Connecting photocells to the NICE Road drive unit

Gate operators NICE Road use the technology of conventional wired circuits, so they are generally compatible with all 24V relay-type photocells. Road operators are not compatible with BlueBus photocells.

Photocells are always used in pairs: a transmitter (TX) and a receiver (RX). Photocells are divided into three types:

There is also:

Before wiring the photocells, disconnect the operator from the power supply. If you are not wiring photocells, install a jumper between terminals 1 and 5 on the control unit.

Wiring wired photocells

The TX photocell is wired with a 2×0.5 m² cable, and the RX photocell is wired with a 4×0.5 m2. In theory, you can install a jumper inside the photocell and wire the RX photocell using a three-core cable.

In the past, Road operators were supplied with various control units:

RBA0 RBA4 RBA4/A RBA4R10


Among other changes, the power supply polarity for the photocells was reversed between control units RBA4 and RBA4/A , so

New photocell wiring diagram for RBA4R10 and RBA4/A control units

In theory, instead of running a wire from terminal 4 on the RX photocell to terminal 1 on the control unit, you can install a jumper between terminals 1 and 4 inside the photocell, so you only need a three-core cable.

 

Photocell wiring for NICE Road operators with RBA4R10 and RBA4/A control units

Old photocell wiring diagram for RBA4 and RBA0 control units

In theory, instead of running a wire from terminal 4 on the RX photocell to terminal 1 on the control unit, you can install a jumper between terminals 2 and 4 inside the photocell, so you only need a three-core cable.

Photocell wiring for NICE Road operators with RBA4 and RBA0 control units

Wiring one wired and one wireless photocell

This applies only to NICE FT210 photocells. One photocell is connected using a four-core cable; the other is battery-powered.

Wire NICE FT210 photocells to a NICE Road operator as follows:

  1. Disconnect the operator from the power supply.
  2. Set the jumpers on the TX photocell as follows:
    • Jumper J1 – removed (if the photocells are more than 7 m apart, insert it)
    • Jumper J2 – removed
    • Jumper J3 – removed
  3. Set the jumpers on the RX photocell as follows:
    • Jumper J1 – removed
    • Jumper J2 – inserted
  4. Connect the wires as follows (the photocell terminals are numbered from top to bottom):
    • From terminal no. 1 (+24V) on the Road operator to terminal no. 10 (+24V) on the RX photocell
    • From terminal no. 4 (-0V) on the Road operator to terminal no. 9 (-0V) on the RX photocell
    • From terminal no. 5 (PHOTO) on the Road operator to terminal no. 1 (PHOTO) on the RX photocell
    • From terminal no. 1 (+24V) on the Road operator to terminal no. 2 (COM) on the RX photocell
  5. Reconnect the operator to the power supply.

The LEDs on the RX photocell should light up as follows (from left to right):

  • LED 1 – green; should be on
  • LED 2 – red; should be off
  • LED 3 – yellow; should be off
  • LED 4 – red; the slower it flashes, the better the photocells can see each other; alternatively, it may show a diagnostic sequence

Wiring a reflector photocell

The only model is NICE EPMOR. The photocell, containing both the transmitter TX and receiver RX, is wired on one side of the passage; there is only a reflector on the other side. Wiring instructions:

  1. Disconnect the operator from the power supply.
  2. See figure 2 on page 2 of the manual https://fortamigo.ie/data/manualy-k-pohonom/fortamigo.ie-NICE-EPMOR.pdf There are three jumpers: J1, J2 and J3. Set them as follows:
    1. If the gate opening is wider than 4 m, remove jumper J1; if it is narrower, leave it in place.
    2. Set jumper J2 to NC, i.e. it should be on the top two pins, with the bottom pin left free.
    3. Leave jumper J3 inserted; this means the photocell test will be disabled.
  3. Connect the wiring as follows:
    1. From terminal 1 on the control unit to terminal 3 on the photocell
    2. From terminal 4 on the control unit to terminal 4 on the photocell
    3. From terminal 1 on the control unit to terminal 6 on the photocell
    4. From terminal 5 on the control unit to terminal 5 on the photocell
  4. Reconnect the operator to the power supply; it should now work.

Wiring multiple pairs of photocells

If you need to connect multiple pairs of photocells to a NICE Road operator, they will share a power supply, and the safety circuits must be wired in series. This means closing the safety circuit between terminals 1 and 5 on the control unit by wiring from terminal 1 on the control unit to terminal 4 on the first RX photocell, then from terminal 5 on that photocell to terminal 4 on the second RX photocell, and finally from terminal 5 on that photocell to terminal 5 on the control unit.

This way, if the beam is interrupted at any pair of photocells, the safety circuit will also be broken, and the gate will stop and start opening.

Wiring photocells to protect the gate's sliding area

If for any reason you need to install photocells on the opening side of a NICE Road operator, you can connect them to the STOP input, i.e. terminals 3–4. In this case, when the photocells detect an obstruction, the gate will stop and reverse slightly. It will remain stopped and cannot be moved until the photocells are clear. After changing the wiring to the STOP input, the operator must be reset and programmed again.

You can also combine the two setups: install one pair of photocells in the passage, active only while the gate is closing, and a second pair outside the passage, in the area where the gate opens, which will stop the gate whenever its beam is interrupted.