NICE M5BAR barrier gate – without boom
| Product availability: | In stock | We normally dispatch goods within 24 hours. |
|---|
In stock
€1,068.13 including VAT
| Weight |
|---|
| 80 kg |
Description of NICE M5BAR barrier gate – without boom
NICE M5BAR is an electromechanical barrier for controlling vehicle access, supplied without an arm. It has a 24 V DC motor and an integrated control unit BCU1 R10 (XBA3 R10). The standard setup is powered from a 230 V AC; 24 V is the motor voltage.
It is designed for an arm specified as 4 or 5 m. The steel cabinet, balancing spring and aluminium arm with an elliptical cross-section allow intensive use within the specified operating limits. Choose the arm, receiver and safety accessories to suit the specific setup.
If you already have a barrier, first check the control board marking. The following settings apply to the BCU1 R10 with a display and rotary selector; the older XBA3 has different controls and cannot be interchanged based solely on a similar name.
When to choose NICE M5BAR
| What to check | Specification and meaning |
|---|---|
| Arm | XBA14 – 4,150 mm / XBA5 – 5,150 mm |
| Clear opening width | 3.17–4.82 m |
| Adjustable operating time | 3–6 s |
| Max. cycles at rated torque | 350 cycles/h |
| Manual release | Using a key in the event of a power failure or during servicing |
| Two opposing barriers | Master–Slave synchronisation |
The arm length is not the clear opening width. When selecting, allow for the space taken up by the cabinet and bracket; check the final clear opening on site. Operating time depends on the settings, the arm and its accessories. The maximum number of cycles does not guarantee unlimited operation under every load condition.
The barrier is designed for vehicles. The arm's movement must not endanger pedestrians; provide a separate pedestrian passage and select safety devices according to the risks at the specific entrance. Before installation, also check the clearance above the arm when it is in the open position.
Arm accessories and their limitations
| Accessory | Condition |
|---|---|
| Rubber profile and lights | Permitted with the correct arm, wiring and balancing. |
| Under-arm barrier skirt WA13 | For a 4 m arm, a maximum of 1 piece, according to the spring table. Do not use WA13 with a 5 m arm unless the manufacturer has confirmed the configuration individually. |
| Mobile support WA12 | Permitted with both 4 m and 5 m arms; it changes the required spring attachment. |
| Articulated joint XBA11 | Only for use with the correct XBA15 arm and joint geometry; it is not a universal joint for any arm. |
After adding lights, a rubber profile, a support or a barrier skirt, select the spring attachment and balance again. Increasing the motor force is no substitute for correct mechanical adjustment.
Barrier kits with arm and accessories
If you want a complete setup with an arm, choose from the available kits. The stated length refers to the arm, not the clear opening width. Kits from different product ranges have different control units and limits; open the kit listing to see its exact contents.
| NICE M5BAR barrier kits | |
|---|---|
M5BAR – 4 m arm![]() | M5BAR – 5 m arm![]() |
Accessories compatible with the M5BAR barrier
Choose accessories to suit the arm and intended use. When installing multiple accessories, their combined mechanical and electrical limits must also be observed.
| What | Why | Type |
|---|---|---|
| The cabinet is supplied separately without an arm; choose the length according to the clear passage width. | ||
| Adjustable support for the end of the closed boom; do not confuse it with the folding support. | ||
| Folding support attached to the boom; include its weight in the spring table. | ||
| Length 2 m, height 60 cm; maximum 1 piece for a 4 m boom. No standard combination is confirmed for a 5 m boom. | ||
| 24 red stickers for improved boom visibility. | ||
| XBA4: up to 4 m; XBA6: up to 6 m. Connect to LIGHT according to the fitted model. | ||
| 9 sections, each 1 m long; mechanical protection for the boom edge, does not replace a safety edge. | ||
| Rechargeable battery, 24 V. Connect after setting up the barrier; the number of operating cycles depends on the charge and equipment. | ||
| Indicates movement and diagnostics; uses its own INTERNAL LIGHT connector. | ||
| Controls passage according to the programmed INTERNAL LIGHT mode. | ||
| Allows the boom to be manually folded to the side. Folding is manual; do not confuse this with the XBA11 folding joint. | ||
| For low ceilings with the correct XBA15 boom; usable range 1 950–2 400 mm, depending on accessory geometry. | ||
Photocells | Two-wire BlueBUS; repeat the Set 1. | |
Remote control | Plug-in SM receiver and transmitter with supported coding. Confirm the set contents when ordering. | |
Control board | Replacement board of the current generation; not an additional external control unit required for a standalone barrier. | |
Service and configuration | BUS T4 for diagnostics and the service counter. | |
Solar power supply | Alternative power source instead of mains; do not connect 230 V at the same time in this configuration. |
Installing the housing and boom
Disconnect the mains and backup battery before starting work. Check that the base is solid, drainage is adequate, there is room for the full boom, and the release mechanism can be accessed safely.
