NICE ROBO1000: installation, wiring and setup
NICE ROBO1000 (RO1000) with control board ROA42 is a sliding gate operator with mechanical limit switches and an integrated O-CODE 433.92 MHz receiver. The maximum gate leaf weight is 1,000 kg and the maximum length is 12 m. The suitability of a particular combination also depends on resistance to movement, usage and the environment; both maximum ratings cannot automatically be used at the same time. The gate leaf length is not the clear opening width.
Before installation: check the RO1000 and ROA42 markings, ensure the gate moves easily by hand along its entire travel, verify the end stops are secure, and allow space for manual release. The warning light terminals carry 230 V; accessories have a separate 24 V output.
Choosing a remote control: NICE ROBO1000 with ROA42 board is not compatible with NICE FloR (FLOR) transmitters. The built-in receiver uses O-CODE 433.92 MHz encoding; compatible models include ON2E and ON4E.
Accessories compatible with NICE ROBO1000
The products listed are compatible with the wiring and interfaces of the ROA42 board. When choosing, check the voltage, contact type and current draw. The remote-control receiver is already built in, so no additional plug-in radio receiver is needed for standard operation.
| What | Why | Type |
| Warning light | Signals gate movement; it also includes an antenna for remote control. | |
| Photocells | Protect the passage area when the beam is interrupted. | - Relay type NICE EPM with an NC contact for basic PHOTO wiring. For phototest check the photocell settings and verify that the phototest works when testing the gate. BlueBUS photocells must not be connected to PHOTO.
|
| Transmitter | Remote control and, depending on the storage method, separate commands. | |
| Antenna | Can improve reception where the signal is weak. | |
| Key switch | Local command without a remote control. | |
| Rack | Transfers movement from the pinion to the gate leaf. | |
| Wi-Fi interface | Adjust supported settings using the MyNice Pro app. | |
| Programmer | Professional diagnostics and advanced settings. | |
Add up the current draw of devices powered from terminals 8–9 and keep it within their 100 mA limit. Phototest output 8–12 also has a 100 mA limit. If the combined load on both outputs is higher, check the load capacity of the ROA42 board. In standby mode, the accessory output is switched off. BiDi-WiFi, Oview and ProView connect via the BusT4 interface, not to the 8–9 power terminals.
What type of gate is the ROBO1000 suitable for?
When choosing, assess the gate leaf weight and length together, resistance to movement along its full travel, the number of opening cycles and the environmental conditions. Measure the force required to move the gate and check that it remains within the operator's capacity throughout its travel.
NICE ROBO1000 OPERATOR LIMITS
Weight and length are separate maximum ratings. When combining them, add the severity indices from the table below.
| ROBO1000 | Maximum | Index at maximum |
| Gate leaf length | 12 m | 50% |
| Gate leaf weight | 1,000 kg | 60% |
A 1,000 kg gate leaf measuring 12 m has an index of 110% (60% + 50%). An index above 100% exceeds the recommended operating limit. Other adverse factors increase the index; therefore, the separate maximum ratings cannot automatically be used at the same time.
NICE ROBO1000 OPERATOR SERVICE LIFE
Add the gate leaf weight and length indices, then include other factors if they are likely to occur more than 10% of the time. Use the graph below to estimate the service life in number of cycles. Also check suitability based on the actual force required to move the gate.
Example: A 300 kg gate leaf measuring 5 m has an index of 10% + 10% = 20% before other factors are included. The cycle estimate is read from the graph at an index of 20%.
| Properties of the entire automation system | Index | Service life graph |
|---|
| Gate leaf weight |  A = index (%), B = service life (cycles). |
|---|
| Up to 200 kg | 5% |
| Over 200 up to 400 kg | 10% |
| Over 400 up to 500 kg | 20% |
| Over 500 up to 600 kg | 30% |
| Over 600 up to 800 kg | 50% |
| Over 800 up to 1,000 kg | 60% |
| Gate leaf length |
|---|
| Up to 4 m | 5% |
| Over 4 up to 6 m | 10% |
| Over 6 up to 8 m | 20% |
| Over 8 up to 10 m | 35% |
| Over 10 up to 12 m | 50% |
| Other factors (with a probability of occurrence above 10%) |
|---|
| Temperature above 40 °C or below 0 °C, or humidity above 80% | 15% |
| Dust or sand | 15% |
| Salt in the environment | 20% |
| Movement interrupted by the Photo input | 15% |
| Movement interrupted by the Alt input | 15% |
For a total index above 100%, choose a more powerful model. Enlarge the index table and service life graph.
Installing the drive and limit switches
First prepare a solid foundation and cable conduits, then install the drive and the M4 rack. The images below show the positions of the foundation plate, pinion and stops. Click to enlarge them.

