NICE SBAR barrier gate – without arm


Product availability: In stock

We normally dispatch goods within 24 hours.


NICE SBAR barrier gate – without arm NICE SBAR barrier gate – without arm
NICE-SBAR
In stock
€637.08 excluding VAT
€783.61 including VAT

 pcs
Weight
46 kg

Description of NICE SBAR barrier gate – without arm

NICE SBAR is an electromechanical barrier for controlling vehicle access, supplied without a boom. It has a 24 V DC motor and a built-in control unit XBA20 R10. The standard setup is powered from a 230 V AC; 24 V is the motor voltage.

A steel cabinet with a protective finish, a balancing spring and an elliptical boom XBA19 make up a setup for an entrance up to 4 m wide. Choose the boom and accessories separately or as part of a complete kit. The drive is self-locking; in the event of a power failure, it can be released with a key or powered by an optional battery PS124.

The XBA7 flashing light, which signals movement and fault conditions. The following wiring and programming instructions are for the XBA20 R10 with OPEN / STOP / CLOSE buttons and LEDs L1–L8. If the barrier is already installed, first check the board markings and layout.

Quick navigation
Selection and limitsKits and alternatives
AccessoriesInstallation
StopsWiring
Terminals and wiring diagramPhotocells
Initial start-upProgramming
Radio and backupDiagnostics
ResetManual release
MaintenanceSpecifications
PDF manual

When to choose the NICE SBAR barrier

What to checkLimit and what it means
Clear opening widthUp to 4 m; the length of the purchased profile is not the clear opening width.
Opening timeAt least 4 s; more than 5 s with XBA4 lights. Settings, the boom and its accessories affect movement.
Operating cyclesUp to 100 cycles/h at rated torque; 80 cycles/h with XBA4 lights.
Space for the boomCheck the boom's path when opening and closing, the available clearance height, distance from vehicles and access to the manual release.
Supplied without a boomChoose the boom, safety devices and remote control to suit the setup.

The barrier controls vehicle access. Provide a separate pedestrian passage and choose safety devices according to the specific risks. The motor's obstacle detection does not replace photocells or other required safety devices. Do not use the boom as a pedestrian gate.

Barrier kits with boom and accessories

The SBAR kit includes a 4 m boom and additional equipment. The other kits in the comparison use a different barrier model; a longer boom is not an accessory that can be fitted to the SBAR at will. Check the contents and overall length of the setup on the specific product page.

NICE SBAR barrier kits
SBAR – 4 m boom

NICE SBAR barrier kit with 4m boom and accessories

XBA20 R10, XBA19, XBA7, XBA13 rubber, OXIBD, ON2E, EPMB and SIA1 anchor set, depending on the kit configuration.

What you need for the setup

WhatWhyType
XBA19
NICE XBA19 – white-painted aluminium boom 45x58x4270mm
Elliptical boom, 45 × 58 mm; supplied profile length: 4,270 mm. The profile length is not the clear opening width.
XBA13
NICE XBA13 – impact protection rubber strip 9x1m
Impact protection rubber strip, pack of 9 × 1 m; fit it before balancing.
XBA4
NICE XBA4 – clip-on warning lights for a 4m boom
Boom lights; they affect operating time and cycle rate.
XBA7
NICE XBA7 – built-in flashing light/automatic lighting for the barrier
Optional beacon or lighting in the top cover.
WA11
NICE WA11 – orange, height-adjustable support for the boom
Standalone height-adjustable support for the lowered boom.
WA10
NICE WA10 – set of 24 red reflective stickers
24 reflective stickers for improved boom visibility.
  • Mechanical accessories
EPMB
NICE EPMB – Era Photocell Medium – BlueBUS-connected photocells (1 pair)
BlueBUS photocells monitor hazardous areas; choose the function according to the risks.
OXIBD
NICE OXIBD – internal two-way radio receiver
Plug-in radio receiver for compatible remote controls; not automatically included with a standalone operator.
PS124
NICE PS124 – backup battery for the operator with integrated charging
Backup operation during a power outage.