Base plate and anchoring
If the existing foundation surface is suitable, mark four holes to match the housing and choose anchors suitable for the substrate. For a new foundation, install conduits, the four supplied anchor bolts, and a level base plate aligned parallel to the boom.
| Substrate check | Requirement |
|---|---|
| Concrete foundation | Reinforced concrete, at least 0.15 m thick and with a volume greater than 0.2 m³. Determine the foundation dimensions according to local conditions. |
| Concrete anchors | 4 anchors with 12 MA (M12) bolts, each with a tensile resistance of at least approximately 3.9 kN. |
| Other load-bearing material | Verify the strength of the substrate and all four anchoring points for a load of at least approximately 9.8 kN. |
| Installation | Level the plate with the surface; secure the housing only after the concrete has fully cured. |
Attaching and assembling the boom
- Insert the two specified pins into the output shaft. Fit the bracket in the position for the vertical boom, and secure it with the screws and spring washers.
- Fit the cover onto the bracket using the six screws; leave them loose for now.
- Insert the supplied joining insert into the end of the correct aluminium boom and secure it with a screw.
- Insert the protective rubber strip and the corresponding connectors into the grooves, then fit the end cap and rubber strip caps.
- Slide the entire boom into the bracket as far as it will go and firmly tighten all six screws.
- Install the selected accessories, then complete spring adjustment, balancing and programming.
Left- or right-hand barrier installation
The spring hinge side must match the direction selector position on the control board. RH/DX is for the spring on the right-hand side of the balancing lever, LH/SX for the spring on the left-hand side. A technician must change the mechanical configuration with the spring safely released; simply turning the selector without changing the mechanics is not sufficient.
Spring attachment and boom balancing
Adjust the spring according to the actual length and weight of the boom with its accessories fitted. For the basic configuration, select the exact model and length column in section A. The upper hole is identified by the letter A/B/C and the lower hole by the number 1/2/3. The position cannot be determined from the kit name alone.
With multiple accessories, use the relevant M5BAR column in section B: add the indices for the installed accessories and select the spring attachment according to the total. A dash indicates a prohibited combination. Therefore, do not add WA13 to the 5.15 m XBA5 unless a solution has been individually confirmed.
| M5BAR with protective rubber strip | Spring attachment |
|---|---|
| XBA14 shortened to 3.50 m | B / 2 |
| XBA14 at 4.15 m long | B / 3 |
| XBA5 at 5.15 m long | C / 2 |
Use the table only if the bracket, spring and hole pattern match the illustration. For a different mechanical configuration, follow the instructions supplied with the specific barrier.
The examples apply to the configuration shown. For additional accessories, follow the table, not the basic example. Before repositioning or replacing the spring, a technician must safely release its preload and secure the boom.
Checking balance at 45°, 20° and 70°
- Disconnect the mains and backup battery, then release the gearbox using the key. Hold the boom securely and position it at approximately 45°.
- If the boom rises, reduce the preload by turning the spring clockwise. If it lowers, increase the preload by turning it counterclockwise.
- Repeat the check at approximately 20° and 70°. The boom must not move significantly on its own.
- Check that the spring is evenly arranged and secure it against rotation using nut B as shown. Check that it is firmly secured and lock the gearbox.
With the motor released, the force required to move the M5BAR boom manually, either when opening or closing, must not exceed approximately 35 N. This is the maximum permissible imbalance. Measure the force perpendicular to the boom, 1 m from the pivot axis; this does not set the motor's impact force.
Mechanical end stops
After releasing the drive, manually move it through its full travel. Use the end-stop screws to set the horizontal closed and vertical open positions, then tighten the lock nuts. Then perform Set 2 position programming. Electronic programming does not replace correctly set mechanical end stops.
