have not been learned.
STOP not illuminated Check the STOP safety input and its learned status.
Neither is BlueBUS illuminated Check the power supply and fuse; if the fault recurs, professional diagnostics are required.

The MC800 table uses codes 1, 2, 4, 5, 7, 8 and 9. Codes and encoder errors from the MC824H do not apply here.

MC800 fuse with legible 5A F marking

Main fuse: 5 A, fast-acting (F). When replacing it, also match the other specifications of the original fuse. Click the image to enlarge it.

Check the fuse with the power disconnected. Find the cause of the blown fuse before replacing it; using a higher rating or bypassing it is not a repair.

When to reset

A reset erases the control unit's custom settings. Use it only when deliberately restoring the factory settings: hold Open + Close until L1/L2 start flashing, then release. You will then need to reconfigure the inputs, learn the devices and travel path, and perform tests. The memory of the plug-in radio receiver is reset using its own procedure.

Source: original NICE MC800 manual IDV0544A00EN, Chapter 7, Tables 8–10; reset in Chapter 6.5.

Final tests and regular maintenance

  • Check opening, closing and stopping using every control device in use.
  • Check the gate-leaf sequence, stops and deceleration; the leaves must not collide or bind.
  • Test each pair of photocells and each STOP device separately, including their response while the gate is moving.
  • Check the force settings and perform the measurements required to safely commission the specific gate.
  • Give the owner instructions for manually releasing the drives, safe operation and the maintenance schedule.

Check the automation at least every 6 months, or more often depending on operating conditions. In the event of a power failure, manually release the drives themselves according to their manuals.

For servicing, provide the control unit, board and motor identification, photocell and receiver types, the number of red BlueBUS flashes, and a photo of the wiring.

Source: original NICE MC800 manual IDV0544A00EN, Chapters 5 and 9.