A more space-saving alternative to photocells is EPSB. Both use BlueBUS; the relay-operated EPM/EPS models cannot be connected to BlueBUS as direct replacements.

Cabinet installation and anchoring

Disconnect the mains supply and battery before starting work. Check that all parts are present and in good condition, that the substrate is sound, and assess the risk of flooding and ensure the boom has a clear path.

Left- and right-hand configurations

The barrier is supplied in its original left-closing configuration. For a right-hand configuration, the balancing lever and spring must be mechanically repositioned and the level I/L8. Changing the electronic setting alone is not sufficient. Adjust the spring as shown for the relevant mechanism, with the boom securely restrained; do not disconnect the spring while it is under uncontrolled load.

  1. Choose a level, solid substrate and mark the four anchor points. Install conduits for the mains and other cables.
  2. On an existing base, use suitable anchors for the material and load; these are not automatically included with the cabinet.
  3. For a new foundation, secure the anchors to the foundation plate with nuts and washers on both sides. Tighten the lower nut to the end of the thread.
  4. Position the plate parallel to the boom, level and at the correct height. Allow the concrete to cure fully; do not load the cabinet before it has cured.
  5. Position the cabinet and securely tighten all four anchor connections. Prevent water and condensation from entering the electronics through the conduits.

NICE SBAR – anchoring the cabinet to a prepared foundation

NICE SBAR – foundation plate and anchors in concrete

The concrete base should be reinforced, at least 0.15 m thick and have a volume greater than 0.2 m³. Specify the foundation and anchor load capacity according to the ground conditions and load; select four M12 anchors to meet the installation requirements, not solely on the basis of the hole diameter.

Installing the boom and safety accessories

  1. Insert two pins into the output shaft. Orient the bracket for a vertical boom and secure it firmly using the appropriate washers.
  2. Fit the bracket cover and leave the mounting screws loose for now.
  3. Slide the protective rubber strip and connectors into the boom grooves, then fit the end cap and rubber-strip caps. The rubber strip may extend approximately 1 cm beyond the end.
  4. Insert the support inserts from the opposite end, slide the boom fully into the bracket and securely tighten its four mounting screws.
  5. Install any lights and other approved accessories before balancing. After changing the boom length or accessories, always check the balance again.

NICE SBAR – installing the boom bracket

NICE SBAR – protective rubber strip and connectors on the boom

Adjusting the mechanical stops

  1. Hold the boom and release the gearbox.
  2. Manually move the boom through its full opening and closing range.
  3. Use stop screws A/B to set the boom horizontally when closed and vertically when open.
  4. Securely tighten the locknuts after adjustment. Do not use motor force as a substitute for the stops.

NICE SBAR – adjustment screws for mechanical stops A and B

Balancing the boom with all accessories fitted

  1. Hold the boom, release the motor, set it to approximately 45° and check that it does not move significantly on its own.
  2. If it rises, reduce the spring tension; if it falls, increase it. Before moving its mounting point, raise the boom to the fully open position and secure it safely.
  3. For the mechanism shown, move attachment point B towards the center to reduce tension, or outwards to increase it.
  4. Repeat the check at approximately 20° and 70° as well. The boom must not fall or rise significantly on its own.
  5. Check manual movement in all positions and in both directions, then re-engage the gearbox lock.

NICE SBAR – balancing spring and attachment point B

The permissible manual force during the check is approximately no more than 50 N, applied perpendicular to the boom at a distance of 1 m from its axis, in all positions and both directions. This is the upper limit, not the target setting. Balancing is a mechanical adjustment; do not compensate for an imbalance by increasing the motor force.

Preparing the wiring

CableCross-section and length
Mains power supply3 × 1.5 mm², up to 30 m; over 30 m, 3 × 2.5 mm² and provision for protective earthing of the automation system as required for installation.
BlueBUS2 × 0.5 mm², up to 30 m.
Key switch4 × 0.25 mm², up to 30 m. Compatible two-wire keypad/reader has its own requirements.
Boom lights / beacon in the coverUse the specified accessory cables; allow free movement without tension or pinching.