Wiring and power supply separation
Connect the 230 V mains supply to the L/N mains terminal block and the protective conductor as shown in the original installation. Secure the cable with the cable gland and strain relief. Do not connect 230 V to the command inputs or BlueBUS. Do not interchange the motor and accessory circuits.
| Cable | Cross-section and length |
|---|---|
| 230 V mains | 3 × 1.5 mm² up to 30 m; for longer runs, 3 × 2.5 mm² with suitable grounding. |
| BlueBUS | 2 × 0.5 mm² up to 20 m; use 2 × 1 mm² up to 40 m. |
| Key switch | Two 2 × 0.25 mm² cables up to 30 m; alternatively, use one 4 × 0.5 mm² cable. |
| OPEN / CLOSE | 2 × 0.25 mm² up to 30 m for each input. |
| Flashing light / indicator | 2 × 0.5 mm² up to 30 m; the device voltage must match the output setting. |
| Master–Slave | 2 × 1 mm² up to 20 m. |
| Antenna | RG58 coaxial cable, maximum 15 m; a length under 5 m is recommended. |
BCU1 R10 control unit: diagram and terminals
Disconnect the mains and battery before wiring. The terminal blocks are removable; connect the wires according to the markings on the actual board. The following diagram is for the controller with a display and rotary selector.
| Terminal / connector | What connects here |
|---|---|
| FLASH | Flashing light, standard 12 V DC, max. 21 W. OU2 changes both the function and voltage; check the current setting before connecting. |
| LIGHT | Boom lights, standard circuit 24 V DC, max. 10 W; OU1 function. |
| OGI | Barrier indicator 24 V DC, max. 10 W; its operation is controlled by OU3. |
| 24 V DC (+ / −) | Separate power supply for compatible accessories: precise terminal polarity, tolerance −30% / +10%, maximum 500 mA total. |
| BlueBUS | Two-wire power supply and communication for compatible accessories, with no polarity. |
| STOP | NO or NC contact, or an 8.2 kΩ resistor, with no +/− polarity; the type is recognized during learning. Any subsequent change of state stops the operation. |
| SbS / OPEN / CLOSE | Voltage-free NO switching contacts with no polarity for step-by-step, opening, or closing commands. The In1–In3 assignments can be changed. |
| HP SbS | Voltage-free NO input with no polarity and high priority; default is In4 = 6. |
| LOOP1 / LOOP2 | Voltage-free NO contact from the external detector output, with no polarity. The detector's power supply is separate and must match its specifications; the loop itself must not be connected to these inputs. |
| MASTER–SLAVE | Communication between two opposing barriers; maintain connections 1–1 and 2–2. |
| SAFETY | NC safety contact for the articulated boom, depending on the equipment used. |
| INTERNAL LIGHT | Dedicated connector for XBA7 or XBA8, function OU4. |
| ANTENNA / SM | Antenna: connect the center conductor and shielding as shown in the diagram; this is not a +/− power supply. SM is a dedicated socket for a compatible receiver; do not connect an external 24 V power supply to it. |
24 V DC accessory power supply: plus and minus
To power a compatible external receiver or key-switch light, use the separate two-pole 24 V terminal block by HP SbS and LOOP1. It provides 24 V DC, tolerance −30% / +10%, maximum 500 mA total for all devices powered from this output. Check their voltage, polarity, and total current draw.
Viewed as shown in the image below, minus (−) is on the left and plus (+) on the right. This order applies to the 24 V terminal block shown; do not assume it applies to another connector.
| BCU1 R10 terminal | Accessory connection |
|---|---|
| 24 V: minus (−) | Left pole in the image → power terminal − / 0 V / GND of the device, according to the marking on its power input. |
| 24 V: plus (+) | Right pole in the image → power terminal + / +24 V of a device designed for this voltage range. |
| Command contact | If the device controls the barrier via a relay output, connect its COM and NO to the two terminals of the selected input SbS, OPEN, or CLOSE. This is a voltage-free contact with no polarity, isolated from the +/− power supply. Do not apply supply voltage to the input. |
BlueBUS has no +/− polarity: connect both BlueBUS terminals on the photocell TX and RX in parallel to the two BlueBUS terminals on the control board. EPMB photocells must not be connected to the separate 24 V auxiliary output. Use the STOP, LOOP1/LOOP2, and command inputs according to their contact type; they are not accessory power outputs.
During testing, also check how the connected devices behave in the selected Stand-by mode. The control board switches off some circuits in this mode; test the availability of the required controls and safety functions in the complete system.
BlueBUS photocells and STOP input
EPMB photocells are connected in parallel to the two BlueBUS wires. The TX and RX of one pair must have the same address; an additional pair needs a different address. For safety protection across the passage, use the FOTO, FOTO II, FOTO 1, or FOTO 1 II addresses according to the position and function. FA1/FA2 are command addresses for opening and do not replace the photocells' safety function.
After adding or removing photocells or changing STOP, perform Set 1 and retest the safety functions. Do not disable STOP by bypassing a fault; wiring multiple safety devices must take their type and monitoring into account.
Lights, warning light, and traffic light
XBA4 / XBA6 are fitted into the boom channel according to their own instructions. XBA7 and XBA8 are connected to INTERNAL LIGHT. Before changing any OU1–OU4 setting, check the output voltage and maximum power rating. Do not confuse the traffic light connector with the terminal for a standard external warning light.
