NICE SNA3 - replacement control unit for NICE Spinbus SN6031 drives
| Product availability: | Currently unavailable |
|---|
Description of NICE SNA3 - replacement control unit for NICE Spinbus SN6031 drives
NICE SNA3 control unit is compatible with garage door operators NICE Spinbus SN6031. Includes a connector type SM for connecting radio receiver (SMXI, OXI, ...) from remote controls (Flor, Era Flor, Era One, Era Inti, ...).
Supports the technology BlueBUS, which makes it easy to connect additional devices (photocells, warning light, card readers, key switches, etc.) using only a two-core cable, with no need to observe polarity.
Thanks to the 24V technology, it is also suitable for the NICE Solemyo solar system, which provides power even in locations without access to an electricity supply. It is also possible to power the control unit using the NICE PS124 backup battery, which allows the garage door to be opened and closed several times for a few hours after a power outage. In standby mode, the control unit, with a connected control signal receiver consumes just 2 W (when powered by the PS124 battery, or by the Solemyo solar system, consumption is just 0.1 W).
Supports NICE Opera technology. Diagnostics using warning light.
After assessing the gate leaf length, the acceleration and deceleration intervals for opening and closing are set automatically. You can also adjust the force, speed etc. See drive control unit programming. Obstacle detection throughout the gate leaf's movement ensures safe motor operation.
NICE SNA3 control unit is suitable for the climatic conditions in Slovakia and meets all European safety standards.
Accessories compatible with the NICE SNA3 control unit
We recommend purchasing these compatible optional accessories for the control unit:
| What | Why | Type |
|---|---|---|
| Warning light | The warning light flashes to signal gate movement—ideal for driveways with poor visibility. It also has a built-in antenna for greater remote-control range. | |
| Photocells | When closing, they detect obstacles and stop the gate's movement, preventing it from hitting cars or people. | - MoonBUS (MOFB) |
| Transmitter |
For remote control of the gate. |
- FloR (Flo2R-s, Flo4R-s) |
| Receiver | Required for remote gate operation. | - OXI - SMXI |
| Antenna | For better remote control range. | - integrated into the warning light LUCYB, MLBT - ABFKIT antenna only, or ABF |
| Keypad | If you forget your remote control, or if many vehicles or people visit and you don't want to give everyone a remote or open the gate yourself. | - MOTXR |
Manual for the NICE SNA3 control unit and NICE Spinbus SN6031 drive
Download the manual for the NICE SNA3 control unit and NICE Spinbus SN6031 drive here:
Manual for the NICE SNA3 control unit and NICE Spinbus SN6031 drive
Wiring the NICE SNA3 control unit for the NICE Spinbus SN6031 drive
...to the mains
Simply plug the drive into a power outlet.
...additional devices
Warning: Before connecting, disconnecting or changing the wiring of additional devices, remember to disconnect the power supply at the circuit breaker, by removing the power fuse, or by disconnecting the backup battery.
NICE SNA3 control unit for the drive NICE Spinbus SN6031 provides the following inputs and outputs for additional devices:
| Input/output | Description | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Programmable output whose behavior can be set by Level II programming for L4; see Level II programming, L4 – Output indicator. It can be programmed for the following devices:
|
|||||||||||||
| Input for parallel connection of compatible devices using BlueBUS via a two-core cable that carries both the power supply and the communication signal. | |||||||||||||
| STOP (Stop) |
Input for devices that stop gate movement. The following devices can be connected:
|
||||||||||||
| Input for devices that step through gate movement (see Gate movement step-by-step operation). Normally open devices (NO) can be connected. | |||||||||||||
| OPEN (Open) |
Input for devices that control the gate opening movement (see Gate opening). Normally open (NO) devices can be connected. | ||||||||||||
| AERIAL (Antenna) |
input for the radio receiver antenna. The antenna is usually built into the warning light, for example: NICE LUCYB, NICE MLBT, or you can use a separate external antenna NICE ABFKIT. |
Gate opener fuses
![]() |
In the gate opener there are two fuses:
|
Standard wiring diagram:
Wiring
Route the cables and connect them to the control unit as follows:
| 1. Press the white cover and turn it | 2. Thread the cables through the opening, pass the antenna cable through the side eyelet, and connect all the cables. |
|---|---|
![]() |
![]() |
Gate opener photocells
The very user-friendly BlueBUS technology allows you to power and control up to 6 pairs of photocells using a two-core cable.