Rack and mechanical stops
The rack must mesh with the pinion along its entire travel; leave approximately 2 mm of clearance. The weight of the gate must not put a load on the pinion. When opening and closing, stop the gate 2–3 cm before the mechanical stop, slide the relevant limit switch bracket along the rack until it clicks, then move it at least another 2 cm. After securing it, check that the gate stops correctly by running a test cycle.

Left- or right-hand installation
The drive is factory-configured for right-hand installation. For left-hand installation, disconnect the mains power supply. As shown in the images below, pull out and rotate 180° the LIMIT SWITCH connector and the MOTOR connector; this does not involve mechanically rotating the motor. After wiring, check the direction of movement and that the limit switches are assigned correctly, then repeat device learning. Use the key release only after the gate has stopped.



Wiring preparation
Prepare the cables before securing the drive. For a different cable route or more demanding conditions, check that the cable cross-section and length are suitable.
| Circuit | Cable and length |
| 230 V supply | 3 × 1.5 mm² up to 30 m; for longer runs, e.g. 3 × 2.5 mm² and grounding at the drive |
| 230 V beacon | 2 × 1.5 mm² up to 10 m |
| Antenna | RG58 coaxial cable up to 10 m, preferably under 5 m |
| Photocells | TX 2 × 0.25 mm²; RX 4 × 0.25 mm², up to 30 m |
| Key switch | Two 2 × 0.5 mm² cables or one 4 × 0.5 mm² cable, up to 20 m. For a single NO contact on SbS, a two-wire cable is sufficient. |
ROA42 board and terminals
The image marks the connection points, PROGRAM and RADIO buttons, TL/TP/F trimmers and programming switches. Make connections with the mains power supply disconnected.

Enlarge the close-up of the ROA42 buttons, switches and terminals
| Terminals | Function and connection |
| 1–2 | Antenna for the integrated 433.92 MHz receiver. |
| 4–5 | Output 230 V AC for a self-flashing beacon. Select a beacon rated for the correct voltage. |
| 8–9 | Accessory power supply 24 V DC (±10%), 100 mA max. total; terminal 8 = 0 V, terminal 9 = +24 V. The output is switched off in standby mode. |
| 9–10 | STOP: NO or NC contact, or 8.2 kΩ resistor. The type is detected during learning. |
| 9–11 | PHOTO: NC safety contact of the photocell relay. |
| 8–12 | TX transmitter power supply during photocell testing; max. 100 mA at the photocell test output. |
| 9–13 | SbS (step-by-step): voltage-free NO contact, e.g. NICE EKSEU. |
Photocells, photocell test and STOP
ROA42 uses a PHOTO relay input; suitable examples include NICE EPM. Two-wire BlueBUS photocells must not be connected to PHOTO.
Without photocell testing
Power both TX and RX from 8–9; connect the RX NC safety contact to 9–11.

With photocell testing
RX remains connected to 8–9, while TX is powered from 8–12. The ROA42 board supplies accessories with 24 V DC. For EPM photocells, do not automatically change the SYNC jumper when enabling photocell testing. The setting depends on how the photocells are powered; test the gate to verify that photocell testing works correctly.