FLASH, LIGHT, and OGI are separate controlled outputs. The +/− order of the 24 V terminal block shown above does not indicate their polarity. For LED or other polarized devices, follow the marking on the specific control-board output and the wiring instructions for that accessory; the order of the poles is not shown in this diagram. Connect XBA7/XBA8 using the supplied INTERNAL LIGHT connector, and PS224 using its dedicated BATTERY connector—not to the auxiliary 24 V supply.
Initial startup and learning
Before switching on, the boom must be installed with all equipment, balanced, and secured. Check the stops, direction selector, safety devices, and clear passage. After connecting the mains, the display and photocell LEDs should light up; with the default settings, the warning light should remain off when the barrier is not operating.
1. Set → 1: BlueBUS and STOP learning
- Turn the selector to find Set.
- Briefly press the selector, select the value 1 and press again to confirm.
- The control unit detects the connected devices and the type of STOP input. Run the learning procedure even if no accessories are connected.
If error E01 persists, check the wiring and compatibility; repeating the learning procedure without resolving the cause is not enough.
2. Set → 2: mechanical position learning
- Unlock the motor and manually set the boom to approximately 45° then lock the gearbox.
- Select Set → 2 and confirm.
- Allow the control unit to learn the full travel. The balancing lever must reach the set mechanical stops.
- If it does not reach the stops, stop the learning procedure by pressing the selector, adjust the mechanism, and start again. After each interruption, the procedure starts again from the beginning.
Menu 8.8.8. starts quick learning of devices and positions. Even with this option, first manually set the arm to approximately 45° and lock the gearbox. The area of movement must remain clear. Learning devices or positions does not save the remote-control buttons.
3. Movement and safety checks
Use the OPEN and CLOSE buttons to perform several complete cycles. The arm should slow down before reaching the stops; it must not catch, drop suddenly, or vibrate significantly. Test each pair of photocells, STOP, the release mechanism, a power failure, and Master–Slave operation, if applicable.
Also check the risk of the arm lifting a person: the test uses a 20 kg load at the midpoint of the arm and, when opening, the arm must not rise more than 50 cm above the closed position. Measure impact force according to the requirements for the specific installation; photocells and force reduction alone do not replace a full risk assessment.
Programming the BCU1 R10 using the rotary selector
The control unit is configured using a rotary selector and a three-digit display. Record the original value before making changes; changes to force, speed, or safety functions require the barrier to be tested again.
- Turn the selector in either direction to choose a parameter code.
- Press it briefly and release. The saved value is displayed; the display remains lit.
- Turn the selector to choose a new value. The display flashes while selecting.
- Press and release to confirm the value. The unit returns to parameter selection.
Selecting ESC ends the change without saving. The display --- indicates a configuration set via OVIEW; it is not another selectable value. In the tables, the confirmed factory setting is shown in bold; the actual control board may have values changed during installation.
Operating functions F01–F09
| Parameter and purpose | Values and operation |
|---|---|
| F01 – Automatic closing Applies after fully opening. | OFF – semi-automatic operation: close by command (factory setting) On – closes after time t01 |
| F02 – Closing after photocell activation After the selected safety device is cleared, it starts counting time t10. | OFF – disabled (factory setting) 1 – open only until the photocell is cleared: activation stops movement; once cleared, t10 starts and the barrier closes 2 – open fully: activation triggers full opening; a new opening command during t10 cancels the subsequent closing 3 – open fully 2: as for value 2, but a new opening command during t10 does not cancel the subsequent closing |
| F03 – Device for F02 | 1 – photocells and loops configured as photocells (factory setting) 2 – photocells only 3 – loops configured as photocells only |
| F04 – Close after power is restored Assess the safety of automatic movement after a power failure before enabling this function. | OFF – disabled (factory setting) 1 – if the arm is not closed, it flashes for t09 after power is restored, then closes 2 – resumes automatic closing if the pause timer was running before the power failure |
| F05 – Standby Enters standby after time t04; a new command resumes operation. | OFF – disabled (factory setting) 1 – switches off the display, BlueBUS, outputs, and some internal circuits 2 – switches off BlueBUS 4 – when powered by a battery, automatically uses full standby |
| F06 – Starting force | OFF – disabled (factory setting) On – when starting from the open or closed position, briefly applies maximum power to overcome static friction |
| F07 – Emergency opening Requires a connected, functional battery. | OFF – disabled (factory setting) On – automatically opens the arm if the mains power supply fails |
