Technical manual for NICE WIDE S, WIDE M and WIDE L barriers

NICE WIDE model comparison

Parameter NICE WIDES NICE WIDEM NICE WIDEL
Minimum opening time 4 s 3.5 s 5 s
Radio receiver built-in + SM / OXI built-in + SM / OXI built-in + SM / OXI

Common control unit data

Parameter Value
Backup power supply NICE PS324
Photovoltaic power supply No
Flashing light output max. 25 W
CL / OGI outputs 24 V DC, max. 10 W per output
Inputs STOP, PHOTO, PHOTO 2, SbS, OPEN, CLOSE
Antenna 50 Ω, RG58 cable
Settings potentiometers and microswitches on the control unit

All WIDE S, WIDE M and WIDE L models have a simple built-in radio receiver as well as an SM connector for OXI family receivers. A current example of a plug-in receiver is NICE OXIBD; a long-range alternative is NICE OXILR with compatible NICE ON3ELR remote controls.

For more information about the full range, see the NICE WIDE barriers category or the NICE barriers.

Compatible accessories for NICE WIDE barriers

The barrier is sold without a boom. First choose the boom and mounting plate for your model, then select safety and operating accessories to suit the specific entrance.

Basic setup by model

WIDE S and WIDE M: boom NICE XBA19 and mounting plate NICE SIA1.

WIDE L: boom NICE XBA15 (3 m), NICE XBA14 (4 m) or NICE XBA5 (5 m) and mounting plate NICE SIA2.

WIDE L with a 6 m boom: two NICE XBA15 booms joined with NICE XBA9.

Drive-through safety

  • NICE EPM – relay photocells for the PHOTO input.
  • NICE XBA13 – impact-protection rubber strip for the underside of the boom.
  • NICE WA10 – reflective elements for improved boom visibility.

Warning lights

Supports, under-boom skirts and special mounting

  • NICE WA11 – adjustable fixed support for all models.
  • NICE WA12 – mobile support for WIDE M/L.
  • NICE WA13 – aluminium under-boom skirt.
  • NICE WIA10 – side-folding boom joint for WIDE S/M.
  • NICE WIA11 – articulated joint for WIDE M in low-clearance installations.

Controls and backup power

  • NICE OXIBD – current OXI family plug-in receiver.
  • NICE OXILR – long-range receiver for compatible NICE ON3ELR remote controls.
  • NICE PS324 – backup power supply with built-in charging for WIDE S/M/L.

Important: Lights, rubber strips, under-boom skirts, supports and other components change the boom's weight. After every change to the setup, check the boom balance and spring suitability again.

Documents and more selection options

Recommended wiring for NICE WIDE

For the barrier's electrical installation, it is important to prepare the cables before installing the barrier housing. For longer cable runs or when several devices share a conduit, verify the sizing for the specific installation.

NICE WIDE barrier and cable layout

Approximate layout of devices and cables. Exact cross-sections and maximum lengths are listed in the table below the diagram.

Connection Cable, length and notes
230 V power supply 3 x 1.5 mm², max. 30 m.
For lengths over 30 m, use 3 x 2.5 mm² and install a separate protective earth at the barrier.
Flashing light 2 x 0.5 mm², max. 30 m.
LIGHT output.
Key switch 2 x 2 x 0.25 mm², max. 30 m.
Two separate wires for the control contacts; can be replaced with a 4 x 0.5 mm² cable.
Photocell TX 2 x 0.25 mm², max. 30 m.
For lengths over 30 m and up to 40 m, use 2 x 1 mm².
Photocell RX 4 x 0,25 mm², max. 30 m.
For lengths over 30 m and up to 40 m, use 2 x 1 mm².
OPEN input 2 x 0,25 mm², max. 30 m.
Normally open contact.
CLOSE input 2 x 0,25 mm², max. 30 m.
Normally open contact.
Antenna RG58, shielded coaxial cable, max. 15 m.
Keep the cable as short as possible; ideally, no longer than 5 m.
Open barrier indicator light 2 x 0,5 mm², max. 30 m.
OGI output or traffic light, depending on the settings of microswitches 9 and 10.

Installing the NICE WIDE cabinet and foundation plate

Before installing the barrier, prepare the cable conduits and check that the substrate allows for secure, level and stable anchoring. The foundation plate for the WIDE S and WIDE M is NICE SIA1, and the foundation plate for the WIDE L is NICE SIA2.