Cables must be suitable for the environment and conduits. Route the 230 V supply through a strain relief to the L/N mains terminals and protective earth (PE). Route the other cables so they do not touch the moving mechanism. Do not connect 230 V to low-voltage terminals.

XBA20 R10 control unit – terminals and wiring diagram

NICE SBAR – control unit terminals and wiring diagram

Terminal / connectorPurpose and conditions
FLASHProgrammable output. For a beacon, use a compatible 12 V device, bulb max. 21 W; select the function at level II/L4. For XBA4, set the boom lights. The FLASH output is polarized; for polarity-sensitive accessories, check the markings and voltage. Polarity does not matter for a bulb.
BlueBUSCompatible two-wire devices connected in parallel, with no polarity. Maximum 12 BlueBUS load units; this does not automatically mean 12 pairs.
STOPLearned safety input for NO, NC or 8.2 kΩ; a volt-free contact or resistor alone is connected without regard to polarity. A change in the learned state stops movement; wire a resistive safety edge according to its instructions.
SbSVolt-free NO contact for step-by-step control, with no polarity; set the function at II/L2.
OPEN / CLOSESeparate volt-free NO contacts for opening / closing, with no polarity.
ANTENNAReceiver antenna, RG58 coaxial cable; connect the centre conductor and shield as shown for the connector.
SM / IBT4NRadio receiver connector / BusT4 interface for compatible programming accessories. It is not a 230 V input.

XBA4 boom lights and XBA7 beacon

Connect XBA4 to FLASH with the function set to boom lights. Leave enough slack in the cable for the boom to rotate, protect it with a grommet, and shorten it only at the marked points; seal the end after shortening. If the lights do not come on with the correct setting, disconnect the mains and battery and swap the two wires at FLASH; then restore power and test the function. Power supplies must be switched off before carrying out any work.

XBA7 is a separate accessory installed in the barrier housing. With the power supplies switched off, connect its supplied cable to the light and to the dedicated connector on the SBAR board, as shown, then connect the designated earth wire. Do not use FLASH for the boom lights or the 100 mA auxiliary power supply in its place. Flashing and illumination are different functions; after setting, check both operation and diagnostics. Installation details are on the XBA7 page.

NICE SBAR – dedicated XBA7 beacon connector

NICE XBA7 – connecting the designated earth wire

24 V power supply for accessories

The auxiliary power supply is 24 V DC (−30 / +50 %), max. 100 mA. The left and right terminals below are identified when viewing the connectors with the STOP and SbS labels readable, in the same orientation as in the original image.

Polarity on the boardAccessory connection
Plus (+)Left terminal of the SbS pair → accessory power supply + terminal.
Minus (−)Right terminal of the STOP pair → accessory power supply − / 0 V terminal.

NICE SBAR – right STOP terminal is minus and left SbS terminal is plus

The total current draw of connected accessories must not exceed 100 mA. The STOP/SbS power supply pair must not be confused with the STOP contact or the step-by-step command: connect a volt-free contact across the two terminals of its respective pair. BlueBUS photocells are powered by BlueBUS, not by this auxiliary pair.

BlueBUS photocells – addressing and checks

Set the TX and RX of one pair with the same jumpers. The next pair must have a different address. See the EPMB page and the original illustration below. After adding, removing or readdressing devices, perform device learning and safety tests.

NICE SBAR – addresses and BlueBUS photocell jumper wiring

FOTO / FOTO II and FOTO 1 / FOTO 1 II protect during closing; FOTO 2 / FOTO 2 II are used during opening. Other configurations shown, FOTO 3 and FA1/FA2, are also supported. FA1/FA2 are an opening command, not automatically a safety device. Check the function and positioning for the specific entrance.

Initial start-up and learning

Before switching on, the anchoring, boom and accessories, balancing, stops and wiring must all be complete. Keep the movement area clear. After switching on, check that BlueBUS flashes regularly, the photocells respond, and the lights are off when idle, as configured.