| F09 – Master / Slave | OFF – main barrier, Master (factory setting) On – subordinate barrier, Slave; see the Master–Slave procedure |
Times, speeds, force, and input functions
| Parameter and purpose | Available values |
|---|---|
| 8.8.8. – Quick learning | Starts learning of BlueBUS, STOP, and positions in a single sequence. First meet the start-up prerequisites. |
| Set – Learning | 1 – BlueBUS and STOP devices 2 – open and closed positions |
| Prn – Program | 000 – basic program (factory setting) 001 / 002 / 003 – reserved custom programs; not normally used |
| t01 – Pause before closing Active when F01 = On. | 0–250 s Factory setting: 20 s |
| t02 – Pre-flashing before opening Time between the warning light switching on and opening starting. | 0–5.0 s Factory setting: 0 s |
| t03 – Pre-flashing before closing Time between the warning light switching on and closing starting. | 0–5.0 s Factory setting: 0 s |
| t04 – Standby delay Time from the end of a cycle until enabled F05 activates. | 0–60 s Factory setting: 60 s |
| t06 – Electromagnet delay After the locking electromagnet is switched off, it waits before opening. On the BCU1 R10 board shown, this is set using parameter t06. | 0–3.0 s Factory setting: 0.2 s |
| t07 – Auxiliary light duration How long the output configured as an auxiliary light remains on. | 0–250 s Factory setting: 60 s |
| t09 – Pre-flashing after power is restored Used by function F04. | 0–20 s Factory setting: 5 s |
| t10 – Closing after photocell activation Time after the device is cleared when F02 is enabled. | 0–250 s Factory setting: 5 s |
| SPO – Opening speed | 1 – lowest 2 – level 2 3 – level 3 4 – highest (factory setting) |
| SPC – Closing speed | 1 – lowest 2 – level 2 3 – level 3 4 – highest (factory setting) |
| SLO – Slowdown when opening | 1 – lowest speed 2 – medium speed (factory setting) 3 – highest speed |
| SLC – Slowdown when closing | 1 – lowest speed 2 – medium speed (factory setting) 3 – highest speed |
| PLO – Slowdown position when opening Difference between the end position and the start of slowdown. | 1 – 0° (factory setting) 2 – approximately 10° 3 – approximately 20° |
| PLC – Slowdown position when closing Difference between the end position and the start of slowdown. | 1 – 0° (factory setting) 2 – approximately 10° 3 – approximately 20° |
| FrO – Opening force Does not replace mechanical balancing. | 1 – lowest 2 – level 2 3 – medium (factory setting) 4 – level 4 5 – level 5 6 – highest |
| FrC – Closing force Does not replace mechanical balancing. | 1 – lowest 2 – level 2 3 – medium (factory setting) 4 – level 4 5 – level 5 6 – highest |
| tF – Force limit intervention time A higher value increases the time before an obstacle is detected. | 3–32, each unit = 30 ms Range: 90–960 ms Factory setting: 3 = 90 ms |
| In1 – SbS input | Available codes: 0, 1, 3, 4, 6, 7, 8, 11, 12, 16, 19, 20, 21, 22, 25, 26, 27, 28, 29, 30. Factory setting: 1 Meaning of input codes; for In2, code 25 controls Master only. |
| In2 – OPEN input | Available codes: 0, 1, 3, 4, 6, 7, 8, 11, 12, 16, 19, 20, 21, 22, 25, 26, 27, 28, 29, 30. Factory setting: 3 Meaning of input codes; for In2, code 25 controls Master only. |
| In3 – CLOSE input | Available codes: 0, 1, 3, 4, 6, 7, 8, 11, 12, 16, 19, 20, 21, 22, 25, 26, 27, 28, 29, 30. Factory setting: 4 Meaning of input codes; for In2, code 25 controls Master only. |
| In4 – HP SbS input | Available codes: 0, 1, 3, 4, 6, 7, 8, 11, 12, 16, 19, 20, 21, 22, 25, 26, 27, 28, 29, 30. Factory setting: 6 Meaning of input codes; for In2, code 25 controls Master only. |
| SE1 – Step-by-step sequence | 1 – industrial: automatic opening, closing by holding the command 2 – open – stop – close – stop 3 – open – stop – close – open 5 – residential step-by-step mode (factory setting) 6 – hold-to-run control |
| SE3 – OPEN sequence | 1 – open – stop – open 2 – residential opening mode (factory setting) 3 – hold-to-run opening |
| SE4 – CLOSE sequence | 1 – close – stop – close 2 – residential closing mode (factory setting) 3 – hold-to-run closing |
| SE5 – Photocell function during closing | 1 – stop and reverse to open (factory setting) 4 – stop temporarily; open when the photocell is cleared 5 – stop temporarily; close when the photocell is cleared |
| SE6 – STOP during opening | 1 – stop immediately 2 – stop and briefly reverse to close (factory setting) |
| SE7 – STOP during closing | 1 – stop immediately 2 – stop and briefly reverse to open (factory setting) |
| SE8 – Obstacle during opening | 2 – stop and briefly reverse to close (factory setting) 3 – stop and reverse fully to close |
| SE9 – Obstacle during closing | 2 – stop and briefly reverse to open 3 – stop and reverse fully to open (factory setting) |
| LO1 – LOOP1 function | 1 – open – open, NO contact (factory setting) 2 – close – close, NO contact 4 – photocell, NC contact |
| LO2 – LOOP2 function | 1 – open – open, NO contact 2 – close – close, NO contact (factory setting) 4 – photocell, NC contact |
In hold-to-run mode, the arm moves only while the contact is active. Residential mode limits interruption of opening by additional commands; check its behavior in your own setup before use. F02 determines subsequent closing after the safety device is cleared; SE5 determines the arm's response when triggered during closing—the settings are not interchangeable.