Safety: A qualified installer must assess the foundation and anchoring method based on the substrate, local conditions and barrier loads. The site must not be prone to flooding and must allow safe access to the cabinet.

Anchoring to a prepared load-bearing foundation

  1. Remove the top cover and rear panel of the barrier cabinet.
  2. Place the cabinet on the prepared foundation and mark the four anchoring points through the mounting holes.
  3. Move the cabinet aside and drill holes at the marked points.
  4. Install four suitable expansion anchors.
  5. Put the cabinet back in place and secure it with suitable nuts and washers.

Anchors, nuts and washers for direct anchoring are not included.

Marking the points for direct anchoring of the NICE WIDE barrier cabinet

Use the cabinet as a template to accurately mark the four anchoring points.

New concrete foundation with foundation plate

Requirement Value according to the manual
Minimum concrete thickness 150 mm
Reinforcement steel reinforcement
Concrete volume more than 0.2 m³
Example foundation dimensions 250 mm thick, area 0.8 m²; approximately 0.9 × 0.9 m
Additional anchoring of the plate to the concrete 4 anchors with M12 bolts; tensile strength of at least 400 kg according to the documentation
  1. Prepare the foundation pit and conduits for routing the electrical cables.
  2. Attach four anchor hooks to the foundation plate. Fit a nut and washer to each hook, on both the top and underside of the plate.
  3. Check the position of the cable conduits in the central opening of the plate.

NICE WIDE foundation plate, anchor hooks and cable conduits

Keep the foundation plate level; route the cable conduits through its central opening.

Important: Tighten the lower nut on each anchor hook all the way to the end of the thread.

  1. Pour the concrete and place the foundation plate before it starts to set.
  2. Set the plate flush with the surface, parallel to the future barrier arm and perfectly level.
  3. Wait for the concrete to cure completely. The manual states that this usually takes about two weeks.
  4. Remove the four top nuts and washers from the anchor hooks.
  5. Open the cabinet, fit it over the anchor hooks and secure it with the nuts and washers you removed.

Fitting the NICE WIDE barrier cabinet onto the anchoring points

Once the foundation has cured, fit the cabinet onto the four anchoring points and secure it with nuts and washers.

Substrates other than reinforced concrete: Check the substrate's consistency and load-bearing capacity. According to the manual, the four anchoring points must safely withstand a load of approximately 1,000 kg. The installer must select the specific anchor type based on the substrate.

Wiring the NICE WIDE control unit

The WIDE control unit has separate terminals for the power supply to accessories, safety inputs, control inputs, warning light, lighting and antenna. Unused NC inputs must be bridged to a common terminal, depending on the wiring configuration.

NICE WIDE control unit terminal wiring diagram

Standard connection for the warning light, control inputs and photocells.

Terminals Name / type Function
3 - 4 LIGHT
Output
Warning light. During movement, it flashes at intervals of approximately 0.5 s on and 0.5 s off.
5 SERVICES
24 V DC
24 V DC accessory power supply, maximum 200 mA.
6 - 8 CL
Output
Lighting or traffic light output, depending on the settings. With the standard settings, it turns on at the start of a maneuver and turns off approximately 60 s after it ends.
6 - 9 OGI
Output
Open barrier indicator light or traffic light output, depending on the settings. With the standard settings, it is off when the barrier is closed, on when open, and flashes while the barrier is moving.
6 - 10 STOP
NC input
Blocks or immediately stops the maneuver when activated by a safety device.
6 - 11 PHOTO
NC input
Photocells for closing. Activation during closing causes the barrier to stop or reverse, depending on the settings.
6 - 12 PHOTO 2
NC input
Opening photocells. Activation during opening causes the gate to stop or reverse, depending on the setting.
6 - 13 SbS
NO input
Step-by-step command. The standard sequence is Open - Stop - Close - Stop.
6 - 14 OPEN
NO input
Open command. Sequence: Open - Stop - Open - Stop.
6 - 15 CLOSE
NO input
Close command. Sequence: Close - Stop - Close - Stop.
7 24 V / Photo test / Stand-by
24 V DC
Auxiliary 24 V DC power supply, max. 200 mA. Depending on the selected mode, this is used for photocell testing or the stand-by function.
AERIAL Antenna
Input
Receiver antenna connection, 50 Ω impedance, RG58 cable.

Setting the boom and limit positions

Before programming, the boom must be correctly installed mechanically and balanced, and the control unit must know the direction of travel and the limit positions. The barrier uses limit switches marked FCA and FCC.