1. BlueBUS and STOP device learning

  1. Press and hold OPEN + STOP/SET together for approximately 3 seconds.
  2. When L1 and L2 start flashing rapidly, release both buttons.
  3. Wait for the process to finish. STOP should be lit and L1 and L2 should be off; L3 and L4 may indicate that position learning is required.

Perform this procedure even if no accessories are connected to the board. Repeat learning after changing any devices.

2. Opening and closing positions

  1. Release the motor, set the boom to approximately 45°, then lock the motor.
  2. Press and hold CLOSE + STOP/SET for approximately 3 seconds; release when movement begins.
  3. The barrier will perform closing – opening – closing. Check that the correct mechanical stops are reached.
  4. If the movement or stops are incorrect, press STOP immediately. After correcting the issue, repeat the entire procedure; do not use incomplete learning as a finished setting.

3. Automatic force learning

When L5 and L6 are flashing, complete three complete opening and closing cycles, initiated by the user, without interruption, until both LEDs go out. Automatic closing functions are temporarily disabled during this learning procedure. Learning is also required after changing the speed or deceleration; check the resulting forces and safety.

Tests before normal use

Test opening, closing, Stop, each control and each safety device individually. Check deceleration before the stops, manual release and balance. Photocells must respond throughout the protected area; also perform the prescribed tests and impact force measurements. Hand over the key, release instructions and maintenance schedule to the user.

Control unit programming

OPEN ▲ opens and moves through the options, STOP/SET ■ stops and confirms, CLOSE ▼ closes and moves through the options in the opposite direction. The following tables use eight LEDs, L1–L8; the input LED selects a parameter, and the value LED shows its setting.

Level I – turning functions on and off

  1. Press and hold STOP/SET until L1 starts flashing, then release the button.
  2. Use OPEN/CLOSE to select the LED for the required function.
  3. Briefly press STOP/SET to change the state: a short flash means OFF, a long flash means ON.
  4. Select the next function with OPEN/CLOSE, then toggle it again with STOP/SET. After 10 seconds without a button press, the changes are saved and programming ends.

Function and descriptionON/OFF status
L1 – Automatic closing
ON: after opening and the set pause, closing starts. OFF: waiting for the next command. Set the time at level II/L1.
ON = on
OFF = off
Factory setting: OFF
L2 – Close after photocell
ON: closes 5 s after the photocell beam is cleared. With automatic closing off, it completes the opening cycle first; with it on, it may stop opening as soon as the beam is cleared. A STOP command cancels this function for the current cycle. OFF: closing is controlled by the Automatic Closing function and the set pause time.
ON = on
OFF = off
Factory setting: OFF
L3 – Always close
ON: after power is restored, closes if it detects that the gate is open; the warning light flashes for 3 s before movement. OFF: remains in its original position.
ON = on
OFF = off
Factory setting: OFF
L4 – Standby
ON: one minute after a cycle, switches off BlueBUS and most LEDs; a new command activates them again. Saves battery power. OFF: power-saving mode is disabled.
ON = on
OFF = off
Factory setting: OFF
L5 – Extended slowdown
ON: doubles the slowdown distance when opening and closing. OFF: short slowdown. After changing this, relearn the force settings.
ON = on
OFF = off
Factory setting: ON
L6 – Pre-flashing
ON: the warning light starts flashing 3 s before movement. OFF: it flashes at the same time as movement.
ON = on
OFF = off
Factory setting: OFF
L7 – Increased sensitivity
ON: increases obstacle-detection sensitivity. Force and speed must be set and tested together. OFF: standard sensitivity.
ON = on
OFF = off
Factory setting: OFF
L8 – Motor direction
OFF: original configuration, closing to the left. ON: closing to the right. Also change the mechanical configuration and relearn the positions.
ON = on
OFF = off
Factory setting: OFF

Level II – Adjustable parameters

  1. Press and hold STOP/SET until L1 flashes, then release it.
  2. Use OPEN/CLOSE to select the parameter input LED.
  3. Press and hold STOP/SET; after about 3 s, the value LED lights up. Keep holding STOP/SET and use OPEN/CLOSE to select the new value.
  4. Release STOP/SET. Set the next parameter in the same way; programming ends if no button is pressed for 10 s.