Meaning of In1–In4 command codes
| Code | Command |
|---|---|
| 0 | No command. |
| 1 | Step-by-step operation according to SE1. |
| 3 | Opening according to SE3. |
| 4 | Closing according to SE4. |
| 6 | High-priority step-by-step operation, effective even when software-locked. |
| 7 | Open and lock via software. |
| 8 | Close and lock via software. |
| 11 | Switch on the timed auxiliary light; it switches off after the set time. |
| 12 | Switch the auxiliary light on/off; the set time also applies. |
| 16 | Photocell. |
| 19 | Unlock and open via software. |
| 20 | Unlock and close via software. |
| 21 | Enable opening commands from BlueBUS command photocells. |
| 22 | Disable opening commands from BlueBUS command photocells. |
| 25 | Step-by-step operation of Master and Slave; on In2, only Master is controlled. Verify the assignment by testing both arms before operation. |
| 26 | Open both Master and Slave. |
| 27 | Close both Master and Slave. |
| 28 | Step-by-step operation of Slave only. |
| 29 | Open Slave only. |
| 30 | Close Slave only. |
OU1–OU4 outputs and signalling
Changing the function may also change the output voltage. External 24 V functions are limited to 10 W per output; the 12 V FLASH warning light is limited to 21 W. Always check the device, voltage and power consumption before connecting. INTERNAL LIGHT is a connector intended for the dedicated XBA7/XBA8 module.
| Output | Code and function |
|---|---|
| OU1 – LIGHT | 0 – 24 V warning light 1 – OGI indicator 2 – gate closed 3 – gate open 4 – flashing arm light (factory setting) 5 – maintenance indicator 6 – auxiliary light 8 – red traffic light 9 – green traffic light 10 – radio channel 1 11 – radio channel 2 12 – radio channel 3 13 – radio channel 4 14 – electromagnetic lock |
| OU2 – FLASH | 0 – 24 V warning light 1 – 12 V warning light (factory setting) 2 – OGI indicator 3 – gate closed 4 – gate open 5 – flashing arm light 6 – maintenance indicator 7 – auxiliary light 9 – red traffic light 10 – green traffic light 11 – radio channel 1 12 – radio channel 2 13 – radio channel 3 14 – radio channel 4 15 – electromagnetic lock |
| OU3 – OGI | 0 – 24 V warning light 1 – OGI indicator 2 – gate closed (factory setting) 3 – gate open 4 – flashing arm light 5 – maintenance indicator 6 – auxiliary light 8 – red traffic light 9 – green traffic light 10 – radio channel 1 11 – radio channel 2 12 – radio channel 3 13 – radio channel 4 14 – electromagnetic lock |
| OU4 – INTERNAL LIGHT | 0 – warning light (factory setting) 1 – OGI indicator 2 – gate closed 3 – gate open 4 – auxiliary light 5 – red traffic light 6 – green traffic light 7 – one-way traffic light 8 – alternating one-way traffic light 9 – pedestrian traffic light |
| Signal mode | Meaning |
|---|---|
| Warning light | Flashes during operation: 0.5 s on / 0.5 s off. |
| OGI | Closed: off; opening: slow flashing; closing: fast flashing; open: on. |
| Gate closed / open | On only at the selected end position. |
| Flashing arm light | Flashes every 0.5 s even when the arm is stationary. |
| Maintenance | Below 80% of the set number: on for 2 s at the start of opening. From 80% to 100%: flashes during operation. Above 100%: flashes continuously. |
| Auxiliary light | On during movement and afterwards until t07 expires. |
| Red traffic light | Flashes slowly while closing, stays on when closed, and is off otherwise. |
| Green traffic light | Flashes slowly while opening, stays on when open, and is off otherwise. |
| Radio channels | A command from the relevant channel switches the output on; any command it sends to the control unit is ignored. |
| Electromagnetic lock | Active when closed; switches off before opening, applying the lock delay time (check whether your board is labelled t06/t05). |
| OU4 = 7 | Green when the arm is open, red in all other states. |
| OU4 = 8 | For the inside, use In2 or LOOP1 set to open; for the outside, use In3 or LOOP2 set to open. Green is assigned to the side that issued the command; the opposite side shows red. When closed or closing, both sides show red. |
| OU4 = 9 | When closed, green on the inside and red on the outside; when open, the reverse. At intermediate positions, both sides show red. |
Counters, versions and service data
| Menu | Use |
|---|---|
| MnP – Set number of operations | Press repeatedly: a = units, b = thousands, c = millions. Used to signal when maintenance is due. |
| MnE – Number of manoeuvres performed | Press repeatedly: t = units, u = thousands, v = millions. |
| ErS – Erase | 1 – devices; 2 – positions; 3 – function values; 5 – all. Procedure and subsequent learning. |