CONNECTING MULTIPLE PAIRS OF PHOTOCELLS NICE MOFB TO THE DATA NETWORK NICE BLUEBUS
Position the photocells around the gate or door as shown in the example layouts for complete wiring, and set the jumpers according to the jumper table for the NICE MOFB photocells gate opener. To prevent interference between pairs positioned close to one another, follow these example layouts, and ensure that the transmitters TX and receivers RX. Connect the photocells in parallel as shown (polarity does not need to be observed):
Example photocell wiring layout
| Sectional garage door | Up-and-over garage door |
|---|---|
![]() |
![]() |
If you need the photocells to work as gate openers (see FA1 and FA2 in the diagram), i.e. when you drive a vehicle between their optical axes, causing them to open the gate, you need to break connection A on both the transmitter TX and receiver RX, see diagram:
Jumper table for NICE MOFB gate opener photocells
![]() |
Connecting multiple pairs of photocells to the BlueBUS system is done by setting different jumper combinations, with each connected pair requiring a unique jumper configuration. Make sure that no two pairs in the same BlueBUS data network have the same configuration. For each pair of photocells, set the jumper on both the TX transmitter and RX receiver to the same value. If a jumper type uses only one jumper, always place the other one in the unused compartment, as shown in the image on the left. |
| Photocell pair designation | Jumper using a combination of jumpers |
|---|---|
| FOTO | ![]() |
| FOTO II | ![]() |
| FOTO 1 | ![]() |
| FOTO 1 II | ![]() |
| FOTO 2 | ![]() |
| FOTO 2 II | ![]() |
|
FOTO 3 WARNING: UNAUTHORIZED CONFIGURATION! |
![]() |
|
FA1 |
![]() |
|
FA2 |
![]() |
If a photocell needs to be replaced for any reason, simply set it to the same jumper as the original one; there is no need to run the device recognition phase.
Radio receiver for operators
![]() |
SNA3 control unit NICE Spinbus SN6031 operator features an SM connector for connecting an external radio receiver (e.g. NICE OXI, NICE SMXI). This receiver is essential for receiving commands transmitted from remote controls, and is therefore required to operate the sliding gate remotely with a remote control. |
Pairing remote controls with the operator
Visit our guide to pairing a remote control with an operator, or click here:
Recognition of connected operator devices
After connecting, disconnecting or changing the wiring of any accessories to the BlueBUS inputs and STOP the following must be performed: the accessory recognition phase. The operator will alert you that this procedure is required by flashing LEDs L1 and L2.
![]() |
|
Gate leaf length recognition
For the gate to move correctly (specifically, to calculate the acceleration and deceleration distances and partial opening), the operator must determine the length of the gate leaf. During this procedure, the operator moves the gate from one end stop to the other and determines its length.
Operator programming
The SNA3 control unit for the Spinbus SN6031 operator lets you program several functions, either by switching a function on or off using Level I programming, or by setting a default parameter using Level II programming.
The SNA3 control unit has three buttons for operating and programming the operator:
![]() |
Button | Use |
|---|---|---|
| Open | The button allows you to command the gate operator to open the gate. It is also used during programming to move the value of the parameter being programmed up. | |
| Stop/Set | The button allows you to command the gate operator to stop the gate. Press and hold it for 5 seconds the first time to enter Level I programming. Press and hold it again to enter Level II programming. for the current LED. | |
| Close | The button allows you to command the gate operator to close the gate. It is also used during programming to move the value of the parameter being programmed down. |
Level I Programming
At Level I, programming turns the selected function on or off. When a function is enabled, the corresponding LED on the control unit lights up. All functions are disabled by default.
To enter Level I programming, press and hold the “Stop/Set” button for approximately 5 seconds, until LED L1 starts flashing. Then use the “Open” and “Close” buttons to move the current LED up or down. You have 10 seconds for each action; otherwise, the operator will exit programming mode. When the flashing LED reaches the LED for the function you want to enable or disable, press the “Stop/Set” button once to make it flash faster (function enabled) or slower (function disabled), then leave it as it is and allow the operator to exit programming mode within 10 seconds. If everything worked correctly, the corresponding LED for the enabled function will remain lit.
