Description of NICE Sumo SU2000V – operator for a sectional or suspended gate up to 25 m², with increased speed

NICE SUMO SU2000V is a shaft-mounted operator for sectional garage doors and suspended sliding gates, including those with two counter-moving leaves. It has a 24 V DC motor with a magnetic encoder, a torque of 82 Nm and a speed of 11–23.5 rpm. The maximum sectional door area is 25 m².

The SU2000V does not include a control unit. For a balanced sectional door, add a NICE DPRO924, which powers the motor and controls the accessories. The 230 V AC mains supply is connected to the control unit, not directly to the motor. The operator is non-reversible and is released manually using the release cable.

The encoder tracks the operator's position; the open and closed positions must be learned. The door must have mechanical stops and be correctly balanced. The motor cannot compensate for damaged springs or a door that moves stiffly.

Quick navigation
Choosing an operatorAccessories
Package contentsInstallation
Manual releaseWiring
Initial setupSettings
Remote controlsDiagnostics
ResetMaintenance
SpecificationsPDF manual

Control unit and accessories

The following wiring and setup instructions apply to the SU2000V with DPRO924 and an incremental encoder. For an older installation with an A924, use its own terminals and manual; these control units are not wired interchangeably.

The DPRO924 wiring, learning procedure and settings below apply to a balanced sectional door. For a suspended sliding gate, select a control system specifically intended for this application and check the entire chain-drive assembly.

WhatWhyType
Control unitRequired for the motor and safety devices; wiring.
PhotocellsStandard relay NC output, Phototest wiring.
Flashing lightA separate 24 V flashing lamp connected to OUT1.
Radio receiver and remote controlSM socket, selection and pairing.
Backup batteryEmergency power supply for the DPRO924 after programming.
Drive adapterDirect adapter or chain, depending on the installation.

The DPRO924 does not have BlueBUS: EPMB is not a direct replacement for relay-output EPM photocells. The PS124 battery used with SOON operators is not a backup battery for the DPRO924.

When to choose the SUMO SU2000V

The SU2000V is suitable when a mechanically balanced sectional door needs faster operation while maintaining a torque of 82 Nm. Door-leaf speed depends on the drums and drive ratio; motor speed is not the gate speed in metres per second.

ConditionWhat it means
Area up to 25 m²Maximum area for a sectional door. The manufacturer specifies this variant for areas of 10–25 m²; suitability for a specific door also depends on resistance, balance and the required torque. This figure does not specify the weight or length of a suspended door leaf.
Torque: 82 NmAssess the torque required at the shaft for the complete door, including at startup.
Speed: 11–23.5 rpmMotor speed range; gate speed depends on the drum and any reduction gearing.
Duty cycle: 50%A 50% duty cycle means intermittent operation with pauses, not continuous operation or a fixed number of cycles per hour.
IP44 ratingProtect the motor from flooding and unsuitable environmental conditions; the separate DPRO924 has an IP55 rating when its enclosure is properly closed.

SU2000V operator

SUMO SU2000V
NICE SU2000V
Standalone NICE SUMO SU2000V shaft-mounted operator
Sectional door up to 25 m².
82 Nm.
11–23.5 rpm
Higher speed.

With these models, higher speed means lower available torque. All three are standalone 24 V DC motors without a control unit; for a sectional door, add NICE DPRO924. Compare the required shaft torque, not just the area or speed.

SUMO SU2000V package contents

Standalone motor with encoder, mounting bracket, drive key, mounting hardware, and cable-operated release with handle. DPRO924, radio receiver, photocells and chain drive are not automatically included with the motor.

NICE SUMO motor, bracket and supplied mounting hardware

Installing the operator

Disconnect the mains power and backup battery before starting work. The door must be mechanically safe and correctly balanced, with functioning springs, tracks and stops. The operator will not fix a door that is difficult to move.