| Fir – Firmware version | Press twice to display two three-digit identification sections. |
| Hdr – Hardware version | Press three times to display three three-digit identification sections. |
| din – Input diagnostics | Input and display statuses. |
Resetting the control board does not reset the service counter. Reset it using OVIEW only after maintenance has been carried out and recorded.
Two opposing barriers: Master–Slave
Two complete barriers can be synchronised. Each has its own motor, control unit and power supply; they must not be connected as two motors to one control board. Connect the communication terminals 1–1 and 2–2 using 2 × 1 mm² cable, up to 20 m long.
- Complete installation, direction, balancing and electrical connections on both barriers.
- On the Slave barrier, perform Set 1 and Set 2, adjust its speed, deceleration and force, then set F09 = On.
- Perform Set 1 and Set 2 on the Master barrier. Until then, the Slave may report communication error E05.
- Issue a command from the Master unit and check the movement of both arms and the safety devices.
Shared BlueBUS devices and the receiver must be connected to the Master. The Slave's own SbS/OPEN/CLOSE commands can operate only its own arm. Speed, deceleration, deceleration position and force are set separately for each barrier. For backup power, each barrier needs its own PS224.
Remote controls and backup power
Receiver and remote controls
The board has an SM socket for a compatible receiver. Current selection OXIBD allows you to use compatible remote controls, such as the ON2E. Connect the receiver with both the mains and battery disconnected. Store and delete remote controls according to the specific receiver instructions; resetting the control board does not replace the receiver's radio programming procedure.
PS224 during a power outage
PS224 is connected only after installation and programming are complete: disconnect the mains, install the battery and connect the designated cable to the backup power connector; then restore the mains supply. Mode F05 = 4 can reduce power consumption when running on battery. Function F07 = On commands the barrier to open during a mains failure if a battery is installed; it is not enabled by default.
Solemyo SYKCE30 is an alternative power supply method. When using the Solemyo system, the barrier must not be connected to the 230 V mains at the same time. Assess the power source capacity based on the number of manoeuvres and the accessories installed.
Troubleshooting
First, identify the code on the display or count the short flashes. The diagnostic sequence repeats after a pause of about 1 s; normal flashing during movement is not an error code.
| Code / signal | What to check |
|---|---|
| E01 / 1 flash | BlueBUS/STOP devices changed or not learned. Check the wiring, then run Set 1. |
| E02 | Positions not learned; after checking the stops and balance, run Set 2. |
| E03 | Limit switches reversed; check the direction and their electrical connections. |
| E04 | Encoder signal missing; check the sensor connector and cable. |
| E05 | Communication error Master–Slave; check the polarity and learning on both barriers. |
| E06 / 5 flashes | Parameter memory error. Disconnect and restore power to all sources, then try again; if the problem persists, servicing is required, possibly including a full reset and relearning. |
| E07 / 7 flashes | Internal electronics fault. Disconnect all power sources; if the fault recurs, arrange servicing. |
| E08 | Barrier type configuration; check the factory settings on the control board. |
| E09 / 9 flashes | Software lockout. Enter the designated unlock command, or HP SbS if applicable; this is not mechanical key release. |
| E10 | Missing NC safety contact or limit switch; check SAFETY and the switches. |
| E11 | BlueBUS short circuit. Check the wiring and devices; once the cause has been resolved, repeat the command. |
| I02 / 2 flashes | Photocell active. Remove the obstruction, clean the optics and check the alignment. |
| I03 / 3 flashes | Force limit triggered. First check the balance, friction and stops. Do not increase the force to compensate for a mechanical fault. |
| I04 / 4 flashes | STOP triggered. Find the cause in the connected device; do not bypass the safety input. |
LED and din mode
STOP is lit when the input is normally enabled; if it goes out, this indicates activation. The SbS, OPEN, CLOSE and HP SbS LEDs are lit when the corresponding command is active. The FC1/FC2 status depends on the RH/LH switch: with RH, FC1 goes out in the closed position and FC2 in the open position; with LH, the opposite applies.