Balancing the boom

Adjusting the balancing spring on the WIDE S barrier

WIDE S balancing mechanism.

Adjusting the balancing spring on the WIDE M and WIDE L barrier

WIDE M and WIDE L balancing mechanism.

  1. Unlock the drive and set the boom to approximately 45°.
  2. Check that the boom stays in place. If it rises, reduce the spring force; if it falls, increase the spring force according to the mechanism of the specific model.
  3. Repeat the check at approximately 20° and 70°. The boom must not rise or fall sharply on its own.

Checking the limit switches

NICE WIDE limit switch and motor connectors

If the FCA/FCC LED indication or the direction of boom movement is incorrect, disconnect the power and rotate the relevant connector 180°.

  1. Unlock the drive and move the boom manually to the closed position.
  2. In the closed position, FCC must be off and FCA must be on.
  3. Move the boom manually to the open position.
  4. In the open position, FCA must be off and FCC must be on.
  5. Set the boom to approximately 45° and lock the drive again.

The deceleration limit switch should activate approximately 20° before the mechanical stop. If the precise deceleration point needs adjusting, adjust the limit switch cams.

Checking the direction of travel

  1. Set all programming microswitches to OFF.
  2. Set the boom to approximately 45°.
  3. Send a brief pulse to the OPEN input.
  4. The boom must start opening. If it moves in the opposite direction, rotate the motor connector 180° and repeat the check.

Programming the NICE WIDE barrier

The NICE WIDE is not programmed in the same way as Robus drives using programming levels L1 to L8. Basic settings are made using a combination of potentiometers A to E,, microswitches 1 to 14, and the PROG and RADIO buttons on the control unit.

Potentiometers, microswitches and buttons on the NICE WIDE control unit

Controls on the control board.

Potentiometers A to E

Item Setting
A – Pause Pause time between the end of opening and the start of automatic closing. Used only in automatic mode.
B – Speed Maximum boom speed from the start of movement to the deceleration point.
C – Force Obstacle detection sensitivity from the start of movement to the deceleration point. If an obstacle is detected, movement is reversed.
D – Low Speed Boom speed in the deceleration phase, from the limit switch to the end position.
E – Low Force Obstacle detection sensitivity during the deceleration phase.

Potentiometer values are adjusted with microswitches 13 and 14 set to OFF. After fine-tuning, save the settings by switching microswitches 13 and 14 back to ON.

Learning the ALT input and mechanical stops

  1. Set the boom approximately halfway along its travel.
  2. Set microswitches 13 and 14 to OFF.
  3. Press and hold the PROG button for approximately 3 seconds.
  4. The control unit learns the status of the ALT/STOP input and starts the sequence: fully closed - fully open - fully closed.
  5. If the limit switch cam positions were changed after programming, the mechanical stops must be learned again.
  6. After testing the movement, adjust the speed, force and deceleration using the potentiometers.
  7. When setup is complete, set microswitches 13 and 14 to ON.

After successful learning, the OK LED flashes green approximately once per second. If a microswitch or potentiometer setting is changed during normal operation, the control unit continues to use the previously saved values and the OK LED flashes orange as a warning.

