Connecting photocells to the NICE MC424LR10 control unit (with MCA2R10)

Three types of photocells can be connected to the control unit:

  • both wired: EPM, BF, EPS; older models: MOF, FE, FI
  • one wired, the other battery-powered, FT210
  • reflective, i.e. one photocell is wired and the other is replaced by a reflector, EPMOR

Photocells work with the control unit by opening the safety circuit: when the photocells can see each other, the circuit is closed; when they cannot, the circuit is open. In other words, you can connect the control unit without photocells by permanently bridging the safety circuit terminals with a wire. The control unit is supplied with these jumpers already in place, so it will work without photocells even if you do not change any connections.

Photocells connected to the NICE MC424LR10 control unit can operate in three ways:

  Designation Safety circuit terminals
active only while the gate is closing FOTO 8-10
active while the gate is both closing and opening FOTO1 8-11
active only while the gate is opening FOTO2 must be reprogrammed

 

I. Type: FOTO

The photocells are active only while the gate is closing; they do not respond while it is opening. This means that if the gate is closing and you interrupt the beam between the photocells, the gate will stop and start opening. If the gate is open and you interrupt the beam, the gate will not close until you remove the obstruction from the beam between the photocells.

The safety circuit is connected between terminals 8 and 10.

  • If your gate opens inward (the motors are on the inside and the gate opens inward), these are usually the photocells on the outside.
  • If your gate opens outward (the motors are on the inside and the gate opens outward), these are usually the photocells on the inside.

If your gate opens outward but the motors are on the outside, this is essentially the same as opening inward, except that “inward” is on the outside.

II. Type: FOTO1

The photocells are active while the gate is both opening and closing. This means that if the gate is moving in either direction (opening or closing), it will stop when you interrupt the beam. The gate cannot open or close while the beam is interrupted.

The safety circuit is connected between terminals 8 and 11.

  • If your gate opens inward (the motors are on the inside and the gate opens inward), these are usually photocells mounted on posts inside, just beyond the gate's fully open position.
  • If your gate opens outward (the motors are on the inside and the gate opens outward), these are usually photocells mounted on posts outside, just beyond the gate's fully open position.

If your gate opens outward but the motors are on the outside, this is essentially the same as opening inward, except that “inward” is on the outside.

III. Type: FOTO2

The photocells are active only while the gate is opening; they do not respond while it is closing. This means that if the gate is opening and you interrupt the beam between the photocells, the gate will stop and start closing. If the gate is closed and you interrupt the beam, the gate will not open until you remove the obstruction from the beam between the photocells.

The safety circuit is not active by default. This feature is rarely used; for details, see Programming and setting up photocells active only while opening (FOTO2).

The only practical use is along the edge of an open gate leaf—for example, if the leaf opens close to a wall, to prevent someone from getting trapped there.

If you want to use multiple pairs of photocells with the same operating mode, connect the photocells in series.

Programming and setting up photocells active only while opening (FOTO2)

Write :)

Connecting photocells: one wired, one wireless (NICE FT210)

Connect NICE FT210 photocells to the NICE MC424LR10 control unit as follows:

  1. Disconnect the control unit from the power supply.
  2. Adjust the yellow jumpers 8-9-10-11 so that only 8-9 and 9-11 remain connected.
  3. Set the jumpers on the TX photocell as follows:
    • Jumper J1 - removed (if the photocells are more than 7 m apart, insert it)
    • Jumper J2 - removed
    • Jumper J3 - removed
  4. Set the jumpers on the RX photocell as follows:
    • Jumper J1 - removed
    • Jumper J2 - inserted
  5. Connect the wires as follows (photocell terminals numbered from top to bottom):
    • From terminal no. 7 (+24V) on the MC424LR10 control unit to terminal no. 10 (+24V) on the RX photocell
    • From terminal no. 6 (-0V) on the MC424LR10 control unit to terminal no. 9 (-0V) on the RX photocell
    • From terminal no. 10 (Photo) on the MC424LR10 control unit to terminal no. 1 (PHOTO) on the RX photocell
    • From terminal no. 8 (Common) on the MC424LR10 control unit to terminal no. 2 (COM) on the RX photocell
  6. Restore power to the control unit.

The LEDs on the RX photocell should be lit as follows (from left to right):
LED 1 - green, should be lit
LED 2 - red, should not be lit
LED 3 - yellow, should not be lit
LED 4 - red; the slower it flashes, the better the photocells can see each other; alternatively, refer to the diagnostic sequence