Factory default values are shown in bold. Settings on a board that is already in use may differ. SBAR forces are also adjusted through learning. L8 history has no adjustable factory setting.

Input LED – name and descriptionSetting LED – value
L1 – Pause time
Applies when automatic closing is enabled. Check the default pause time on your board’s value LED.
L1 – 5 s
L2 – 10 s
L3 – 20 s
L4 – 40 s
L5 – 60 s
L6 – 80 s
L7 – 120 s
L8 – 200 s
L2 – SbS step-by-step mode
Sequence of commands for wired SbS and the first radio command. The hold-to-run mode requires the command to be held down.
L1 – Open – stop – close – stop
L2 – Open – stop – close – open
L3 – Open – close – open – close
L4 – Condominium mode; a command lasting more than 2 s triggers Stop
L5 – Condominium mode 2; a command lasting less than 2 s triggers partial opening
L6 – Step-by-step mode 2
L7 – Hold-to-run mode
L8 – Automatic opening, hold-to-run closing
L3 – Motor speed
After changing this, perform automatic force learning.
L1 – V1 – 30%
L2 – V2 – 47%
L3 – V3 – 65%
L4 – V4 – 82%
L5 – V5 – 100%
L6 – Open V3, close V2
L7 – Open V4, close V3
L8 – Open V5, close V4
L4 – FLASH output
The function must match the connected device and its voltage. XBA4 requires arm lights.
L1 – Open-arm indicator light
L2 – Active when the arm is closed
L3 – Active when the arm is open
L4 – Warning light
L5 – Arm lights
L6 – Electric lock
L7 – Electromagnetic lock
L8 – Service indicator light
L5 – Opening force
Relative control sensitivity; learning may change it. Do not compensate for poor balancing by increasing the force.
L1 – Force 1 – low
L2 – Force 2
L3 – Force 3
L4 – Force 4
L5 – Force 5
L6 – Force 6
L7 – Force 7
L8 – Force 8 – high
L6 – Closing force
Check safety and impact forces after every change.
L1 – Force 1 – low
L2 – Force 2
L3 – Force 3
L4 – Force 4
L5 – Force 5
L6 – Force 6
L7 – Force 7
L8 – Force 8 – high
L7 – Service alert
Number of manoeuvres before the service alert. Does not replace regular maintenance.
L1 – 2,500 manoeuvres
L2 – 5,000 manoeuvres
L3 – 10,000 manoeuvres
L4 – 15,000 manoeuvres
L5 – 20,000 manoeuvres
L6 – 30,000 manoeuvres
L7 – 40,000 manoeuvres
L8 – 50,000 manoeuvres
L8 – Fault history
Read-only display of the last eight manoeuvres; display procedure.
L1 – Result of the 1st manoeuvre – latest
L2 – Result of the 2nd manoeuvre
L3 – Result of the 3rd manoeuvre
L4 – Result of the 4th manoeuvre
L5 – Result of the 5th manoeuvre
L6 – Result of the 6th manoeuvre
L7 – Result of the 7th manoeuvre
L8 – Result of the 8th manoeuvre

If two adjacent value LEDs flash for pause time, speed, force or the service alert, the current value lies between them. OPEN/CLOSE rounds it to one of the available levels. Flashing L1 or L8 may indicate a value outside the tabulated range. While the system is moving, the LEDs show the instantaneous load; this is not the same scale as the force setting.

Do not compensate for friction, incorrect balance or an obstruction by increasing the force. After changing the force or speed, repeat the safety tests and measure the impact forces.

Remote control and backup power

Insert the radio receiver into the SM connector with both mains and battery power switched off. A standalone motor or barrier control cabinet does not automatically include a receiver and controller; check the equipment supplied with the specific kit. Current kits use OXIBD. Pairing, deleting transmitters and locking the radio memory are configured on the receiver according to its own instructions.

Receiver output in default modeCommand
1Step-by-step (SbS)
2Partial opening
3Open
4Close

NICE transmitters select according to the receiver's coding. Era One, Era Inti and MYGO transmitters with compatible coding pair with the corresponding family; matching frequency alone does not confirm compatibility. Do not assess mixing different coding types in one memory solely by the transmitter name.