Direct shaft mounting

The NICE SUMO SU2000V operator mounts directly on the sectional door shaft Ø 25.4 mm. For shafts Ø 31.75 / 35 / 40 mm, use NICE CRA9. The mounting bracket is included; choose wall anchors to suit the substrate. The Ø 25.5 mm opening in the motor does not indicate a different recommended shaft diameter.

  1. Remove the cover, prepare the cable glands and hold the release lever in place during installation; secure it in the installation position as shown.
  2. Slide the motor onto the shaft, aligning the keyways. Insert the drive key and secure it against slipping out with a suitable retaining collar.
  3. Bolt the bracket to the operator and anchor it to the wall so that the operator remains parallel to the wall.
  4. Release the installation lock on the release lever, return it to the operating position, and check the cover and release mechanism.

For a steel structure, use M8 bolts, grade 6.8 or A2-50. Anchoring to any other substrate must safely withstand a tensile load of 1,000 N; select the anchor type to suit the structure.

SUMO: cable glands, release lever installation position, drive key and bracket
SUMO: cable glands, release lever installation position, drive key and bracket

Offset mounting using a chain

Where there is not enough room for direct mounting, use a shaft with an 18-tooth sprocket NICE CRA1 in the operator and a sprocket on the door shaft. The drive uses a 1/2″ × 5/16″ chain NICE CRA3 (1 m) or NICE CRA4 (5 m), with a connector NICE CRA2. Use brackets to mount the operator off-axis NICE CRA8.

Drive ratioComponents and result
1 : 1NICE CRA1 + NICE CRA7 (18 / 18 teeth). No speed reduction.
1 : 2NICE CRA1 + NICE CRA6 (18 / 36 teeth). The door shaft turns more slowly; the transmitted torque and door construction must be assessed.

The sprockets must be aligned, the chain correctly tensioned, and guarded against catching hands or clothing. Changing the drive ratio does not automatically change the permitted door area. Dimensions, balance, travel and the complete assembly must be assessed together.

Position the chain at least 2.4 m above the floor and out of reach; if this is not possible, fit a protective guard. Under a load of 4,000 N, the shaft carrying the sprocket must not deflect by more than 2 mm.

SUMO: vertical chain drive with CRA1, CRA6 or CRA7 and CRA8 brackets
SUMO: vertical chain drive with CRA1, CRA6 or CRA7 and CRA8 brackets

Chain-drive setup for a suspended sliding gate

For a suspended gate, the loop consists of a shaft with a sprocket NICE CRA1, a tensioner with an idler sprocket NICE CRA5, chain NICE CRA4 and connectors NICE CRA2. Attach the gate leaf to the upper or lower chain run, depending on the direction of travel. For two opposing leaves, attach one to the upper run and the other to the lower run.

This is a custom-designed chain-drive assembly. The sectional door area limit does not determine the permitted weight or length of a suspended gate leaf. Check the resistance to movement, force transmission, travel path, mechanical stops and protection of pinch points.

Suspended gate chain loop and NICE CRA5 tensioner

SUMO: horizontal chain loop installation for a suspended gate
SUMO: horizontal chain loop installation for a suspended gate

Manual release and return to motorized operation

The SU2000V uses the supplied nylon cable with handle to release the drive from floor level; the cable run can be no longer than 6.5 m. Release the drive only when the door is stationary and balanced.

  1. Pull the handle down to position 1 as shown.
  2. Move the door manually with care.
  3. Before operating electrically, return the release mechanism to its original locked position and check that the drive is engaged.

SUMO SU2000V: floor-level cable release, position 1 for manual operation
SUMO SU2000V: floor-level cable release, position 1 for manual operation

An external release is available separately: NICE KA1 (6 m steel cable) and NICE KIO or NICE KIOMINI. This does not replace the required correct installation of the supplied release; adapt the cable routing and mechanical connection to the operator.