After any change to PHOTO or STOP, repeat device learning and test the gate response. When STOP is activated, the drive stops immediately and makes a short reverse movement.
Initial start-up and device learning
- Disengage the drive, move the gate manually to approximately the middle of its travel, re-engage it and switch on the power.
- Check the input LEDs and the operation of both limit switches. Perform the learning procedure even if no additional accessories are connected.
- Press and hold PROGRAM. After about 3 seconds, the OK LED starts flashing rapidly. Wait until STOP is lit and the green OK LED stays on steadily; release PROGRAM within 10 seconds.
- Three green flashes confirm that the settings have been saved. Five red flashes immediately after learning mean that the procedure was unsuccessful. Disconnect the power and check PHOTO, STOP and the wiring, then repeat the learning procedure. Distinguish this one-off learning result from the repeated operational signal 5× red OK.
- Test opening and closing, and check the direction, stopping at the limits, photocells, STOP and manual release. Carry out a safety test and force measurement.
Repeat the learning procedure after changing the PHOTO/STOP inputs, DIP switches 1/2 or drive orientation.
ROA42 board settings
TL, TP and F trimmers
| Trimmer | Range and setting |
| TL | Maximum operating time; marked settings: 20, 30, 60, 90 and 120 s. After a full opening and closing cycle, set a 2–3 s margin. When deceleration is enabled, the slow phase starts after TL/2. If the 120 s setting is still insufficient, consider adjusting the TLM jumper as instructed in the manual and measure the resulting time at the gate. |
| TP | Pause before automatic closing; marked settings: 3, 20, 40, 60 and 120 s. Used in automatic modes. Verify the actual pause by testing the gate. |
| F | Motor force setting: MIN, 25%, 50%, 75% and MAX are positions on the trimmer. The percentages do not represent a guaranteed proportion of the measured force in newtons. The setting must be verified by force measurement and a safety test. |
The factory settings are DIP 1 ON, DIP 2 OFF (semi-automatic mode) and DIP 8 ON (deceleration). The default TL setting is 90 s. The approximate reference settings for TP and F are 60 s and 75%; check the actual settings on the board and during a gate test.
DIP 1 and 2: operating mode
| DIP 1 / 2 | Mode |
| OFF / OFF | Manual operation: the gate moves only while the command is held continuously |
| ON / OFF | Semi-automatic; an impulse starts the full movement to the limit switch or until TL expires; factory setting |
| OFF / ON | Automatic with TP pause |
| ON / ON | Automatic with “always close” function: if the gate is open when power is restored, closing is preceded by 5 s of pre-flashing |
DIP 3 to 10: additional functions
| DIP | When ON |
| 3 | Shared entrance operation: another step-by-step command does not interrupt opening; during closing, it stops the gate and reverses its direction. This function is not available in manual mode. |
| 4 | 5 s beacon pre-flashing; 2 s in manual mode. |
| 5 | In automatic mode, closing starts 5 s after the photocells are cleared. In semi-automatic mode, PHOTO activation during closing triggers automatic closing after the TP pause. |
| 6 | PHOTO is also active during opening and stops the gate. In semi-automatic or automatic mode, opening resumes when the photocells are cleared. |
| 7 | Soft start. |
| 8 | Deceleration starts after TL/2. Speed drops to 30% of the nominal value and motor torque by 70%. Speed drops to 30% of the nominal value and motor torque by 70%. |
| 9 / 10 | Braking: OFF/OFF disabled; OFF/ON light; ON/OFF medium; ON/ON strong. |
With TL set to 90 s, deceleration starts after approximately 45 s. A change to TL takes effect on the next opening cycle. If the gate stops before reaching the end, check for mechanical resistance, TL, F and the effect of deceleration; increasing F alone is no substitute for a safety test.
Standby mode
Standby is enabled by default. After successful learning, it activates after 5 minutes of inactivity; before learning, after 10 minutes. The 24 V accessory output is then switched off. If a connected device requires continuous power, choose a suitable power supply or disable standby; power consumption will increase. The time can be changed via Oview/ProView.
Briefly press and release PROGRAM, then check the status: two OK flashes = standby active, one flash = inactive. To change the status, select the desired option according to the OK flashes (two = on, one = off), then hold PROGRAM for at least 5 s and release it when OK returns to its normal 1 Hz flashing. Check the status again afterwards.
Connecting BusT4 programming devices
The ROA42 board has a connector marked IBT4N for in the board illustration. With the power disconnected, insert BiDi-WiFi directly into the BusT4 connector. To connect ProView or Oview use the IBT4N. Disconnect the mains power before inserting it; an incorrectly inserted module may damage the control unit.
BiDi-WiFi is used to configure supported parameters via MyNice Pro. Oview and ProView are service programming devices. These devices do not replace the O-CODE radio receiver and must not be connected to the power output 8–9.
Remote Controls and Built-In Receiver
The integrated ROA42 receiver operates at 433.92 MHz with O-CODE coding and can store up to 100 transmitters in Mode I. A suitable example is the NICE Era One ON2E. NICE FloR (FLOR) transmitters are not compatible with this receiver and cannot be stored in it. Matching frequency alone (433.92 MHz) is not enough; check the remote control's coding before ordering.
Mode I: Store All Buttons
- Press and hold RADIO for about 4 seconds, then release it when LED R lights up.
- Within 10 seconds, press and hold a button on the new transmitter for about 3 seconds.
- Three flashes of LED R confirm that it has been stored. Buttons 1/2/3/4 are assigned to SbS/pedestrian opening/open/close. The two-button ON2E has buttons 1 and 2 only.
Mode II: One Button, One Command
- Briefly press RADIO 1× for SbS, 2× for pedestrian opening, 3× for open, or 4× for close.
- Check that LED R flashes the selected number of times in confirmation. Within 10 seconds, press and hold the selected transmitter button for about 3 seconds.
- Three flashes of LED R confirm that it has been stored. The same command can be stored for another transmitter by repeating the previous step within 10 seconds; the mode exits automatically if no further action is taken.
Adding a New Remote Control Using One Already Stored
When the motor is stopped, you can add a new transmitter without using the RADIO button on the control board. Leave powered only the receiver for the gate where you want to store it; this procedure may affect all receivers within range.
- Near the control board, press and hold the same button on the new remote control for about 5 seconds.
- On the already stored old remote control, press the corresponding button 3 times, about 1 second each time.. In Mode I, this can be any button; in Mode II, use the button for the command you want to transfer.
- On the new remote control, press the same button again for about 1 second and check that it works by sending a test command.
The new remote control adopts the storage mode of the old one. Six flashes of LED R during the procedure indicate incompatible coding; eight flashes indicate that the memory is full.
Erasing and Locking the Radio Memory
If you lose your only remote control, contact a service technician before erasing the memory; an incorrect procedure may also delete the other stored remote controls. The radio memory lock prevents both adding and deleting remote controls.
Remote Control Pairing Guide
The steps for the built-in ROA42 receiver are listed above. The image below links to general NICE pairing instructions; for the ROBO1000, follow the timings and LED R confirmation described here.