PS124 backup battery

PS124 is an optional 24 V rechargeable battery. It provides a limited number of manoeuvres during a power failure; the number depends on charge, temperature and load. Connect it to the designated battery connector only after installation and programming. Switch off the mains before connecting, secure the battery in place, then restore power after connection. Disconnect the battery as well during servicing.

Use the supplied PS124 connecting cable: the narrower connector goes to the battery, the wider one to the board. Connect it to the designated battery connection, not to BlueBUS, FLASH or the 24 V auxiliary output. With the original supplied PS124 cable, polarity (+/−) is not specified; use both designated connectors. Do not force or modify the connectors.

  1. With the mains disconnected and a charged battery connected, L2 on the PS124 should confirm that the automation system is powered.
  2. When the mains is switched on, L1 should confirm charging. If the battery is discharged, leave the system to charge and repeat the test.
  3. Test a complete manoeuvre on mains power, then disconnect the mains and check opening and closing on battery power. Speed may be lower when running on backup power.
  4. Restore mains power after the test.

For solar-only power supply Solemyo SYKCE30 the drive must not be connected to the mains at the same time. System selection and connection of the PSY24 must take into account the specific control board, number of cycles, accessories and local light conditions.

Diagnostics and troubleshooting

The beacon's short flashes form two identical groups separated by approximately 1 s. Count the flashes in one group. During normal operation, BlueBUS flashes once per second; two quick flashes confirm an input change.

FlashesMeaning and what to check
2A photocell is blocking movement. Remove the obstruction, clean and align TX/RX; check the addresses.
3Increased resistance / force limit triggered. Check the mechanism and balance; do not increase the force blindly.
4STOP triggered. Check the contact or resistive circuit; do not bypass the safety input to address a fault.
5Internal parameter error. Disconnect all power supplies and reconnect them. If the fault persists, perform a reset followed by a learning procedureas described in the manual; if that does not help, the control board requires servicing.
6Manoeuvre frequency exceeded. Wait a few minutes and observe the permitted number of cycles.
7Internal electrical fault. Disconnect both the mains and battery; if the fault recurs, the control board or motor wiring requires servicing.

Symptom / LEDProcedure
BlueBUS is offCheck the power supply and fuses. Replace only with the same type and rating, with the power off and after addressing the cause.
BlueBUS stays onSerious fault. Disconnect both the mains supply and the battery for a few seconds, then restore power. If the condition persists, the control board requires servicing.
STOP is offSTOP does not match the learned safe state. Check the connected device and learning.
L1 + L2 flashingThe connected devices need to be learned.
L3 + L4 flashingThe positions / travel need to be learned.
The remote control lights up, but the operator does not respondCheck the battery, compatible coding and storage in the receiver.
SbS / OPEN / CLOSE stays onThe command contact may remain closed; check the button, relay and wiring.

L5 + L6 flashing during force learning. For an electrical fault with L1 flashing rapidly, check that the release mechanism is locked; L2 may indicate that the arm movement is taking too long. Fuses on the board shown: F1 = T1 A, F2 = T1.6 A; also follow the markings on the specific board.

History of the last eight manoeuvres

  1. Enter programming using STOP/SET, then use OPEN/CLOSE to select input LED L8.
  2. Hold STOP/SET for approximately 3 s. The value LEDs that light up identify manoeuvres with an anomaly; L1 is the latest and L8 the eighth.
  3. While holding STOP/SET, use OPEN/CLOSE to select the relevant manoeuvre. The LED displays the number of error flashes, as shown in the table above.
  4. Release STOP/SET and allow the menu to exit.

Control unit reset

Resetting removes the board's custom settings. The radio memory is erased separately at the receiver. This procedure does not erase the motor direction or the number of manoeuvres performed.

  1. With the barrier arm stopped, hold OPEN + CLOSE for approximately 3 s, until L1–L8 light up.
  2. Release both buttons. All LEDs flashing rapidly for approximately 3 s confirms the reset.
  3. After the factory settings are restored, L1 and L2 flash. Relearn the devices, positions and forces, then carry out safety tests.