With SUMO and DPRO924, position synchronization must be restored after manual movement. If the control unit was switched on while the gate was released, it will record the release. Restore synchronization by moving the gate to the saved fully closed position; until it is synchronized, open it while holding the command button. Monitor the gate while doing so, and do not bypass the safety devices.

Wiring SU2000V with DPRO924

Disconnect the mains supply and PS224 before starting work. The motor cable and encoder cable are separate circuits. DPRO924 controls one SU2000V motor on a counterbalanced sectional door.

DPRO924: motor, incremental encoder, commands, relay photocells, warning light and safety circuit
DPRO924: motor, incremental encoder, commands, relay photocells, warning light and safety circuit

Wiring and cable lengths

ConnectionCable / maximum length
Mains supply to DPRO9243 × 1.5 mm² / 30 m. For longer runs, use 3 × 2.5 mm² cable and protective earthing at the automation unit.
Motor3 × 2.5 mm² / maximum 10 m; motor conductors as specified by the motor terminals, protective conductor as specified by the wiring for the particular assembly.
Incremental encoder2 × 1 mm² / maximum 10 m; route separately from power wiring.
Warning light2 × 0.5 mm² / 20 m.
Photocells4 × 0.5 mm² / 20 m; specific branches depend on the selected wiring diagram.
Command switch2 × 0.25 mm² / 20 m or 4 × 0.5 mm².
AntennaRG58 / maximum 10 m, 5 m or less recommended.

Terminals and accessory polarity

DPRO924 terminalFunction / wiring
MOTOR 1 / 2 / 31 and 2 – 24 V DC motor output; 3 – protective earth. The polarity at the motor output changes with the direction of movement. Do not connect 230 V mains to the motor terminals.
Incremental encoderTwo encoder signal wires; non-polarized. Not an auxiliary power supply.
GND (1) / 24 V (2)1 GND = negative (−), 2 24 V = positive (+); 24 V DC −30% / +50%, maximum 200 mA for all accessories combined.
Phototest (3)Tested positive supply for TX: 3 = positive (+), GND 1 = negative (−); 24 V DC, max. 200 mA at the Phototest output.
Common / COM SBYPositive common terminal for commands, 24 V DC. Common for SbS remains active; COM SBY for Open/Close/Photo/Photo2 switches off in Total Stand-by mode. This is not GND.
SbS / Open / CloseVoltage-free NO contacts: SbS to Common, Open and Close to COM SBY. The contacts themselves are not polarized.
Photo / Photo2Voltage-free NC photocell contact; the common terminal connection depends on Phototest or Stand-by mode.
STOP Safety Edge8.2 kΩ resistive or OSE optical safety edge. OSE: +12 V = positive, GND = negative, SIG = signal.
ALTNC safety circuit. An open contact prevents operation.
OUT1 / OUT2 / OUT3OUT1 – 24 V warning light up to 25 W with independent flashing; OUT2/3 – voltage-free relay contacts for resistive loads up to 3 A. Do not assign fictitious +/− polarity to the OUT2/3 contacts.
LIGHT on the cover board1 = negative (−), 2 = positive (+), 24 V DC, maximum 5 W; cable up to 2 m. The output is not short-circuit protected.

Terminal block directly in the SU2000V

SU2000V: terminals 1/2 are for the motor, 3/4 for the encoder. Connect 1/2 to the DPRO924 motor output and 3/4 to the Incremental encoder input. Label Terminal 3 on the motor is not PE. According to the SU2000V wiring diagram, the third conductor of the three-core motor cable is safely insulated at the motor end. Protective earthing for the DPRO924 mains supply is still mandatory.

SUMO SU2000V: motor terminals 1/2 and encoder terminals 3/4; third motor cable conductor safely insulated
SUMO SU2000V: motor terminals 1/2 and encoder terminals 3/4; third motor cable conductor safely insulated

EPM photocells with Phototest

DPRO924 uses NICE EPM with a conventional relay output. For the safety function, connect terminals on the EPM 4 COM and 5 NC; contact 3 NO is not the correct safety contact.