LED Diagnostics
During normal operation, the green OK LED flashes about once per second. Repeated groups of red flashes separated by a one-second pause indicate a fault; single flashes during device learning should be interpreted according to the relevant procedure. Always perform a functional test after repairs.
| Indication | Check |
| OK LED off | Power supply, switch and fuses; identify the cause of the outage. |
| 1× red OK flash | Unsuccessful learning or a change to DIP 1/2 without subsequent learning. Check PHOTO and STOP, then repeat device learning. |
| 2× red OK flashes | PHOTO, obstruction, NC contact and photocell test. |
| 4× red OK flashes | STOP and its learned type. |
| 5× red OK flashes | Error saving internal parameters. Wait at least 30 s, while the control unit attempts to resume operation. If the error persists, contact NICE service. |
| 7× red OK flashes | After changing DIP 1/2 repeat the learning procedure or restore the previous mode. If the error is unrelated to a mode change and persists, have a service technician check the control board's internal circuits and the motor wiring. |
| 8× red OK flashes | Another command is still active. Release it and check the SbS contact, button or transmitter holding it. |
The PHOTO and STOP LEDs are lit when the safety circuit is ready; the SbS LED is lit when a command is present. When the relevant limit switch is activated manually, its LED should go out. When replacing fuses, first eliminate the cause of the fault and use only the ratings specified for the particular control board.
NICE ROBO1000 Technical Specifications
| Parameter | ROBO1000 / ROA42 |
| Gate | Separate maximum ratings: 1,000 kg and 12 m; check the combination against the severity index |
| Power supply / power consumption | 230 V AC, 50/60 Hz / 350 W |
| Motor | 230 V AC; accessory output is separate, 24 V |
| Force | Rated 300 N; max. starting force 680 N |
| Speed | Approx. 9 m/min at rated load |
| Duty cycle | Gate leaf up to 4 m: 16 cycles/h; up to 8 m: 8 cycles/h. No separate cycles-per-hour rating is specified for gate leaves over 8 m. Maximum continuous operation: 4 min. |
| Environment | −20 to +55 °C; IP44 |
| Dimensions / weight | 363 mm wide × 238 mm deep × 364 mm high; 11.5 kg |