Programming microswitches 1 to 14

Microswitch / position Function
1 - 2
OFF - OFF
Manual mode. Movement occurs only while a command is active.
1 - 2
ON - OFF
Semiautomatic mode. One command carries out a complete opening or closing cycle.
1 - 2
OFF - ON
Automatic mode. A command opens the barrier; after the set pause, the barrier closes automatically.
1 - 2
ON - ON
Automatic mode with the always-close function. After a power failure, the barrier starts closing if it was left open.
3
ON
Apartment block mode. While opening, additional SbS or OPEN commands are ignored until the barrier is fully open. While closing, another command stops the movement and opens the barrier.
3
OFF
Apartment block function is disabled.
4
ON
The step-by-step command operates in the Open - Close - Open - Close cycle.
4
OFF
The step-by-step command operates in the Open - Stop - Close - Stop cycle.
5
ON
Pre-flashing. The warning light starts flashing before the manoeuvre begins, for approximately 5 s in automatic mode and 2 s in manual mode.
5
OFF
Pre-flashing is disabled.
6
ON
The warning light stays on or flashes during the manoeuvre and during the pause before automatic closing.
6
OFF
The warning light operates only while the barrier is moving.
7
ON
Closing immediately after passing through the photocells. After the photocells are cleared, the barrier closes after approximately 5 s.
7
OFF
The function is disabled.
8
ON
The PHOTO input is also active while opening. In semi-automatic or automatic mode, opening resumes once the photocells are cleared.
8
OFF
The PHOTO input is active only while closing.
9 - 10
OFF - OFF
The OGI output is an open-barrier indicator, and the CL output is lighting.
9 - 10
ON - OFF
One-way traffic light and lighting. OGI operates as a green light, while CL remains lighting.
9 - 10
OFF - ON
Two-way traffic light for entry and exit. OGI and CL control the red or green light according to the direction of travel and the barrier status.
9 - 10
ON - ON
Traffic light configurable via Oview. The default logic uses a green light when the barrier is open and a red light when it is closed.
11
ON
Rapid clearance of the passage. Accelerated opening or closing times are set via Oview.
11
OFF
Rapid passage clearance is disabled.
12
ON
Function configurable via Oview; photocell test by default. Terminal 7 is used as a 24 V output for testing the photocells.
12
OFF
Terminal 7 is a fixed 24 V output for accessories.
13 - 14
OFF - OFF
Test and setup mode. The control unit operates using the current potentiometer settings and allows adjustments during testing.
13 - 14
ON - ON
Programming lock. Saves and locks the potentiometer and microswitch settings.
13 - 14
ON - OFF or OFF - ON
Invalid combination.

Radio receiver outputs

All WIDE S, WIDE M and WIDE L models have a built-in radio receiver and an SM connector for OXI family receivers; a current example of a plug-in receiver is NICE OXIBD. An alternative for long-range operation is NICE OXILR with LoRa technology, which requires compatible NICE ON3ELR transmitters. With the standard assignment, the receiver outputs have the following functions:

Receiver output Function
1 SbS - step-by-step command
2 STOP
3 OPEN - opening
4 CLOSE - closing
5 CL - lighting or traffic-light output
6 Radio channel 1
7 Radio channel 2

NICE WIDE special functions

Function Description
Always-close function If mode 1 - 2 is set to ON - ON and the barrier is open when power is restored, the control unit automatically starts closing with pre-flashing.
Closing after passing through the photocells With microswitch 7 set to ON, the pause is shortened in automatic mode and the barrier closes approximately 5 seconds after the photocells are cleared.
Traffic light Microswitches 9 and 10 change the function of the OGI and CL outputs. The outputs can operate as an indicator light, lighting, a one-way traffic light or a two-way traffic light for entry and exit.
Forced movement in hold-to-run mode If a safety device blocks movement, the control unit allows forced movement by holding down the command. This mode is intended for servicing or emergencies.
Maintenance indication The control unit can indicate when maintenance is required based on the number of manoeuvres performed. The threshold is set via Oview.

Troubleshooting and diagnostics

Diagnostic LEDs on the NICE WIDE control unit

Positions of the OK and R LEDs and the input indicator lights on the control board.

Basic faults

Problem Cause and check
The transmitter does not operate the barrier and its LED does not light up. Cause: The remote control battery is dead.
Check: Check and replace the battery in the remote control.
The LED on the remote control lights up, but the barrier does not respond. Cause: The remote control is not stored in the receiver.
Check: Check that the remote control is stored as described in the section separate article on pairing remote controls.
The barrier does not respond to any command. Cause: There is no power supply, or a fuse is damaged.
Check: Check the mains power supply and fuses F1 and F2.
The maneuver does not start and the warning light does not flash. Cause: The control unit is not receiving a command.
Check: Check the SbS input LED or the receiver indicator. For a radio command, the OK LED should flash twice quickly.
The barrier moves and then reverses direction. Cause: The force is set too low or the arm is poorly balanced.
Check: Check the arm balance and the Force and Low Force potentiometer settings.
The barrier moves slowly or does not start from its end position. Cause: The control unit has not correctly learned the end positions.
Check: Check the limit switches and repeat the stop-position learning procedure.
The barrier moves in the opposite direction. Cause: The motor is wired in reverse.
Check: Check the direction of movement and the motor connector.