List of programmable functions that can be enabled:
| LED | Function | Description |
|---|---|---|
| L1 | Automatic closing |
After a certain time (set under “Level II Programming – Pause duration”), the gate will start closing automatically after it has opened. If this function is disabled, the gate can only be operated by a command from the gate remote control and similar devices. |
| L2 | Close after photocell interruption |
This function keeps the gate open only for the time required for a vehicle to pass through. Once the photocells are clear (the vehicle has passed through), the gate will start closing automatically after 5 seconds. This function operates in one of two ways, depending on whether automatic closing is enabled (see the previous function). Automatic closing enabled – the gate stops when the photocells are clear and starts closing after 5 seconds. This means the gate may not open all the way. |
| L3 | Motor force |
This function affects the motor’s sensitivity to obstacles. If this function is disabled, the operator is less sensitive, which is suitable for larger and heavier gates.. If your gate is small and lightweight, you can enable this function.. |
| L4 | Standby mode |
This function reduces power consumption to a minimum. It is particularly useful when powered by a backup battery (e.g. NICE PS124). When this function is enabled, the control unit switches off one minute after the gate’s last movement. BlueBUS input (and therefore all devices connected to it), as well as all LEDs except the BlueBUS LED, which will flash slowly. In this state, when a command is received, the control unit first restarts and only then carries out the command. |
Level II Programming
At Level II, programming sets values for the individual functions (these functions differ from those in Level I).).
Forget about Level I programming. To enter Level II programming, press and hold the “Stop/Set” button for approximately 5 seconds, until LED L1. starts flashing. Then use the “Open” and “Close” buttons to move the current LED up or down. You have 10 seconds for each action; otherwise, the operator will exit programming mode. When the flashing LED reaches the LED for the function whose parameter you want to set, press and hold the “Stop/Set” button to enter the settings for that LED. The LED that remains lit (while you continue holding “Stop/Set”) indicates the current parameter value. You can change this value up or down using the “Open” or “ "Close” button (while continuing to hold “Stop/Set”), then release the “Stop/Set” button and allow the operator to exit programming mode within 10 seconds. To check that everything worked correctly, repeat the procedure without changing the parameter value.
List of programmable functions with adjustable settings:
|
Input LED — Name |
Setting LED — Value |
|---|---|
| L1 — Pause duration If the value is “Automatic closing“ in Level I programming. |
L1 — 10 seconds L2 — 20 seconds L3 — 40 seconds L4 — 80 seconds |
|
Sets the gate movement sequence triggered by repeatedly pressing, for example, a button on the gate remote control, or by activating the STEP-BY-STEP input (also referred to as P.P., or Step-by-step). |
L1 — Open/Stop/Close/Stop L2 — Open/Stop/Close/Open L3 — Condominium L4 — Hold-to-run |
|
Sets the gate speed during normal operation (excluding acceleration and deceleration). |
L1 — Very slow (55%) L2 — Slow (70%) L3 — Medium (85%) L4 — Fast (100%) |
|
Sets when a signal should be sent to the FLASH output. |
L1 — Gate-open indicator L2 — Warning light L3 — Electromechanical lock L4 — Electromagnetic lock |
Connecting additional external devices to the drive
![]() |
If you need to connect additional devices to the drive that require an external power supply (e.g. indicator lights, key switch, magnetic cards, etc.), connect the device as shown in the diagram. The supplied voltage is 24Vdc -30% to +50%, with a maximum current of 100mA. |
Special drive functions
Gate held open
If the command to the STEP-BY-STEP input (also referred to as P.P. or Step-by-step) lasts longer than 3 seconds, the control unit will keep the gate open for as long as the command is active. This function is particularly useful when used with a timer.
Forced operation
If a safety device fails, or if an immovable obstacle, for example, gets into the beam of the photocells and the gate will not move for safety reasons, you can activate the “Hold-to-run” mode, either permanently in Level II programming. in the L2 - Step-by-step mode setting L4 - Hold-to-run, or temporarily:
- Send a command to the gate (using aremote control, key switch etc.)