DevicePower supply and contact
TX EPM1 = positive (+), 2 = negative (−). In Phototest mode: TX 1 → Phototest (3) DPRO924, TX 2 → GND (1) DPRO924.
RX EPM1 = positive (+), 2 = negative (−). RX 1 → 24 V (2) DPRO924, RX 2 → GND (1). RX 4 COM → 24 V (2), RX 5 NC → Photo or Photo2. Contact 4/5 is voltage-free; do not use contact 3 NO.
Two pairsAssign each pair to the correct input. If they interfere with each other, change their position or use suitable optical shields. EPM synchronization via SYNC requires AC power; do not use it blindly with the control unit's DC output.

EPM: TX/RX power supply 1 (+), 2 (−), relay contacts 4 COM and 5 NC
EPM: TX/RX power supply 1 (+), 2 (−), relay contacts 4 COM and 5 NC

DPRO924: RX to GND/24 V and TX to GND/Phototest
DPRO924: RX to GND/24 V and TX to GND/Phototest

Phototest checks the photocells before movement. After wiring it, program the safety devices. Unused Photo or Photo2 is linked to Phototest in this wiring diagram; this does not replace the required gate protection.

Alternative: Total Stand-by

Total Stand-by is enabled via Oview; after the set time (factory default: 1 min), it reduces power consumption by switching off the accessories. TX 1 (+), RX 1 (+) and RX 4 COM → COM SBY; TX 2 (−) and RX 2 (−) → GND (1); RX 5 NC → Photo or Photo2. Phototest is not performed with this wiring. Link unused Photo/Photo2 to COM SBY. Do not combine the two wiring diagrams.

DPRO924: separate alternative for photocell power supply in Total Stand-by mode
DPRO924: separate alternative for photocell power supply in Total Stand-by mode

Safety edge and safety circuit

DPRO924: resistive edge SIG/GND and optical OSE +12 V/SIG/GND
DPRO924: resistive safety edge SIG/GND and optical OSE +12 V/SIG/GND

An active safety edge is required for semi-automatic and automatic operation of a sectional door. Automatic operation also requires photocells. In hold-to-run mode, the operator must have a direct view of the entire door; access to the controls must be restricted according to the installation location.

The 8.2 kΩ resistive edge is connected between SIG and GND, with no polarity. Optical OSE according to the markings: brown wire to +12 V, green to SIG, white to GND. If a different color-coding system is used, follow the markings provided by the edge manufacturer. With this resistive interface, NC contacts are connected in series with the terminating 8.2 kΩ resistor, and NO contacts in parallel with the resistor; the wiring must comply with the safety design. Repeat the learning procedure after making a change. The resistor must not be used to bypass required protection.

Warning beacon and status indicator

The OUT1 is intended for the NICE ELDC with its own flashing function, 24 V, max. 25 W. OUT1 is not an auxiliary GND/24 V pair; do not infer the polarity order from other connectors. The ELDC power supply pair itself has no specified +/− polarity in its diagram. Connect the antenna to the radio receiver using its connector.

The status indicator on the cover board is separate: LIGHT 1 (−), 2 (+), 24 V DC / 5 W. It goes out when the safety circuit is open, flashes 0.5 s ON / 0.5 s OFF during normal operation, and follows the OK indicator when there is a fault. The cable can be up to 2 m long, and the output is not short-circuit protected.

DPRO924: LIGHT 1 (−), 2 (+) on the cover button board
DPRO924: LIGHT 1 (−), 2 (+) on the cover button board

Backup power and service interface

NICE PS224 connects to the designated DPRO924 battery connector only after installation and programming are complete. The number of movements possible during a power outage is not fixed and depends on the door and battery. Oview connects via NICE IBT4N and allows adjustment of force, sensitivity and deceleration points, as well as diagnostics. Choose accessories for DPRO924, not for the old A924.

