Connecting an external receiver from another brand to a NICE Robus and Run operator
An external receiver from another brand generally requires a power supply and a relay output. Robus and Run operators provide 24 V DC, and the relay output is connected to the same input as a wired button.
Step 1. Powering the external receiver
If you need to connect additional devices that require external power to the operator (e.g. external receiver, indicator lighting, key switch, magnetic cards, etc.), connect the device as shown. The supplied voltage is 24 V DC, -30% to +50%, with a maximum current of 100 mA.

(NICE RBA3) (NICE RBA3R10)
Step 2. Relay input
Connect the relay to the SBS input (marked P.P. on older control units). Alternatively, you can connect the relay to the OPEN input and use the automatic closing function. In this case, the external receiver will only open the gate, and the automatic closing function will close it after a timed pause.
Next, perform the “Recognition of connected operator devices” procedure on the Robus as follows:
Step 3. Recognition of connected operator devices
Whenever you connect, disconnect, or change the wiring of auxiliary devices on the BlueBUS and STOP inputs, the recognition phase for auxiliary devices must be carried out.
- Press and hold the “Open” and “Stop/Set” buttons
- As soon as L1 and L2start flashing rapidly, release the buttons
- Wait a few seconds until the control unit has completed the device recognition process.
- If everything went well, the STOP LED should be lit, and L1 and L2 should go out. Alternatively, L3 and L4may start flashing if you have not yet completed the gate leaf length recognition phase.
Example wiring of the GSM module GSM-05 to the NICE RBA3R10 control unit (NICE ROBUS operator):

Example wiring of the GSM module GSM LITE 3+ to the NICE RBA3R10 control unit (NICE ROBUS operator):