- If there is a problem, the gate will not move and the warning light will probably indicate an error.
- So, within 3 seconds of the previous command, send the command again and hold it.
- The gate will move while you hold the command and stop when you release it.
Troubleshooting the drive
If anything is unclear or you have any other issues, feel free to contact our technical support team for NICE drives.
Depending on the nature of the problem
During installation (or if the drive fails), you may encounter one of the following problems:
|
Problem |
Possible solution |
|---|---|
|
The gate does not respond to the remote control, and the LED on the remote control does not light up. |
Check that the batteries in the remote control are working; if not, replace them. See the manual for the specific remote control for instructions. |
|
The gate does not respond to the remote control, but the LED on the remote control lights up. |
Check whether the remote control has been stored in the receiver memory correctly, or try remote control programming it again. |
|
The gate does not move and the BlueBUS LED does not flash.
|
Check whether the drive is receiving 230V power.. If it is, test both fuses and, if necessary, replace them with new fuses of the same type. |
|
The gate does not move and the warning light does not flash. |
Check whether the drive has registered the command. When a command is sent using a remote control the BlueBUS LED should flash rapidly twice. If the command is sent by another device via the STEP-BY-STEP input (P.P.), the corresponding indicator should light up STEP-BY-STEP LED. |
|
The gate does not move and the beacon flashes several times. |
Count the number of flashes and see Diagnostics using beacon flashes. |
|
The gate starts moving, but stops immediately and begins moving in the opposite direction. |
The programmed motor force is probably too low for your gate. Check that there are no obstacles preventing the gate from moving, and increase the drive force if necessary. |
|
The gate starts, but the beacon does not work. |
Check whether there is voltage at the FLASH output during gate operation (the voltage level is not important, approx. 10-30Vdc). If there is voltage at the output, the problem is likely with the beacon (or another device); try replacing it with a similar one to see if it works. If there is no voltage at the output, the FLASH output may be overloaded. Check whether there is a short circuit in the wiring. |
Diagnostics using beacon flashes
While the gate is operating beacon flashes regularly once every second. If a problem occurs, the beacon signals an error with two faster consecutive series of flashes.
|
Flash sequence |
Error |
Solution |
|---|---|---|
|
1 flash 1-second pause 1 flash |
BlueBUS error
|
Devices connected to the BlueBUS input do not respond as expected based on the devices detected during the device detection phase. Repeat the detection phase. If that does not help, try once more; otherwise, use a process of elimination to identify the faulty device and replace it (purchase, return under warranty, or repair it). |
|
2 flashes 1-second pause 2 flashes |
Photocell activation |
The photocells, which is normal if their beam is interrupted while the gate is closing. If the beam was not interrupted, the photocells may be dirty, exposed to glare, or faulty. |
|
3 flashes 1-second pause 3 flashes |
Motor force limiter activated
|
While moving, the gate detects increased friction – the gate may not be properly adjusted. Try moving it manually and adjusting the gate. Otherwise, it usually helps to increase the motor force. |
|
4 flashes 1-second pause 4 flashes |
STOP input activated
|
A command was sent to the STOP input, so if this behavior is unexpected, check the devices connected to it. |
|
5 flashes 1-second pause 5 flashes |
Internal control unit error |
Wait 30 seconds and try again. If the problem persists, try resetting it. Otherwise, the control unit will probably need to be repaired or replaced. |
|
6 flashes 1-second pause 6 flashes |
The hourly operation limit has been reached. |
Wait a few minutes for the cycle limiter to drop below its limit. |
|
7 flashes 1-second pause 7 flashes |
Internal electronic circuit error. |
Disconnect the entire drive for a few seconds and try again. If the problem persists, try resetting it. Otherwise, the control unit will probably need to be repaired or replaced. |
|
8 flashes 1-second pause 8 flashes |
Continuous command active.
|
A command is being sent continuously to the drive – check the devices connected to the OPEN input. If you have a timer connected, it is probably the cause.
|
Diagnostics using LED flashes
On the SNA3 control unit of the NICE Spinbus SN6031 drive, there are two sets of LEDs. Each set uses flashing or steady lights to indicate normal operation of the control unit or diagnose errors, as shown in the following tables.