Initial startup of DPRO924 with SUMO

DPRO924: OPEN, STOP and CLOSE buttons on the control unit cover
DPRO924: OPEN, STOP and CLOSE buttons on the control unit cover

On the cover board, the switches enabling the OPEN and CLOSE buttons must be set to ON; STOP is always active. Before learning, the door should be approximately 50 cm above the floor, so the direction can be checked safely. The green OK indicator flashes about once per second; ALT/Photo/Photo2 must match the wiring.

1. Learning the safety devices

At least one safety device must be connected. Learn the devices and positions one after the other, without interruption.

  1. Set A1 to ON; A2/A3/A4 to OFF.
  2. Hold STOP for about 3 s until the OK indicator is steadily red; release it.
  3. When finished, set the switches to OFF and immediately continue with incremental encoder learning.

2. Positions with an incremental encoder

If you do not save a custom partial-opening position, the default position is 1/4 of the travel. It can be changed during learning or via Oview.

  1. Set B2 OFF, B3 OFF; A1 ON, A2/A3/A4 OFF.
  2. Hold STOP for about 3 s until the indicator is steadily red, then release it.
  3. Use OPEN to move the door to the desired open position before the mechanical stop. Confirm by holding STOP for 3 s: one red flash.
  4. Use CLOSE to move the door to the fully closed position. Confirm by holding STOP for 3 s: two red flashes.
  5. For a custom partial opening, use OPEN to move the door to that position and confirm by holding STOP for 3 s: three red flashes. Otherwise, continue to the next step.
  6. Set A1 to OFF; select A3/A4 according to the operating mode and confirm by holding P1 for at least 2 s.

If OPEN closes the door, stop, disconnect mains power and the battery, swap the motor wires at outputs 1/2, and restart the learning procedure. Do not swap the encoder pair to change the direction.

3. Learning the forces

After setting the positions, perform complete opening and closing cycles without interruption until the unit stops alternating red/green flashes of the OK indicator during movement. An interrupted cycle will not be counted. During learning, the unit uses maximum force: the area must be supervised. Repeat force learning after changing the speed, deceleration points or sensitivity. Carry out safety tests when finished.

The unit initially calculates the RA/RB deceleration points; adjust them via Oview. Repeat force learning after changing the deceleration points.

Setting DPRO924 modes

DPRO924: DIP switch group A (1–4) and DIP switch group B (1–3)
DPRO924: DIP switch group A (1–4) and DIP switch group B (1–3)

Switch groups A and B are on the main board. After changing them, OK may flash red/green alternately and the unit may reject commands: confirm the correct configuration by pressing P1 for 2 s, or repeat learning of the safety devices. If these functions are set via Oview, the corresponding DIP switches must be OFF.

DIP A – operation

SettingMeaning
A1 OFF, A2 OFF, A3 OFF, A4 OFFHold-to-run: movement only while a command is held.
A1 ON, A3/A4 OFFLearning the safety devices and positions. For SU2000V, also set A2 to OFF.
A1 OFF, A2 OFF, A3 OFF, A4 ONIndustrial mode: semi-automatic opening, closing by holding the command.
A1 OFF, A2 OFF, A3 ON, A4 OFFSemi-automatic operation after position learning.
A1 OFF, A2 OFF, A3 ON, A4 ONAutomatic closing with a stored pause time.
A2 ONReverse the absolute encoder; not used with the SU2000V incremental encoder.

DIP B – sensitivity, speed and motor

SwitchStatus and meaning
B1 – sensitivityOFF = off, ON = on. ON reduces the impact force when an obstacle is encountered; after changing it, learn the forces and perform a measurement.
B2 – speed adjustmentOFF = normal operation; ON = speed adjustment; OK flashes orange rapidly.
B3 – motor typeOFF for the SU2000V with encoder. ON is for a motor with electromechanical limit switches.