Manual release during a power failure

Stop the automation and support the arm before releasing it. If it is not properly balanced, it may move on its own.

  1. Turn the keyhole cover, insert the key and turn it 180° as shown.
  2. Move the arm manually, ensuring its path is clear and safe.
  3. To lock it, return the key to its original position, remove it and close the keyhole cover. Check that it has been secured again before issuing another command.

NICE SBAR – manual release using the key

Maintenance and safe use

Service at least every 6 months or 20,000 manoeuvres, whichever comes first. Shorten the interval for intensive use. A service reminder is not a substitute for regular inspections.

  • Disconnect the mains supply and backup battery before carrying out any work.
  • Check the anchors, corrosion, wiring, arm, spring, bracket, stops and balance. Replace damaged parts.
  • Clean the photocells and check their response and the manual release. Repeat the safety tests after servicing.
  • Keep remote controls out of children's reach. Keep clear of the movement path and do not use equipment that needs repair.

Service reminder and service counter reset

Enter Level II programming and select input LED L7. Hold STOP/SET for approximately 3 s until the value LED is displayed, and keep holding it through the following steps. Briefly press OPEN + CLOSE together to display the consumed proportion of the limit: one flash = approximately 10%. After servicing, on the same parameter, hold STOP/SET and press OPEN + CLOSE together for at least 5 s; rapid flashes confirm the reset. Then release STOP/SET. This does not erase transmitters or replace a full reset.

Set limit exceededSignal
Below 80%Beacon flashes normally; the service indicator lights for 2 s when opening.
Approximately 81–100%Beacon lights for 2 s at the start of movement; the service indicator flashes during the manoeuvre.
Above 100%Beacon lights for 2 s at both the start and end; the service indicator stays on continuously.

The service indicator only works with the relevant output. Dispose of the equipment and batteries at the appropriate collection point at the end of their service life; do not put them in household waste.

What affects service life

Service life depends on the equipment and operating conditions. Add the relevant indices from the table; for alternative speed and force levels, use only the selected level.

Features of the complete automation systemIndexService life graph
XBA4 arm lighting15%

NICE SBAR – estimated service life graph by operating conditions

SpeedV3/V4: 5%; V5: 20%
Photocell interruption in more than 10% of manoeuvres15%
STOP interruption in more than 10% of manoeuvres25%
Braking10%
Force 5/6 or 7/810% for the selected group
Salinity10%
Dust and sand10%
Temperature above 40 °C or below 0 °C15%

Find the total on the graph's horizontal axis, then read the estimated cycles from the curve. The result assumes correct installation and maintenance; it is neither a guarantee nor a service interval.

Technical specifications of the NICE SBAR barrier

ParameterValue
Model / control unitSBAR without arm / XBA20 R10
Mains supply230 V AC, 50/60 Hz
Motor24 V DC
Current consumption1 A, catalogue value
Power consumptionMax. 300 W at start-up; 200 W at rated torque
Torque100 Nm at start-up / 25 Nm rated
Opening time≥ 4 s; with XBA4 > 5 s
Max. cycle frequency100 cycles/h; with XBA4 80 cycles/h, at rated torque
Enclosure rating / insulation classIP44 / Class I, with protective earthing
Operating temperature−20 to +50 °C
Cabinet dimensions330 × 180 × 1 180 mm (width × depth × height)
Cabinet weight46 kg
Backup powerPS124, optional

Before anchoring, measure the actual cabinet and hole positions; the installation space must also allow for the bracket and access to the cover. Assess the technical specifications together with the arm, its accessories and its balance.

How can I order this item?

Choose the option that suits you:

  1. order online: use the buy button to add the goods to your shopping cart (you will find the buy button here in the product variants table).
  2. order by email: place your order at [email protected]

Ask us anything about NICE SBAR barrier gate – without arm

Product: NICE SBAR barrier gate – without arm
Name:
Email:
Phone:
Message:
This page is protected by Google reCAPTCHA.