Connecting photocells to the NICE Rox operator

Drives NICE Rox use the technology of conventional hard-wired circuits, so in principle they are compatible with all relay-type photocells powered by 24 V. Rox drives are not compatible with photocells using BlueBus technology.

Photocells always come in pairs: a TX transmitter and an RX receiver. Photocells are divided into three types:

There is also:

Disconnect the drive from the power supply before wiring the photocells. If you are not installing photocells, fit a jumper between terminals 9 and 11 on the control unit.

Wiring wired photocells

The TX photocell is connected using a 2 × 0.5 m2, and the RX photocell is connected using a 4 × 0.5 m2. In theory, instead of running a wire from terminal 4 on the RX photocell to terminal 9 on the control unit, you can install a jumper between terminals 1 and 4 on the photocell and use a three-core cable.

Connect the photocells as follows:

  • Connect terminal 1 on each photocell to terminal 9 on the control unit.
  • Connect terminal 2 on each photocell to terminal 8 on the control unit.
  • Connect terminal 4 on the RX photocell to terminal 9 on the control unit.
  • Connect terminal 5 on the RX photocell to terminal 11 on the control unit.

Wiring one wired and one wireless photocell

This applies specifically to NICE FT210 photocells. One photocell is connected using a four-core cable; the other is battery-powered.

Connect NICE FT210 photocells to a NICE Rox drive as follows:

  1. Disconnect the drive from the power supply
  2. Set the jumpers on the TX photocell as follows:
    • Jumper J1 – remove it (if the photocells are more than 7 m apart, insert it)
    • Jumper J2 – remove it
    • Jumper J3 – remove it
  3. Set the jumpers on the RX photocell as follows:
    • Jumper J1 – remove it
    • Jumper J2 – insert it
  4. Connect the wires as follows (photocell terminals are numbered from top to bottom):
    • From Rox drive terminal no. 9 (+24V) to RX photocell terminal no. 10 (+24V)
    • From Rox drive terminal no. 8 (-0V) to RX photocell terminal no. 9 (-0V)
    • From Rox drive terminal no. 11 (PHOTO) to RX photocell terminal no. 1 (PHOTO)
    • From Rox drive terminal no. 9 (+24V) to RX photocell terminal no. 2 (COM)
  5. Reconnect the drive to the power supply

The LEDs on the RX photocell should be lit as follows (from left to right):

  • LED 1 – green; it should be lit
  • LED 2 – red; it should be off
  • LED 3 – yellow; it should be off
  • LED 4 – red; the slower it flashes, the better the photocells can see each other; alternatively, it may show the diagnostic sequence

Wiring a reflector photocell

The only model is NICE EPMOR. The photocell, which contains both the TX transmitter and RX receiver, is wired on one side; there is only a reflector on the other side of the passage. Wiring procedure:

  1. Disconnect the drive from the power supply.
  2. Refer to figure 2 on page 2 of the manual https://fortamigo.ie/data/manualy-k-pohonom/fortamigo.ie-NICE-EPMOR.pdf There are three jumpers: J1, J2 and J3. Set them as follows:
    1. If the gate opening is wider than 4 m, remove jumper J1; if it is narrower, leave it in place
    2. Set jumper J2 to the NC position; it should be on the top two pins, leaving the bottom pin free.
    3. Leave jumper J3 in place; this means we will not use the photocell test.
  3. Connect the wiring as follows:
    1. From control unit terminal 9 to photocell terminal 3
    2. From control unit terminal 8 to photocell terminal 4
    3. From control unit terminal 11 to photocell terminal 6
    4. From control unit terminal 9 to photocell terminal 5
  4. Reconnect the drive to the power supply; it should now work.

Wiring multiple pairs of photocells

If you need to connect multiple pairs of photocells to a NICE Rox drive, they will share a power supply and their safety circuits should be connected in series. This means closing the safety circuit between terminals 9 and 11 on the control unit by running a wire from control unit terminal 9 to terminal 4 on the first RX photocell, then from terminal 5 on that same photocell to terminal 4 on the second RX photocell, and finally from terminal 5 on that photocell to terminal 11 on the control unit.

If the beam between any pair is interrupted, the safety circuit will also be broken, causing the gate to stop and start opening.

Wiring photocells to protect the gate's retraction area

If, for any reason, you also need to protect the area where the gate retracts when using a NICE Rox drive, you can:

  • either install another pair of photocells on the retraction side,
  • or install a single pair of photocells to cover the entire gate travel (if the distance between the photocells allows it)

Then set DIP switch 6 on the control unit to ON. The gate will then stop if the photocell beam is interrupted, both while closing and while opening. If a photocell beam is interrupted while the gate is opening, the gate will automatically continue opening all the way as soon as the beam is clear.