Automatic closing – pause time

  1. After learning the positions, set A3/A4 to ON and A1/A2 to OFF.
  2. Press and hold P1 for at least 2 seconds.
  3. Send an OPEN command and wait until fully open.
  4. From this point, wait for the desired pause time, then send a CLOSE command. The time is saved.

To change the pause time, set A4 to OFF and confirm by holding P1 for 2 seconds; this cancels the previous pause time. Then set A4 to ON, confirm by holding P1 for 2 seconds, and repeat the opening, waiting and closing sequence.

Travel and deceleration speed

Opening, slow opening, closing and slow closing are set separately. You can use Oview or the control board buttons:

  1. Set B2 to ON; OK flashes orange rapidly.
  2. Hold P1 and send OPEN or CLOSE, depending on the direction being adjusted.
  3. While holding P1, adjust the current section: OPEN increases the speed by 5% per press; CLOSE decreases it by 5%.. Green OK indicates a normal-speed section; red indicates deceleration.
  4. Release P1; to adjust the next movement, start again by holding it down.
  5. Set B2 back to OFF, complete force learning and carry out the tests.

The current monitoring function is disabled while P1 is held. Monitor the gate during this operation; do not use it to test the force against an obstacle.

Remote control and antenna

With a supported receiver in Advanced Mode 2, command 13 electronically unlocks the automation system.. This cancels the electronic lock on the automation system; it does not mechanically release the drive. Assign the button according to the instructions for the specific receiver.

Insert the radio receiver into the SM socket with both mains power and the battery disconnected. Do not confuse the equipment supplied with a standalone drive with a complete kit: choose the receiver and transmitters to match the equipment actually supplied.

NICE OXIBD supports both unidirectional and bidirectional transmitters; a suitable unidirectional transmitter is the NICE MYGO4. An older installed receiver may use different coding. The same 433.92 MHz frequency alone is not enough.

In standard Mode 1, the receiver outputs are: 1 – step-by-step, 2 – partial opening, 3 – opening, 4 – closing. Mode 2 lets you assign an individual button to a selected command. Follow the instructions for the specific OXIBD receiverfor precise pairing and deletion; the control unit buttons do not erase the receiver’s radio memory.

For the OXIBD, connect the antenna to the receiver connector as shown in the OXIBD antenna wiring diagram. Connect the coaxial cable’s centre conductor to the signal terminal and its shield to the antenna ground. These are not the +/− power connections.

DPRO924 diagnostics

After power-up, two slow green OK flashes indicate a motor with an incremental encoder. One slow red flash confirms a learned 8.2 kΩ safety edge; two flashes confirm OSE. Rapid green flashing after power-up may indicate that the memory has not been learned.

Red OK flashesCause and check
2 flashesPhotocell: obstruction, optics or relay wiring.
3 flashesForce, sensitivity or blocked encoder: check for mechanical resistance and inspect the encoder cable.
4 flashesSTOP/ALT or release: secure the motor and check the safety circuit.
5 flashesInternal parameters: press STOP on the cover and wait at least 30 seconds. If the fault persists, contact service or perform a reset and relearn.
6 flashesThe permitted number of cycles per hour has been exceeded: wait a few minutes for the limit to clear.
7 flashesInternal electrical fault: press STOP, disconnect all power sources, and have the board and wiring inspected by a qualified technician.
8 flashesContinuous input command: remove the cause of the stuck contact.
9 flashesThe automation system is electronically locked: use command 13 via a supported receiver to unlock it; radio commands.

Additional OK indicator signalsSolution
Steady red + 8 green flashesNo encoder signal. Press STOP and check the separate encoder cable.
Steady red + 10 green flashesTravel time exceeded. Press STOP and check the mechanism and positions; adjust the time via Oview.
Red/green alternating while idleDIP setting changed: check the configuration and confirm by holding P1 for at least 2 seconds.
Red/green alternating during movementForce learning in progress; complete full cycles.
Rapid orange flashingB2 is ON; complete the speed adjustment, then set B2 to OFF.

