Programming the functions of NICE Robus and NICE Run drives

Programmable functions of NICE Robus and Run operators

NICE Robus and Run operators have 8 functions that can be switched on/off and 8 functions that can be set to 8 possible values. Programming is done using three buttons—OPEN, STOP/SET, and CLOSE—and eight LEDs, L1 to L8. The default values are set at the factory, so if you don’t need to change anything, there’s no need to program anything. These functions are:

8 functions that can be switched on/off (level-one programming)

All these functions are disabled by default. On the control unit, you can tell whether a function is enabled by checking whether the corresponding LED, L1 to L8, is lit. Example: only automatic closing is enabled, so LED L1 on the control unit is steadily lit.

  • L1 - Automatic closing - enable this function if you want the gate to close automatically after the set time delay (30 seconds by default).
  • L2 - Close after photocell - enable this function if you want the gate to close 5 seconds after passing through the photocells. There are two possible behaviours when this is combined with automatic closing:
    • Only Close after photocell is enabled, while Automatic closing is disabled: the gate always opens fully, even if you passed through it “a long time ago”, and then closes after 5 seconds.
    • Both Close after photocell and Automatic closing are enabled: as soon as you enter the photocell beam, the gate stops (so it does not open fully). Once you leave the beam (after the car has passed), a 5-second countdown starts and the gate closes.
  • L3 - Always close - enable this function so that the gate receives a close command after a power failure. Otherwise, it would remain open when power is restored.
  • L4 - Standby mode - enable this function when operating on a backup battery or solar panel. After one minute, the control unit enters “sleep” mode and wakes only when it receives a command to start a manoeuvre. Although this function reduces power consumption, the control unit may not behave exactly as expected with complex setups (GSM controls, card readers, induction loops, timers, etc.). We therefore recommend leaving this function disabled unless you really need it.
  • L5 - Boost - when this function is enabled, the operator starts at full power, which can help eliminate false obstacle detections caused by snow, ice, or frost.
  • L6 - Pre-flashing - enable this function if you want the gate’s warning light to flash for 3 seconds before each manoeuvre, before movement begins. Greater safety at the cost of a delay.
  • L7 - CLOSE wired input acts as partial opening - a voltage-free contact closure on the CLOSE wired input sends a close command to the gate. Enabling this function reassigns the input, allowing you to send a partial-open command to the operator via a wired connection.
  • L8 - Slave control unit - enable this function only when two opposing sliding-gate operators are connected as a paired system.

8 functions that can be set to 8 possible values (level-two programming)

  • L1 - Pause time: how long before the gate closes automatically (automatic closing must be enabled for this to work):
    • L1 - After 5 seconds
    • L2 - After 15 seconds
    • L3 - After 30 seconds - factory default
    • L4 - After 45 seconds
    • L5 - After 60 seconds
    • L6 - After 80 seconds
    • L7 - After 120 seconds
    • L8 - After 180 seconds
  • L2 - Step-by-step mode: how the operator/gate behaves when the remote control is pressed repeatedly (or when commands are repeatedly sent to the SbS wired input)
    • L1 - Open > Stop > Close > Stop
    • L2 - Open > Stop > Close > Open - factory default
    • L3 - Open > Close > Open > Close
    • L4 - Condominium mode - the gate always completes the opening manoeuvre, i.e. it ignores further commands while opening
    • L5 - Condominium mode with stop - as in L4 Condominium mode, but the gate can be stopped while opening by holding the button for at least two seconds
    • L6 - Step-by-step mode 2 - sequence as in L2, but a full-open command is sent by holding the button for at least 2 seconds; a shorter press triggers partial opening only
    • L7 - Hold-to-run - the operator moves only while the button is held down
    • L8 - During opening, the sequence is as in L2; during closing, the button must be held down, as in L7 Hold-to-run
  • L3 - Operator speed: how fast the operator opens and closes the gate
    • L1 - Very slow (30%)
    • L2 - Slow (45%)
    • L3 - Medium (55%)
    • L4 - Fast (70%) - factory default
    • L5 - Very fast (85%) - factory default for NICE Robus RB500HS
    • L6 - Extremely fast (100%)
    • L7 - Opens as “L4 Fast”, closes as “L2 Slow”
    • L8 - Opens as “L6 Extremely fast”, closes as “L4 Fast”
  • L4 - OGI output behaviour: when and how the OGI (Open Gate Indicator) wired output operates. The output is 24 V DC, max. 4W.
    • L1 - The output is open when the gate is closed and closed when the gate is open. During opening, it switches slowly in a repeated pattern; during closing, it switches rapidly in a repeated pattern - factory default
    • L2 - Closed only when the gate is fully closed; otherwise off.
    • L3 - Closed only when the gate is fully open; otherwise off.
    • L4 - Activated only by radio output no. 2; that is, if your remote control is paired in Mode I, the output closes when you press the second button on the remote.
    • L5 - Activated only by radio output no. 3; see previous item
    • L6 - Activated only by radio output no. 4; see previous item
    • L7 - Activated when the number of manoeuvres exceeds the maintenance-warning threshold; see “L7 Service reminder”.
    • L8 - The output operates an electric lock; before opening starts, the control unit first activates this output
  • L5 - Motor force: how forcefully the operator pushes, or how sensitive it is to obstacles
    • L1 - Super-light gate
    • L2 - Very light gate
    • L3 - Light gate
    • L4 - Average-weight gate
    • L5 - Moderately heavy gate - factory default
    • L6 - Heavy gate
    • L7 - Very heavy gate
    • L8 - Super-heavy gate
  • L6 - Partial opening distance: pedestrian entrance - the distance the operator opens the gate when a partial-open command is given
    • L1 - Distance: 0.5 metres
    • L2 - Distance: 1 metre - factory default
    • L3 - Length 1.5 metres
    • L4 - Length 2 metres
    • L5 - Length 2.5 metres
    • L6 - Length 3 metres
    • L7 - Length 3.5 metres
    • L8 - Length 4 metres
  • L7 - Service reminder: after how many manoeuvres the drive will signal that it would be a good idea to service the gate/drive. This is for information only.
    • L1 - Automatic - the drive counts the number of manoeuvres by itself according to their difficulty - from the factory
    • L2 - 1,000 manoeuvres
    • L3 - 2,000 manoeuvres
    • L4 - 4,000 manoeuvres
    • L5 - 7,000 manoeuvres
    • L6 - 10,000 manoeuvres
    • L7 - 15,000 manoeuvres
    • L8 - 20,000 manoeuvres
  • L8 - List of the last manoeuvres and their errors: Strictly speaking, this isn't programming, since it is used to identify the types of errors the drive recorded during the last eight manoeuvres—and it follows a different procedure.