Horizontal BLUEBUS, STOP, PP and OPEN LEDs
|
Indicator |
Status |
Solution |
|---|---|---|
|
BlueBUS LED |
||
|
Off |
Error
|
Check the mains power connection. If it is correct, check fuses F1 and F2 and replace them, if necessary, with new fuses of the same rating. |
|
On |
Serious error
|
Try disconnecting the control unit, or all inputs. If that does not help, reset it and if that still does not help, the control unit will probably need to be replaced. |
|
Flashing at one-second intervals |
Everything is OK |
Normal control unit operation. |
|
2 quick flashes |
Input status changed |
Normal operation – the status of the STEP-BY-STEP, STOP, OPEN, have been activated photocells, or the drive received a command from the remote control. |
|
Flashing sequences separated by a one-second pause |
More options |
The number of flashes in each sequence corresponds to error diagnostics via the warning light. |
|
STOP LED |
||
|
Off |
The STOP input has been activated |
Check the devices connected to the STOP input. |
|
On |
Everything is OK |
The STOP input is not active. |
|
STEP-BY-STEP LED (also referred to as P.P., Step-by-Step) |
||
|
Off |
Everything is OK |
STEP-BY-STEP input is not active. |
|
On |
The STEP-BY-STEP input has been activated |
Normal operation of the control unit if an active device was connected to the STEP-BY-STEP input. |
|
OPEN LED |
||
|
Off |
Everything is OK |
The OPEN input is not active.
|
|
On |
The OPEN input has been activated |
Normal operation of the control unit if an active device was connected to the OPEN input. |
Vertical LEDs L1–L4
|
Indicator |
Solution |
|---|---|
|
LED 1 |
|
|
Off |
During normal operation, indicates that the Automatic closing function is off. |
|
On |
During normal operation, indicates that the Automatic closing function is on. |
|
Flashing |
|
|
LED 2 |
|
|
Off |
During normal operation, indicates that the Close after photocell activation function is off. |
|
On |
During normal operation, indicates that the Close after photocell activation function is on. |
|
Flashing |
|
|
LED 3 |
|
|
Off |
During normal operation, indicates that the Motor force function is off. |
|
On |
During normal operation, indicates that the Motor force function is on. |
|
Flashing |
|
|
LED 4 |
|
|
Off |
During normal operation, indicates that the Standby mode function is off. |
|
On |
During normal operation, indicates that the Standby mode function is on. |
|
Flashing |
|
Installing a backup battery in the NICE Spinbus SN6031 drive
NICE PS124 backup battery is not included as standard with the drive, but it can be ordered separately. It is used in the event of a power outage, when it will power the gate drive. The battery is continuously recharged from the mains.
Resetting the control unit
1. Press and hold simultaneously first (Open) a third (Close) button.
2. When all the LEDs light up, release.
3. Wait until the control unit resets.
Technical specifications of the NICE SNA3 control unit for the NICE Spinbus SN6031 operator
| Model | NICE SNA3 | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| Type description | Control unit for gear motor NICE Spinbus SN6031 for automatic operation of garage doors in private settings. | ||||||||||
| Backup power supply | can be purchased and installed NICE PS124 backup battery | ||||||||||
| Lighting | No, the bulb is on the operator. | ||||||||||
| Beacon output |
Depending on the programmed output:
|
||||||||||
| BlueBUS output | one output for 6 BlueBUS devices | ||||||||||
| STOP input | for normally open, normally closed and devices with a constant resistance of 8,2KΩ | ||||||||||
| STEP-BY-STEP input (P.P., step-by-step) | normally open (closing triggers the “Step-by-step") | ||||||||||
| Radio receiver | without a receiver, “SM” connector for receivers NICE SMXI, NICE OXI etc. | ||||||||||
| Antenna input | 52Ω for RG-58 coaxial cable (or similar) | ||||||||||
| Programming functions | 4 on/off functions (Level I programming.) 4 adjustable functions (Level II programming.) |
||||||||||
| Self-learning functions |
|
||||||||||
| Operating temperature | -20°C to +50°C | ||||||||||
| Use in saline, acidic and potentially explosive environments | no | ||||||||||
| Protection class | IP00 |