Clearing the DPRO924 memory

Resetting clears the settings, positions and learned safety devices. The plug-in radio receiver’s memory is separate.

  1. With the gate stationary, set A1/A2/A3/A4 to ON; OK flashes orange rapidly.
  2. Hold STOP for about 3 seconds until OK turns solid red, then release it.
  3. After resetting, OK flashes orange rapidly. Set all A DIP switches back to OFF; OK flashes green.
  4. Set the correct motor type, repeat safety-device and position learning, learn the forces, and carry out the tests.

Checks before handing over the gate

  1. With the drive released, check that the gate moves smoothly and is properly balanced. Manual testing must require a force of no more than 225 N. This is not the motor’s torque or the permitted impact force.
  2. After engaging the drive, test opening, closing and STOP; the gate must not bind or hit beyond the stored limit positions.
  3. Test each pair of photocells at the TX, at the RX and in the centre of the beam, for example using a cylinder 5 cm in diameter and 30 cm long. Check the gate’s actual response.
  4. Test the safety edge, safety circuit and emergency release. Measure impact forces with a suitable measuring device; repeat the test after changing the force or sensitivity.
  5. Hand over the gate only after successful testing, with its labels, release instructions and maintenance schedule in place. Pass through only when the gate is fully open and stationary.

Drive and gate maintenance

Disconnect both the mains power and the battery before each scheduled inspection. Check the bracket, anchors, wedge, shaft, release mechanism, guide components and balance; for chain drives, also check tension, wear and whether lubrication is needed. Use the operator only with functional mechanical stops and safety devices.

For normal residential use, the manufacturer recommends a professional inspection every 6 months. For more frequent use, adjust the interval to suit operating conditions; inspect and clean the EPM photocells at least every 6 months. Repeat the tests after servicing. Spring or load-bearing cable faults must be handled by a professional, not by increasing the motor force.

SUMO SU2000V technical specifications

ParameterValue
Control unitSeparate NICE DPRO924; not included with the SU2000V.
Motor power supply24 V DC; operating range 15–36 V DC.
Motor current draw / power consumption13 A DC / 500 W. This is not the current drawn from the 230 V mains.
Torque82 Nm.
Rotational speed11–23.5 rpm; settings depend on the control unit and configuration.
Sectional door areaMaximum 25 m².
Duty cycle50%.
Protection rating / temperatureSU2000V: IP44; −20 to +50 °C.
Shaft / boreShaft Ø 25.4 mm; motor bore Ø 25.5 mm.
Dimensions / weight350 × 270 × 110 mm / 10.5 kg.
Motor insulation thermal classClass B.

SUMO SU2000V dimensions, shaft bore and bracket range
SUMO SU2000V dimensions, shaft bore and bracket range

DPRO924 power supply and limits

ParameterValue
Mains power supply230 V AC, 50/60 Hz; Class I, earthing required.
Maximum mains power consumption500 W.
Accessory output24 V DC −30% / +50%, 200 mA; polarity and terminals.
BackupNICE PS224.
FusesF2 T2 A; F1 automotive 20 A. Use the same type and rating after eliminating the cause.
EnclosureIP55 when properly closed; 310 × 210 × 125 mm, approximately 4 kg.

360° view of the operator

 

How can I order this item?

Choose the option that suits you:

  1. order online: use the buy button to add the goods to your shopping cart (you will find the buy button here in the product variants table).
  2. order by email: place your order at [email protected]

Ask us anything about NICE Sumo SU2000V – operator for a sectional or suspended gate up to 25 m², with increased speed

Product: NICE Sumo SU2000V – operator for a sectional or suspended gate up to 25 m², with increased speed
Name:
Email:
Phone:
Message:
This page is protected by Google reCAPTCHA.