Programming the NICE Robus and Run drives

Of course, it depends on whether you want to program a level-one function (a function that can only be switched on or off) or a level-two function (a function that can be set to one of eight values).

The procedure starts the same way for both levels, which may give the impression that level two is used to set the values of level-one functions. That is not the case. For both methods, think of the functions (LEDs L1 to L8) as 8 level-one functions and another 8 level-two functions.

Programming a level-one function (a function that can only be switched on or off)

  1. Select the function you want to switch on/off. For example, let's switch on function L6 - Pre-flashing.
  2. Press and hold the STOP/SET button. When LED L1 starts flashing, release the button.
  3. Note: You have 10 seconds for each subsequent button press. If you don't press anything within 10 seconds, programming will end automatically.
  4. Use the OPEN (up arrow) and CLOSE (down arrow) buttons to move the flashing LED up or down until it reaches the LED for the function you want to switch on/off. So, for L6 - Pre-flashing, press the CLOSE button 5 times until the flashing LED moves to position L6.
  5. Now press the STOP/SET button once without holding it down; the LED will change its flashing rate.
  6. Wait 10 seconds, and you're done. If you were switching the function on, the corresponding LED will stay lit; if you were switching it off, the LED will go out.

Programming a level-two function (a function that can be set to one of eight values)

  1. Select the function you want to reprogram and choose its new value. For example, let's change L6 - Partial opening distance from the preset value L2 - Length 1 m to L5 - Length 2.5 m.
  2. Press and hold the STOP/SET button. When LED L1 starts flashing, release the button.
  3. Note: You have 10 seconds for each subsequent button press. If you don't press anything within 10 seconds, programming will end automatically.
  4. Use the OPEN (up arrow) and CLOSE (down arrow) buttons to move the flashing LED up or down until it reaches the LED for the function whose value you want to change. So, for L6 - Partial opening distance press the CLOSE button 5 times until the flashing LED moves to position L6.
  5. Now press the STOP/SET button and hold it down, until one of the LEDs lights up (the currently set value). For the Partial opening distance function, the factory-set value L2 - Length 1 m will light up.
  6. Keep holding the STOP/SET button and repeatedly press the OPEN (up arrow) or CLOSE (down arrow) button to move the lit LED to the value you want to set. In our example, you want to move the LED from L2 - Length 1 m to L5 - Length 2.5 m, so press the CLOSE button three times.
  7. Release the STOP/SET button. The LED whose value you changed will flash for a short while (10 seconds), then stop flashing. In our example, LED L6 will flash for a short while, then stop flashing.
  8. That's it—you've successfully changed the value of a level-two function.

 If this isn't clear, don't worry—we also have step-by-step instructions for the most commonly programmed functions :)

Step-by-step instructions (examples):

Step-by-step instructions for functions that can be switched on/off (level-one programming)

Switching on automatic closing

Assumption: LED L1 is off, meaning automatic closing is disabled.

  1. Press and hold the STOP/SET button. When LED L1 starts flashing, release the button.
  2. Within 10 seconds, press the STOP/SET button once. LED L1 will then change its flashing rate.
  3. Wait for LED L1 to stop flashing and remain lit.

Switching off automatic closing

Assumption: LED L1 is continuously lit, meaning automatic closing is enabled.

  1. Press and hold the STOP/SET button. When LED L1 starts flashing, release the button.
  2. Within 10 seconds, press the STOP/SET button once. LED L1 will then change its flashing rate.
  3. Wait for LED L1 to stop flashing and remain off.

Step-by-step instructions for functions that can be set to a value (level-two programming)

Control units with a Bus-T4 connector you can also program using your mobile phone if you purchase a programmer NICE BIDIWIFI, or alternatively another programmer. Programming is more convenient, and you also get access to more detailed settings.