Menu din displays the inputs using the display segments. First digit: A1 = Loop1, B1 = Close, C1 = HP SbS, D1 = Loop2, E1 = Open, F1 = SbS; dp1 flashes once per second while the control board is running. The second digit indicates the limit switches, buttons, selected direction and battery power; the third indicates the photocells and connected Slave. Correct the direction in the mechanics and switch, not by swapping random wires.
Clearing settings and starting over
On the selector, choose ErS, press, select the required value and confirm. 1 clears the learned devices, 2 positions, 3 function values, 5 all control unit data. After a complete reset, repeat Set 1, Set 2, setup and safety tests.
Control board reset does not reset the number of operations performed. After carrying out maintenance, reset the service counter using OVIEW. Erase transmitters as specified in the procedure for the specific receiver.
Manual arm release
In the event of a power failure, malfunction or during installation, stop operation, disconnect the power supply and secure the area. Hold the arm; an incorrectly balanced arm may move on its own.
- Insert the release key and turn it 180° to the left or right.
- Move the arm manually to the required position.
- To restore motorized operation, return the key to its original position and remove it. Check that the arm is secured and that control has been safely restored.
Maintenance and service life
For an existing installation with a BCU1 R10, schedule a professional inspection no later than after 6 months or 20,000 operations, whichever comes first. With intensive use, the cycle limit may be reached much sooner. Also check the balance after changing the arm accessories.
Disconnect all power sources and check for corrosion, anchoring, screws and spring attachment, shaft play, the condition of the arm, and release operation. After restoring the power supply, repeat the safety device and force tests. Record servicing and any spring replacement in the maintenance log.
Factors affecting the estimated service life
| Characteristics of the complete automation system | Index | Service life graph |
|---|---|---|
| XBA11 folding joint | 15% | |
| Speed, level 2 | 0% | |
| Speed, level 3 | 10% | |
| Speed, level 4 | No index is specified for calculating from this graph. | |
| Photocell activations in more than 10% of operations | 10% | |
| STOP activations in more than 10% of operations | 10% | |
| WA12 mobile support | 10% | |
| Salt in the environment | 10% | |
| Dust / sand | 5% | |
| Under-barrier rail | 5% | |
| Temperature above 40 °C or below 0 °C | 5% | |
| Set FrO / FrC force | Level 4: 5% Level 6: 10% At level 5, do not use this graph to calculate the number of cycles. |
The table and graph must correspond to the specific barrier configuration. Add the indices for the applicable factors, find the total on the horizontal axis, and read the estimated number of cycles from the vertical axis. If there is no clear index for the selected setting or the total is outside the graph's range, do not estimate the number of cycles from it. The estimate assumes correct installation and regular maintenance; it does not guarantee a number of cycles or advise postponing servicing.
Technical specifications of the NICE M5BAR barrier
| Parameter | Value |
|---|---|
| Model | NICE M5BAR – without arm |
| Type | Electromechanical barrier with 24 V DC motor and built-in control unit |
| Control unit | BCU1 R10 (XBA3 R10) |
| Mains supply | 230 V AC, 50/60 Hz |
| Motor voltage | 24 V DC |
| Current draw | 1.1 A |
| Maximum power consumption at startup | 110 W |
| Power consumption at rated torque | 50 W |
| Operating time | 3–6 s |
| Starting torque | 200 Nm |
| Rated torque | 70 Nm |
| Max. frequency at rated torque | 350 cycles/h |
| Clear passage width | 3.17–4.82 m |
| Ingress protection rating | IP54 |
| Operating temperature | −20 to +55 °C |
| Cabinet dimensions | 400 × 299 × 1,215 mm (width × depth × height) |
| Weight | 80 kg |
| Insulation class | I |
| Backup power supply | PS224 |
The parameters apply at a reference temperature of approximately 20 °C. Assess the requirements of each specific installation in conjunction with the arm length, accessories, balancing, and safety tests.
The dimensioned drawing also includes external protruding parts and provides detailed installation dimensions. Do not use only the rounded cabinet dimensions in the table when planning the location.
How can I order this item?
Choose the option that suits you:
- order online: use the buy button to add the goods to your shopping cart (you will find the buy button here in the product variants table).
- order by email: place your order at [email protected]