Diagnostics using the OK LED flashes

OK LED flashes Meaning and checks
Off Control unit fault or no power supply.
Check: Check the power supply and fuses.
Steady on Serious control unit anomaly.
Check: Try disconnecting and reconnecting the power supply; if the condition persists, check the control unit.
Flashes once per second Normal status.
Check: The control unit is working correctly.
2 quick flashes followed by a pause Photocell triggered.
Check: Check the PHOTO and PHOTO 2 inputs and the passage area.
3 quick flashes followed by a pause Obstacle detection triggered between the limit switches.
Check: Check the arm balance and force setting.
4 quick flashes followed by a pause ALT/STOP input triggered.
Check: Check the STOP circuit and connected safety devices.
5 quick flashes followed by a pause Motor control hardware problem.
Check: Wait about 30 s, try another command and, if necessary, disconnect and reconnect the power supply.
6 quick flashes followed by a pause Temperature limit exceeded.
Check: Wait for the control unit to cool down.

Input status LEDs

LED Status meaning
STOP Off: The STOP input is active or the circuit is open.
On: Normal status of the STOP input.
PH Off: PHOTO photocell triggered.
On: Normal status of the PHOTO input.
PH2 Off: PHOTO 2 photocell triggered.
On: Normal status of the PHOTO 2 input.
SbS Off: The step-by-step command input is inactive.
On: The SbS input is active.
OP Off: The OPEN input is inactive.
On: The OPEN input is active.
CL Off: The CLOSE input is inactive.
On: The CLOSE input is active.
FCA Off: The opening limit switch is activated; the arm is open.
On: The arm is not at the opening limit switch.
FCC Off: The closing limit switch is activated; the arm is closed.
On: The arm is not at the closing limit switch.

NICE WIDE barrier service life

The NICE WIDE barrier manual gives an approximate service life of up to 500,000 operating cycles. Actual service life depends on operating conditions, arm length, accessories fitted to the arm, and how often safety devices intervene during a cycle.

Factor S M L
Dusty or sandy environment 10% 10% 10%
Salty environment 10% 10% 10%
Aluminium barrier skirt on the boom 5% 5% 5%
Mobile boom support - 15% 15%
Ambient temperature above 40 °C or below 0 °C 5% 5% 5%
Movement interrupted by a photocell 10% 15% 15%
Movement interrupted by the STOP input 10% 15% 15%
Speed trimmer set above 50% 10% 10% 15%
Force trimmer set above 50% 5% 10% 10%

The percentages are cumulative. The higher the resulting load index, the lower the expected number of operating cycles. At a load index of approximately 30%, the service life is estimated at around 200,000 cycles.

Backup battery, photocells and lights

For backup power for WIDE S, WIDE M and WIDE L barriers, use NICE PS324 with built-in charging. It enables emergency operation during a power failure; the number of movements depends on the battery condition and the load on the system.

Safety photocells are connected to the PHOTO and PHOTO 2 inputs. With the standard setting, the PHOTO input is activated during closing; when microswitch 8 is enabled, it can also be activated during opening. If microswitch 12 is set to ON, terminal 7 is used to test the photocells.

The warning beacon is connected to the LIGHT output. The CL and OGI outputs can be used for lighting, as an open-barrier indicator or for traffic light control, depending on the settings of microswitches 9 and 10. The maximum output power for an indicator or traffic light is 10 W.

Compatible boom lights: for WIDE S and WIDE M NICE XBA4; for WIDE L NICE XBA6 or NICE XBA18 depending on the length of the assembly. After installation, recheck the boom balance.

Routing and connecting the lighting cable in the NICE WIDE boom

Route the cable through the bracket and boom. Observe the polarity when connecting to terminals 3 and 4.

Manual release of the NICE WIDE barrier

In the event of a power failure or during servicing, the barrier can be released with the key and the boom moved manually.

Manual release of the NICE WIDE barrier using the key

Release WIDE S by turning the key 180°; release WIDE M and WIDE L by turning it 90°.

  1. Slide the lock cover aside.
  2. Insert the release key.
  3. For WIDE S, turn the key 180°; for WIDE M and WIDE L, turn it 90°.
  4. Move the boom manually to the desired position.
  5. To re-engage the barrier, turn the key back, remove it and close the lock cover.

Ordering and technical advice

Ask us about wiring or choosing a system

If you can’t find the information you’re looking for, email us at [email protected]. We can advise you on choosing a barrier, boom, spring, safety devices and accessories.

Information we need to select a system

  • the clear passage width and required boom length,
  • the expected number of cycles per hour,
  • a list of boom accessories: lights, protective rubber strip, barrier skirt or mobile support,
  • the required control method and safety devices.

Technical note: Electrical wiring, force adjustment and safety device checks must be carried out by a qualified person in accordance with the specific installation and applicable regulations.